Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹14.6 LAdmitted-Finance | -18.00% | ₹14.6 L | L1 | Admitted-Finance |
Tender Value
₹1.9 Cr
EMD Value
₹3.8 L
Closing Date
27 Feb 2026, 5:00 pmClosed
Executive Engineer
PWD Electrical Division II Jaipur
Rate Contract for Utility Shifting work under Jurisdication of Electrical Division II, Jaipur
2026_CEPWD_540156_3
EE_DIV2_NIT_51_2025_26
Open Tender
Electrical Works
365 days
Jaipur
Please refer tender documents
2 documents required · 2 mandatory
₹2,000
Through Egras Challan in Office ID 9284
₹3.8 L
Yes
In the Chamber of Executive Engineer
6 Mar 2026
19 Feb 2026
27 Feb 2026
19 Feb 2026
27 Feb 2026
19 Feb 2026
23 Feb 2026
Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required.
8.0 Mtr long of 200 Kg Working Load
9.0 Mtr long PCC pole of 200 Kg Working Load
9.0 Mtr long PCC pole of 400 Kg Working Load
11.0 Mtr long PCC pole of 400 Kg Working Load
Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as required.
Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm
Stay set of dia 16mm, 1.8m long stay rod and anchor plate 300 x 300 x 4.0 mm
Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom's specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required.
LT cross arm 600 mm long with clamp
LT cross arm 1200 mm long with clamp
Suspension clamp with eye hook & Pole clamp
Dead end clamp with eye hook & Pole clamp
Type A LT connector for Aerial bunched cable
Type B LT connector for Aerial bunched cable
Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom's standard specifications,suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required.
100 mm x 70 mm
Supply and fixing of LT porcelain shackle insulator as per IS:1443 1979 and as per Discom's standard specifications, suitable for working voltage 1100 volts including all accessories like GI Hardware fittings confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required.
75mm x 90mm
100mm x 110mm
Supplying and drawing Aluminium conductor steel reinforced (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required.
30 Sqmm of (6+1) 2.59mm (Weasel)
50 Sqmm of (6+1) 3.35 mm (Rabbit)
50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT
80 Sqmm of (6+1) 4.09 mm (Raccon)
100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog)
ACSR Panther Aluminium 30/3 MM
AAA Conductor (Equivelent size Weasel)
Supply and fixing of 'V' type cross arms with clamps as per latest Discom specifications made of MS angle (65X65X6)on the existing poles complete including all necessary nut and bolt, clamps with two coats of Red oxide and two coats of Aluminium paint etc. as required.
Supply and fixing of Galvanised steel 'V' type cross arms with clamps as per latest Discom specifications made of Galvanised steel angle(65x65x6) on the existing poles complete including all necessary nut and bolt, clamps as required.
Supply and fixing of top hamper on the existing pole as per latest Discom specifications complete including nut bolts with two coats of Red oxide and two coats of Aluminium paint etc as required.
Vertical type
11 kV (.7m long) (65 x 65 x6mm angle)
11 kV(50 x 6 mm flat)
Horizontal type
11 kV (65 x 65 x6mm angle)
11 kV with double top hamper (65 x 65 x 6mm angle)
Supply and fixing of Galvansied top hamper on the existing pole as per latest Discom specifications complete including nut bolts etc as required.
Vertical type
11 kV (.7m long) (65 x 65 x6mm Galvanised Steel angle)
11 kV(50 x 6 mm Galvanised steel flat)
Horizontal type
11 kV (65 x 65 x6mm Galvanised Steel angle)
11 kV with double top hamper (65 x 65 x 6mm Galvanised Steel angle)
Supply and fixing of MS. Channel Bracket 100 mm x 50 mm with clamp as per Discom Specifications including Nut, Bolt with two coats of Red oxide and two coats of Aluminium paint etc. as required.
1.8 Mtr. Long
1.4 Mtr. Long
Supply and fixing of galvanized steel Channel Bracket 100 mm x 50 mm with clamp as per Discom Specifications including Nut, Bolt with two coats of Red oxide and two coats of Aluminium paint etc. as Required.
1.8 Mtr. Long
1.4 Mtr. Long
Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required.
Supply and fixing of 11kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required.
B & S type hardware 45 KN
T & C type hardware 45 KN
B & S disc insulator 45 KN
T & C disc insulator 45 KN
Supply and fixing of PG / T clamps on overhead lines/jumpers, made of aluminium alloy 4600 of IS 617-1994 (with latest amendment if any) with steel nut and bolts conforming to IS 1363-1992 & IS 1367/1979-80 (with latest amendments if any) all ferrous metal parts intended for outdoor use except those made of stainless steel shall be protected by hotdip galvanising in accordance with IS 2633-1986 complete in all respect as required.
PG Clamp for Panther Conductor
PG Clamp for Dog Conductor Type - A
PG Clamp for Weasel Conductor
PG Clamp for Rabbit Conductor
T Clamp for Panther Conductor
Supplying and laying of Hot dip galvanized steel stay wire of 550-900 N/mm Quality confirming to IS-2141/2000 in all respect Including chemical composition (Heavily coated Hard quality) of dia 7/3.15 mm(7/10 SWG) and as per latest Discom specs. etc. as required.
Supply and fixing of 11 / 33. KV Stay insulator as per IS:5300/1969 and as per Discom's standard specifications etc. as required.
110 x 75 x 22mm 11 KV Stay Insulator
140 x 85 x 25mm 33 KV Stay Insulator
Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. of outgoing.
200 Amp. LT Distribution Kiosk for 63/100 KVA Transformer
400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer
100 Amp. Distribution Kiosk of Size 500mm x 550 mm x 700 mm suitable for Underground cable
Supply and fixing of 11 KV Outdoor 4 way feeder pillar Box confirming to Discom specifications and made of 3.15 mm thick powder coated CRCA sheet enclosure confirming to IS 14772/IEC 60670 (1989) of Size 1000 mm x 1000 mm x 1500 mm, Both front and rear doors should have 3 heavy duty M.S. hinges with Brass pin inserted inside and locking arrangements.The bottom foundation frame stand should be made from 65x65x6mm MS Angle with four legs of 200mm height provided with 150x150x6mm flats grouted with C.C. of M-10 grade to achieve the height of 2.0 feet above the road level suitable for four outgoing.
Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required.
Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required.
Supply and fixing of distribution type Lightening arrestor ( Set of 3 Nos.) 9 kV, 10 kA (IS:3070) with mounting breaking to be installed on existing DP structure etc. as required.
Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double pole as per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required.
Supply and fixing of 1.6 mm thick MS 11 kV Danger plates as per IS :2551-1982 & specification of Discom on the existing poles complete in all respectas as required.
Providing and fixing of single pole mounted substation structure set for isolator / single phase transformer as per DISCOM specification complete in all respect with nuts and bolts as required MS flat 50 x 6mm, MS angle 65 x 65 x6mm, MS channel 100 x 50 x 6mm. ( Excluding cost of pole ). Etc. as required.
Supply and erection of RS joist of 116 x 100 mm, 11 Meter long with the welded/ bolted top hamper 65 x 65 x 6mm (0.7 Mtr long) making necessary arrangement for fixing 11 kV 'V' cross arm, LT bracket and guard wire bracket, grouted in ground 1/6 th of its length and fixed with cement, coarse and grit in 1:3:6 ratio in 1/5th of its length (40cm dia) from the bottom including two coats of aluminium paint over the complete length of joist etc. as required. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra)
Supplying and drawing of XLPE insulated LT Aluminum conductor Aerial bunched cable confirming to IS 14255/1995 and IS 398 (Pt-4)/ 1994 and as per Discom Specs. on existing cross arms through I hook with all necessary T&P required including binding and twisting etc. complete in all respect as required.
1 X 25 sq. mm. + 1X25 sq. mm. (Bared)
1 X 25 sq. mm. + 1X25 sq. mm. (insulated)
3 X 16 sq. mm. + 1X25 sq. mm. (Bared)
3 X 16 sq. mm. + 1X25 sq. mm. (insulated)
3 X 25 sq. mm. + 1X25 sq. mm. (Bared)
3 X 25 sq. mm. + 1X25 sq. mm. (insulated)
3 X 50 sq. mm. + 1X35 sq. mm. (Bared)
Supply & Erection of M S lattice structure of height 12.8 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of Aluminium paint after erection work completed as per technical specifications & drawing of DISCOM. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra).
Supply & Erection of Galvanised steel lattice structure of height 12.8 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make, all completed as per technical specifications & drawing of DISCOM. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra).
Supply & Erection of M S lattice structure of height 11.0 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of Aluminium paint after erection work completed as per technical specifications & drawing of DISCOM. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra)
Supply & Erection of Galvanised steel lattice structure of height 11.0 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make,all completed as per technical specifications & drawing of DISCOM. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra)
Supply of Fabricated 33 KV of 'V' type cross arms made of MS angle(75x75x6 mm) with clamp etc as per Discom specifications on the existing poles complete including all necessary nut and bolt etc with clamps including two coats of Red oxide and two coats of Aluminium paint etc. as required.
Supply of Fabricated 33 KV of 'V' type cross arms made of Galvanised steel angle (75x75x6 mm) with clamps etc on the existing poles complete including all necessary nut and bolt etc with clamps as required.
Supply and fixing of top hamper as per Discom specifications on the existing pole complete including nut bolts etc as required. Vertical type 33 kV. 0.75mtr. IS 75x75x6mm as per tech specs. Of DISCOM (Steel weight 6.5Kg. Approx. per top hamper).
Supply and fixing of Galvanised steel top hamper as per Discom specifications on the existing pole complete including nut bolts etc as required. Vertical type 33 kV. 0.75mtr. IS Galvansied angle 65x65x6mm as per tech specs. Of DISCOM (Steel weight 5.8Kg. Approx. per top hamper).
Supply & Erection of special stud structure for 33KV lattice structure as per Discom specifications made of M.S. angle, channer, flats complete in all respects with bracings including painting of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of Aluminium paint after erection work completed as per technical specifications & drawing of DISCOM. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra).
Supply and fixing of 33 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required.
Supply and fixing of 33kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required.
B & S type hardware 120KN
B & S disc insulator 120KN
Supply and fixing of guard bracket 2.2 mtr. long made from (75x40) ISMC 7.14Kg. Per Mtr. M.S. channel including necessary clamp and botls etc. as per technical specification & drawing of DISCOM.
Supply and fixing M.S. channel (cut point) 100x50mm ISMC (9.5Kg. Per Mtr.) 2x1.8mtr. long with pilot patti 50x6mm thick necessary nuts and bolts etc. as per technical specification & drawing of DISCOM.
Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. complete as per technical specification of DISCOM.
Labour charges for Dismantling the structure with pole mounted transformer of different capacity along with distribution boards and re- erecting the transformer on newly erected structure along with distribution boards and including testing and commissioning (as well as cabling connection complete as required)
Labour charges for dismantling of existing PCC/MS electrical Pole including MS channel, V cross arm, 11KV insulator, LT insulator, guard wires, stay wires, one span of ACSR conductors and other electric items, coming along and in the alignment of the road, then removal and re-rolling of the PCC /MS Pole as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge, clean the site good as per the requirement and dismantle material receipt duly signed by DISCOM Engineer submit the receipt to EIC as required.
Labour charges for dismantling of existing Lattice tower including MS channel, V cross arm, 11KV/33 KV insulator, guard wires, stud/stay wire, one span of ACSR conductor and other electric items coming along and in the alignment of the road, then removal and re-rolling of Lattice tower as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from DISCOM/ concering authority complete as required.
Labour charges for dismantling of existing street light electrical pole with street light fixture, underground cable, MS box and other electric items of the pole coming along and in the alignment of the road, then removal and re- rolling of MS/PCC pole of different sizes as well as other materials and handing over the same to DISCOM/UIT/MC store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from concering authority complete as required.
Labour charges for dismantling of service line connection (weather proof cable/armoured cable) for single phase /three phase supply of industrial/domestic connections from existing PCC/MS pole and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and provide temporary supply to domestic/industrial connections to the consumer where supply is disconnected and clean the site good as per the requirement and direction of Engineer Incharge complete as required.
Labour charges for Trimming of tree branches/plants and prepairing route approaches for electric proposed line complete with prior permission of local authority in writing , taking proper shutdown from discom office and inform to DISCOM after complete the work.
Providing & Laying XLPE insulated & P.V.C. sheathed Un-Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing commissioning etc. as required of following size.
Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size.
Providing & Laying XLPE insulated & P.V.C. sheathed Un-armoured Copper cable confirming to IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing commissioning etc. as required of following size.
Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size.
Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth.
Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same
Excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 100 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically (Longest side is vertical to cable) along the cable , (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same
Add Extra in item no. 11.1 to 11.4 for Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Up to 35 Sq.mm fixed with 25 mm x 2 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
Above 35 sq. mm and upto 95 sq. mm fixed with 40 mm x 3 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
Above 95 sq. mm and upto 185 sq. mm fixed with 40 mm x 4 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
Above 185 sq. mm and upto 400 sq. mm fixed with 50 mm x 5 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.
2 x 4.0 sq.mm
2 x 6.0 sq.mm
2 x 10.0 sq.mm
2 x 16.0 sq.mm
2 x 25.0 sq.mm
2 x 35.0 sq.mm
2 x 50.0 sq.mm
2 x 70.0 sq.mm
3 x 4.0 sq.mm
3 x 6.0 sq.mm
3 x 10.0 sq.mm
3 x 16.0 sq.mm
3 x 25.0 sq.mm
3 x 35.0 sq.mm
3 x 50.0 sq.mm
3 x 70.0 sq.mm
3.5 x 25.0 sq.mm
3.5 x 35.0 sq.mm
3.5 x 50.0 sq.mm
3.5 x 70.0 sq.mm
3.5 x 95.0 sq.mm
3.5 x 120.0 sq.mm
3.5 x 150.0 sq.mm
3.5 x 185.0 sq.mm
3.5 x 240.0 sq.mm
3.5 x 300.0 sq.mm
3.5 x 400.0 sq.mm
3.5 x 500.0 sq.mm
3.5 x 630.0 sq.mm
4 x 4.0 sq.mm
4 x 6.0 sq.mm
4 x 10.0 sq.mm
4 x 16.0 sq.mm
1 x 70.0 sq.mm
1 x 95.0 sq.mm
1 x 120.0 sq.mm
1 x 150.0 sq.mm
1 x 185.0 sq.mm
1 x 240.0 sq.mm
1 x 300.0 sq.mm
1 x 400.0 sq.mm
1 x 500.0 sq.mm
1 x 630.0 sq.mm
1 x 800.0 sq.mm
1 x 1000.0 sq.mm
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty Copper lugs (IS 8337- 1976) duly crimped with crimping tool, PVC tape for following size of PVC insulated & PVC sheathed/ XLPE copper conductor cable of 1100 volt grade as required.
1 x 16.0 sq.mm
1 x 25.0 sq.mm
1 x 35.0 sq.mm
1 x 50.0 sq.mm
1 x 70.0 sq.mm
1 x 95.0 sq.mm
1 x 120.0 sq.mm
2 x 4.0 sq.mm
2 x 6.0 sq.mm
2 x 10.0 sq.mm
2 x 16.0 sq.mm
2 x 25.0 sq.mm
2 x 35.0 sq.mm
2 x 50.0 sq.mm
2 x 70.0 sq.mm
2 x 95.0 sq.mm
2 x 120.0 sq.mm
3 x 1.5 sq.mm
3 x 2.5 sq.mm
3 x 4.0 sq.mm
3 x 6.0 sq.mm
3 x 10.0 sq.mm
3 x 16.0 sq.mm
3 x 25.0 sq.mm
3 x 35.0 sq.mm
3 x 50.0 sq.mm
3 x 70.0 sq.mm
3 x 95.0 sq.mm
3 x 120.0 sq.mm
4 x 1.5 sq.mm
4 x 2.5 sq.mm
4 x 4.0 sq.mm
4 x 6.0 sq.mm
4 x 10.0 sq.mm
4 x 16.0 sq.mm
4 x 25.0 sq.mm
4 x 35.0 sq.mm
4 x 50.0 sq.mm
4 x 70.0 sq.mm
4 x 95.0 sq.mm
4 x 120.0 sq.mm
6 x 1.5 sq.mm
6 x 2.5 sq.mm
8 x 1.5 sq.mm
8 x 2.5 sq.mm
10 x 1.5 sq.mm
10 x 2.5 sq.mm
12 x 1.5 sq.mm
12 x 2.5 sq.mm
Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size.
Supplying and making end termination with heavy duty Copper lugs ( ANY type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size.
Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.
100mm x 50mm x 1.6mm
150mm x 50mm x 1.6mm
225mm x 50mm x 1.6mm
300mm x 50mm x 1.6mm
375mm x 50mm x 2.0mm
450mm x 50mm x 2.0mm
600mm x 50mm x 2.0mm
300mm x 62.5mm x 2.0mm
375mm x 62.5mm x 2.0mm
450mm x 62.5mm x 2.0mm
600mm x 62.5mm x 2.0mm
750mm x 62.5mm x 2.0mm
600mm x 75mm x 2.0mm
750mm x 75mm x 2.0mm
Supply, Fabricating & installing following sizes of perforated Powder coated MS cable tray with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.
100mm x 50mm x 1.6mm
150mm x 50mm x 1.6mm
225mm x 50mm x 1.6mm
300mm x 50mm x 1.6mm
375mm x 50mm x 2.0mm
450mm x 50mm x 2.0mm
600mm x 50mm x 2.0mm
300mm x 62.5mm x 2.0mm
375mm x 62.5mm x 2.0mm
450mm x 62.5mm x 2.0mm
600mm x 62.5mm x 2.0mm
750mm x 62.5mm x 2.0mm
600mm x 75mm x 2.0mm
750mm x 75mm x 2.0mm
Supply, Fabricating & installing following sizes of Hot dipped Galvanized iron Ladder type cable tray ( Galvanized thickness not less then 50 microns) with rungs at span of 250mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with M.S. suspenders etc. as required.
100mm x 50mm x 1.6mm
150mm x 50mm x 1.6mm
225mm x 50mm x 1.6mm
300mm x 50mm x 1.6mm
375mm x 50mm x 2.0mm
450mm x 50mm x 2.0mm
600mm x 50mm x 2.0mm
300mm x 62.5mm x 2.0mm
375mm x 62.5mm x 2.0mm
450mm x 62.5mm x 2.0mm
600mm x 62.5mm x 2.0mm
750mm x 62.5mm x 2.0mm
600mm x 75mm x 2.0mm
750mm x 75mm x 2.0mm
Supplying and fixing of CE certified and UL listed GI wire mesh cable tray made from spot welded steel wire hot dipped galvanised between 60 and 80 microns of zinc as per BS 729 including horizontal and vertical bends, reducers, tees, cross members and other OEM made accessories like wall clamp, hold down clamps, Earthing terminal, brackets as required, and duly suspended from the ceiling with electro-zinc coated TF rods, etc. as required of following sizes.
100 mm x 50 mm x 3.5 - 5.9 mm
150 mm x 50 mm x 3.5 - 5.9 mm
200 mm x 50 mm x 3.5 - 5.9 mm
300 mm x 50 mm x 3.5 - 5.9 mm
400 mm x 50 mm x 3.5 - 5.9 mm
500 mm x 50 mm x 3.5 - 5.9 mm
100 mm x 100 mm x 3.5 - 5.9 mm
150 mm x 100 mm x 3.5 - 5.9 mm
200 mm x 100 mm x 3.5 - 5.9 mm
300 mm x 100 mm x 3.5 - 5.9 mm
400 mm x 100 mm x 3.5 - 5.9 mm
500 mm x 100 mm x 3.5 - 5.9 mm
Supply and fixing following size of Pre Galvanized (275 GSM) floor raceways / Under floor trunking with/ without partion, including common cover, joint sleeve, cross over junction Box etc. as required.
75 mm x 25 mm x 1.5 mm
100 mm x 25 mm x 1.5 mm
150 mm x 25 mm x 1.5 mm
250 mm x 25 mm x 1.5 mm
300 mm x 25 mm x 1.5 mm
75 mm x 38 mm x 1.5 mm
100 mm x 38 mm x 1.5 mm
150 mm x 38 mm x 1.5 mm
250 mm x 38 mm x 1.5 mm
300 mm x 38 mm x 1.5 mm
150 mm x 38 mm x 2.0 mm with 2 Compartment
250 mm x 38 mm x 2.0 mm with 3 Compartment
300 mm x 38 mm x 2.0 mm with 3 Compartment
Supply and fixing following Pre Galvanized (275 GSM) Adjustable Junction Box for floor raceways / Under floor trunking etc. as required.
Junction Box 200 mm x 200 mm x 40-75 mm with Galvanized Lid
Junction Box 250 mm x 250 mm x 40-75 mm with Galvanized Lid
Junction Box 300 mm x 300 mm x 40-75 mm with Galvanized Lid
Junction Box 350 mm x 350 mm x 40-75 mm with Galvanized Lid
Junction Box 250 mm x 250 mm x 40-75 mm with stainless steel Lid
Junction Box 300 mm x 300 mm x 40-75 mm with stainless steel Lid
Junction Box 350 mm x 350 mm x 60-120 mm with stainless steel Lid
S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required.
1 x 25 sq.mm-50 sq.mm
1 x 70 sq.mm-150 sq.mm
1 x 185 sq.mm-300 sq.mm
1 x 400 sq.mm
1 x 500 sq.mm
1 x 630 sq.mm
1 x 800 sq.mm
1 x 1000 sq.mm
2 x 1.5 sq.mm-6 sq.mm
2 x 10.0-16.0 sq.mm
2 x 25.0 sq.mm-50 sq.mm
2 x 70.0 sq.mm-150 sq.mm
2 x 185.0 sq.mm-300 sq.mm
2 x 400 sq.mm
2 x500 sq.mm
3/3.5/4 x 1.5 sq.mm-6 sq.mm
3/3.5/4 x 10.0-16.0 sq.mm
3/3.5/4 x 25.0 sq.mm-50 sq.mm
3/3.5/4 x 70.0 sq.mm-150 sq.mm
3/3.5/4 x 185.0 sq.mm-300 sq.mm
3/3.5/4 x 400 sq.mm
3/3.5/4 x500 sq.mm
S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required
P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra).
Providing and laying Non Pressure NP-3 class R.C.C. pipes confirming to IS:458 including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra).
200 mm Dia.
250 mm dia.
300 mm dia
450 mm dia.
labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.:
All kind of Soils
Hard Rocks
Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size.
3 core 95.0 Sq.mm
3 core 120.0 Sq.mm
3 core 150.0 Sq.mm
3 core 185.0 Sq.mm
3 core 240.0 Sq.mm
3 core 300.0 Sq.mm
Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 33 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size.
3 core 150.0 Sq.mm
3 core 185.0 Sq.mm
3 core 240.0 Sq.mm
3 core 300.0 Sq.mm
Excavation of trench of size 120 cm (Depth) x 35 cm(Width) for Laying of suitable no. of HT cable( Inter spacing between cables should not be less than 2 D) in ground with following procedure:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same
Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level. (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
Add Extra in Item no. 13.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes.
11 KV End Termination Kit Indoor type
3 core up to 35 Sqmm
3 core 50/70/95 Sq.mm
3 core 120/150/185 Sq.mm
3 core 240/300 Sq.mm
3 core 400 Sq.mm
11 KV End Termination Kit Outdoor type
3 core up to 35 Sqmm
3 core 50/70/95 Sq.mm
3 core 120/150/185 Sq.mm
3 core 240/300 Sq.mm
3 core 400 Sq.mm
11 KV Straight Through Joint Kit
3 core up to 35 Sq.mm
3 core 50/70/95 Sq.mm
3 core 120/150/185 Sq.mm
3 core 240/300 Sq.mm
3 core 400 Sq.mm
33 KV End Termination Kit Indoor type
3 core 95 Sq.mm
3 core 120/150/185 Sq.mm
3 core 240/300/400 Sq.mm
33 KV End Termination Kit Outdoor type
3 core 95 Sq.mm
3 core 120/150/185 Sq.mm
3 core 240/300/400 Sq.mm
33 KV Straight Through Joint Kit
3 core 95/120/150 Sq.mm
3 core 185/240/300 Sq.mm
3 core 400 Sq.mm
Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required.
Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required.
Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required.
SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
(e) Testing of earth resistance for value of 5 ohms or less as required.
(f) Test certificates for confirming above standards from OEM is mandatory.
17.2 mm thick and 3 Mtr. Long
25 mm thick and 3 Mtr. Long
SITC of Strip in Pipe Earthing using hot-dip galvanized 'B' class G.I. pipe, as secondary conductor. The system shall incorporate a crystalline conductive compound between the primary and secondary conductors to enhance conductivity and long-term stability. of following size and length and as per point mentioned (a), (b), [c), (d), (e) (f) as below
(a) Bore a hole of dia. 150 mm of required length, Place the rod in the centre of Hole
(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 30 kg for 3000 mm. 20 Kg. for 2000 mm The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
© Connect the Strip Terminal (110 mm long) with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
(e) Testing of earth resistance for value of 5 ohms or less as required.
(f) Test certificates for confirming above standards from OEM is mandatory.
Outer Pipe - 76 mm dia GI pipe , Inner Conductor- GI strip 50x6 mm Length 3meter. Terminal 50x6mm GI.
Outer Pipe - 76 mm dia GI pipe , Inner Conductor- GI strip 50x6 mm Length 2 meter.Terminal 50x6mm GI.
Outer Pipe - 76 mm dia GI pipe , Inner Conductor- Copper strip 25x3 mm Length 3meter. Terminal 50x6mm Copper.
Outer Pipe - 76 mm dia GI pipe , Inner Conductor- Copper strip 25x3 mm Length 2 meter.Terminal 50x6mm Copper.
Outer Pipe - 56 mm dia GI pipe , Inner Conductor- GI strip 25x3 mm Length 3meter. Terminal 40x5 mm GI.
Outer Pipe - 56 mm dia GI pipe , Inner Conductor- GI strip 25x3 mm Length 2 meter. Terminal 40x5 mm GI.
Outer Pipe - 56 mm dia GI pipe , Inner Conductor- Copper strip 25x3 mm Length 3meter. Terminal 40x5 mm Copper.
Outer Pipe - 56 mm dia GI pipe , Inner Conductor- Copper strip 25x3 mm Length 2 meter. Terminal 40x5 mm Copper.
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.
20mm x 3mm copper strip
25mm x 3mm copper strip
25mm x 5mm copper strip
30mm x 5 mm copper strip
40mm x 6mm copper strip
50mm x 6mm copper strip
20mm x 3mm tinned copper strip
25mm x 3mm tinned copper strip
25mm x 5mm tinned copper strip
30mm x 5 mm tinned copper strip
40mm x 6mm tinned copper strip
50mm x 6mm tinned copper strip
20mm x 3mm G.I. ( Hot Dipped ) Strip
25mm x 3mm G.I. ( Hot Dipped ) Strip
25mm x 6mm G.I. ( Hot Dipped ) Strip
32mm x6mm G.I. ( Hot Dipped ) Strip
50mm x 6mm G.I. ( Hot Dipped ) Strip
Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required.
6 SWG tinned copper Wire
8 SWG tinned copper Wire
10 SWG tinned copper. Wire
6 SWG copper Wire
8 SWG copper Wire
10 SWG copper. Wire
6 SWG G.I. ( Hot Dipped ) Wire
8 SWG G.I. ( Hot Dipped ) Wire
10 SWG G.I. ( Hot Dipped ) Wire
16 Sq.mm Copper coated steel stranded conductor (Wt. 130 Kg/Km)
25 Sq.mm Copper coated steel stranded conductor ( Wt. 200Kg/Km)
Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra)
15 mm dia.
20 mm dia.
25 mm dia.
32mm dia
40 mm dia.
50 mm dia.
65 mm dia.
80 mm dia.
100 mm dia.
150 mm dia.
Mesh earthing as per IS:3043 with Hot dipped galvanized earth strip of size 25 mm x 6 mm to form a mesh of size 1000 mm x 1000 mm in horizontal formation to create equal sections of 200 mm x 200 mm by means of welding and embodying 1 mtr. Below the ground level, refilling the pit by alternative layers of charcoal & salt up to 500 mm with 20 mm dia. GI 'B' class watering pipe, wire mesh funnel and 300 mm x 300 mm size masonary chamber with lockable 6 mm thick MS sheet cover hinged with suitable angle iron frame testing of earth resistance for value of 5 ohms or less as required.
P & F of Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
S & F of Earth Bar with Disconnecting link Made out from 50 mm x 6 mm copper purity purity >95% /GI strip pre fitted on epoxy powder coated metal base mounted on hexagonal SMC Insulators of following Size.
400 mm , 6 Way Copper
600 mm , 10 Way Copper
400 mm , 6 Way GI
600 mm , 10 Way GI
Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass with suitable lenses on LED / integrated lens diffuser to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated metal case potted driver as a unique BIS R number (as per IS 15885) having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate(Fitting & driver both have separate BIS R number). The System level Luminaire efficacy >=130 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , LED driving output current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K as required.
High Power LED Flood Light Minimum lumen outpu 3900 lm
High Power LED Flood Light Minimum lumen output 6500 lm
High Power LED Flood Light Minimum lumen output 10400 lm
High Power LED Flood Light Minimum lumen output 13000 lm
High Power LED Flood Light Minimum lumen output 15600 lm
High Power LED Flood Light Minimum lumen output 19500 lm
High Power LED Flood Light Minimum lumen output 23400 lm
High Power LED Flood Light Minimum lumen output 26000lm
High Power LED Flood Light Minimum lumen output 32500 lm
High Power LED Flood Light Minimum lumen output 39000 lm
High Power LED Flood Light Minimum lumen output 45500 lm
High Power LED Flood Light Minimum lumen output 52000 lm
High Power LED Flood Light Minimum lumen output 65000 lm
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing and secondary lens on each LED/ integrated lens diffuser without cover & should be High power LED of 3 to 5 watt each . The System efficacy >=135 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required.
LED Street Light fixture with Minimum lumen output 2700 lm
LED Street Light fixture with Minimum lumen output 4050 lm
LED Street Light fixture with Minimum lumen output 6075 lm
LED Street Light fixture with Minimum lumen output 8100 lm
LED Street Light fixture with Minimum lumen output 9450 lm
LED Street Light fixture with Minimum lumen output 12150 lm
LED Street Light fixture with Minimum lumen output 13500 lm
LED Street Light fixture with Minimum lumen output 16200 lm
LED Street Light fixture with Minimum lumen output 20250 lm
LED Street Light fixture with Minimum lumen output 24300 lm
LED Street Light fixture with Minimum lumen output 28350 lm
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required.
LED Street Light fixture with Minimum lumen output 2500 lm
LED Street Light fixture with Minimum lumen output 3750 lm
LED Street Light fixture with Minimum lumen output 5625 lm
LED Street Light fixture with Minimum lumen output 7500 lm
LED Street Light fixture with Minimum lumen output 8750 lm
LED Street Light fixture with Minimum lumen output 11250 lm
LED Street Light fixture with Minimum lumen output 12500 lm
LED Street Light fixture with Minimum lumen output 15000 lm
LED Street Light fixture with Minimum lumen output 18750 lm
LED Street Light fixture with Minimum lumen output 22500 lm
LED Street Light fixture with Minimum lumen output 26250 lm
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
Tendernotice_2.pdf
PDF • 8.54 MB
condition3.pdf
Tender Documents • 0.03 MB
BOQ_963001.xls
BOQ • 1.22 MB
Download all tender documents and submit your bid