GE U ELECTRIC SUPPLY DELHI CANTT-10
Repair and maintenance of electrical breakdown including fault detection localisation and rectification in underground 11 KV LT Cable network OH Conductor and replacement to 11 KV HT Cable at Tigris MAP Sumran Line MAP Shekhawati Line Sanyat Line Mau
2020_MES_363542_1
GE ELECT/D-61/2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC SUPPLY DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹90,000
Yes
4 Sept 2020
30 Jul 2020
29 Aug 2020
31 Jul 2020
27 Aug 2020
22 Aug 2020
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified. Note : Measurement shall be taken after punning down.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
All as per srl item No 5 here-in-before but using old bricks obtained under srl item No 1 here in before.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm.
All as per srl item No 7 here-in-before but using old cable cove obtained under srl item No 1 here in before.
Supply, laying, jointing, testing and commissioning in replacment LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed. Cables of the following sizes:- Note Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately.
16 Sqmm 4 core
25 Sqmm 4 core
35 Sq mm 3.5 core.
50 Sq mm 3.5 core.
70 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
300 Sqmm 3.5 core
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches fixed to pole, including jointing & testing complete all as specified and directed of following sizes Note :- Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately.
95 sqmm 3 core.
120 sqmm 3 core.
185 sqmm 3 core
240 sqmm 3 core
300 sqmm 3 core
Supplying, laying, jointing testing and connecting in replacement HT cable, 11000 volts (E) grade, with Aluminum conductor of size 1000 Sqmm, single core, XLPE insulated, PVC sheathed, screened, Armoured with GI strip(Earthed), screened by a layer of extruded semi conducting cross linkable compound, copper tape, cross laid up with prefiller complete all as specified and directed.
Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 11 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Note: (a) 11 KV HT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable cable cover/bricks will be laid in trenches for cable protection. If extra PCC cover/bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
All as per item Ser No 12 above but 1100 Volt LT cables
Taking out faulty underground 1100 Volt LT cable of different sizes by excavation and removing bricks of any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required. Note: (a) 1100 Volt LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable bricks will be laid in trenches for cable protection. If extra bricks/PCC cable cover and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
All as per item Ser No 14 above but 11000 Volt HT cables
Material and labour disconnecting faulty /burnt end or portion of cable by removing the cable from loop including necessary excavation & earth work , suitable size of thimble LT tap , relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 25 Sqmm 3.5/4 core to 240 Sqmm 3.5 core of LT cable to LT Panel/pole/main switch complete all as directed.
Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade complete all as directed for the following sizes :-
25-50 Sqmm x 3.5 core/ 4 core
70-150 Sqmm x 3.5 core
185 -240 Sqmm x 3.5 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm, 3 core.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 1 core XLPE armoured aluminium conductor cable 1000 Sqmm
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 1 core XLPE armoured aluminium conductor cable 1000 Sqmm
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.6 mpa working pressure
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 to 150 mm bore and making good both ends all specified and directed
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of following bore sizes
Supply and fix in replacement air break switch gang operated tripple pole mechanically operated mechanism, switch air break gang operated mounted on 15 Nos insulator and steel frame with operating rod of 25 mm bore GI Pipe and locking arrangements worked from ground level for current rating 400 Amps, HT 11 KV grade including drop out fuses and necessary silver coper coating jumpers and making all electrical connections complete.
Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.10 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized iron strip 32 x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised ironside complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
M & L for 2 coat of aluminium painting over a coat of red oxide to steel surfaces of HT 4/6 pole sturcture (Angle Iron/MS channel /MS clamp etc) including preparation of old surface complete all as specified.
Material & Labour for replacement of jumper/bus bar made of ACSR conductor of existing size on HT Four/Six pole structure having 2/3 incoming/outoing feeder including bus bar with PVC sleeve , lugs , nut bolts and washers complete all as directed.
All as per Serial item No 29 here-in-before but 4/6 incoming/outoing feeder
S&F in replacement Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint on 4/6 pole 11 KV HT structure
M & L for cutting and removing grass, vegetation bushes etc from surrounding 4 pole/6 pole HT structure , outside area of HT installation and removing all rubbish to a distance not exceeding 50 m as directed.
Material and labour for sprading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surounding area of outdoor RMU manually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick watered and rammed to true surface all as specified and directed
Suplying and laying as replacement in sub station fixing 3.3 to 11 KV electrical insulation mat of size 5 mtr x 1 mtr x 2.5 mm thick specification as per IS 15652 2006
Supplying and fixing in replacement male contact/moving contact for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement female contact /fix contact jaw for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement tinned copper flexible jumper 200 Amp/400 Amp for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement MS jumper carrier for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement back connector plate for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement porcelain post insulator for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement drop out fuse element 5 to 25 Amp complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement drop out fuse element 50 Amp complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement drop out fuse element 60 Amp complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement drop out fuse element 100 Amp complete all as directed at site by Engr-in-charge.
S&F in replacement disc type insulator,porecelain, viterous 145mm high and 255mm dia ball and socket type , brown tow in series assembly for tension with tension clamps for conductors, working presseue 11000 volts complete all as specified and directed.
S&F in replacement pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers,nut size 150 mm height 150mm dia, 11000 volts grade complete all as specified and directed.
S&F in replacement for Danger Notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white , with letters, figures and conventional skull and bobes in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT, 25x20 cm size including taking down old one complete all as specified and directed.
S&F in replacement Lightening arrestors expulsion type with all fittings, transmission class, discharge capacity 10 kilo Amps suitable for 11000 volts complete as specified and directed.
Cutting of tree branches near/ over/under the OH conductor as directed to Engr-in-Charge.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
M/s Adhikari construction co.
M/s Birja Nand
ALLIED CONSTRUCTION
Buddham Builders
Rajindera Enterprises
DS CONSTRUCTION
Ridhi engineers and builders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .