Construction of proposed OPD complex and Surgical ward with OT complex at Chandannagar S.D. Hospital, Hooghly (RN-18000145) --- Arrangement of Air-Conditioning System.
2022_WBPWD_380165_1
WBPWD/SEWEC /HED /NIQ-40 /2021-22_2nd call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Chandannagar
Please refer Tender documents.
5 documents required · 5 mandatory
₹44,000
Office of the Superintending Engineer, Western Ele
7 Jul 2022
12 May 2022
15 Jun 2022
12 May 2022
13 Jun 2022
14 May 2022
12 May 2022 - 13 May 2022
13 May 2022
Amount
Supply of 5.0 ton capacity concealed type Split AC of rated cooling capacity-60000 BTU/hr. with 2 nos. twin rotary compressor, 2 nos. IDU of rated power supply- 230V-1Ph- 50 Hz., 1 no. ODU of rated power supply- 400V-3Ph- 50 Hz. Air-flow/per IDU :- 1000 CFM. (Make: Hitachi /O general/ Mitshubishi )
Erection and commissioning charges for the above-said 5.0 TR ton Concealed type Split Air Conditioner
Charges for scaffolding arrangement incl. lifting, shifting for outdoor & indoor units of 5.0 TR Concealed type Split Air Conditioner machine
Supplying, fabrication & fixing M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making platform for installation of outdoor unit of 7.5 Concealed split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 50 mm x50mm x 6 mm in each platform. The platform should be baricaded & safe for ODU Maintenance in outer edge for transmitting the load centrally through 2 nos. (50 mm x 50 mm x 6 mm) Angle of 2 mtr. length each inserted into the exiting wall. Area of the platform is 3Mtr. x 1.2Mtr. or as per Machine configuration & load with adequate service access as per direction of EIC.
Supplying, fabrication & fixing M.S frame made with 2 Nos. angle size (40mm x 40mm x 6mm) of 1mtr. length tied by 25mm x 25mm x 6mm angle of 1100mm length for installation of indoor unit of Concealed Split AC incl. drilling 2 nos holes in each Angle, cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. Area of the frame as follows:- i) 1 mtr. x 1.1 mtr.
Supply, installation & commissioning Copper Refrigeration pipe line for liquid and suction line with supports & brackets (For concealed split AC)
a) Liquid Line (3/8" OD HD Copper Pipe with 0.6mm thick)
b) Suction line (5/8" OD HD Copper Pipe with 0.7mm thick)
Supply & Fixing Pipe Insulation in suction & liquid line with 9mm nitrile rubber tube for Concealed Split AC
Liquid Line
Suction Line
Supply & laying 1.1 Kv grade PVC insulated FRLS control copper cable for interconnection between ODU unit to IDU unit of Concealed Split AC
3 Core 2.5sq. mm. Communication Cable
Supply and fixing of Al powder coated continuous Grill. (Make: Premier or equivalent)
Supply & laying Drain Water piping work out of PVC / HDPE hard pipes of following sizes incl. fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchors.
a) 25 mm dia
b) 40 mm dia
Supply and fixing flexible canvass connection for concealed split air-conditioners.
For 5.0 ton
Supply, cutting & fixing drop ceiling made of Gypsum & E-board to cover the indoor units of concealed split unit incl. Painting the board as per direction of E.I.C.
Arrangement of Trap Door made of Aluminium Channel & Fire Retardant PVC Board for maintenance of IDU units
Supply of 3 Star rated 2.0 ton capacity split Air-conditioner machine fitted with Rotary compressors suitable for Refrigerant-R32/R410A. (Make- Hitachi, Model- Logicool 3100f or equivalent model of O-General/Daikin ).
Supply of 3 Star rated 1.5 ton capacity split Air-conditioner machine fitted with Rotary compressors suitable for Refrigerant-R32/R410A. (Make- Hitachi, Model- Logicool 3100f or equivalent model of O-General/Daikin ).
Installation, testing & commissioning of the above-said split AC incl. Supply & fixing required Angle Iron Structure on wall & mending works as per direction of E.I.C.
Supply & Laying Extra Add-on items- 5/8"(for suction) & 1/4"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation, 4 core x 2.5 sq.mm. copper cable incl. fixing arrangement and wrapping insulation of aerotape complete in all respect for 1.5/2.0 TR A.C. Machine. and Supply & laying PVC Drain Pipe 25mm dia by saddling on wall incl. PVC "T", elbow, bend etc as per direction of E.I.C.
SITC of 10 KVA true on-line double conversion UPS with three phase in / three phase out with battery backup for one hour (minimum 15600 VAH Flame retardent battery) as per details annexure enclosed. (with 2 years warranty incl. Battery). [Factory testing is essential before despatch]. [Make : Numeric / Emerson / APC/ Schneider /AVO Switiching ]
Topology: IGBT BASED DSP CONTROLED
Rating of UPS(KVA/KW): 10 KVA / 9 KW
Input Frequency: 45 to 65 Hz
Input PF: 0.99 with IGBT Rectifier
Isolation Transformer: Delta to Star Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided . No external/Step up Transformer will be accepted
Back feed Protection: UPS should have back feed protection
DC Ripple: Residual ripple Voltage should be <1%
Charging: Automatic float cum Boots Charging Capability with setteble float & boost charging voltages and current levels and boots charger timer
Input current Distortion: THDi<=5%
Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3%
Output Frequency: 50 Hz +/- 0.1%
Output Power Factor: 0.9
Crest Factor: 3:1
THDu: < 2% (linear load), < 5%(non linear load)
Waveform: Pure Sine Wave
Birdge: Microprocessor based and IGBT Technology
Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute.
Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms
Overall Efficiency: 94%
Battary Cabinet: With power coated MS angle with MS sheet suitable dimention and gadge, well air ventilation to ensure the battery optimum life cycle.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary accessories.
Battery : 12 V, Mono Block batteries. SMF VRLA
DC Bus : Minimum 192V or above, 60 mim back up required (Minimum 15600 VAH) Battery. Battery Make: Exide/Amara Raja(Quanta)
Protections: Input & Output Over / Under Voltage, Single Phasing DC - High / Under Voltage, Battery Charging Over Current, Output Overload / Short Circuit / Over Temp., UPS auto ON on Mains recovery
Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip
Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current
Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current
Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch
Termination: Input, Battery, Output & Bypass
Enclosure: IP 20
Operating Temp: 0 to 40 Deg C
Humidity: Upto 95% Rh (non-condensing)
Cooling: Forced Air
Noise: < 70 dB
Cold Start : Provided
Parallel Redundant facitities should be present for each unit with Accessories
Communication: RS 232, RS 485, Dry contact ,LED indication
Monitoring Software: UPS Monitoring Software on Windows XP Platform
Certification : ISO 9001: 2008, ISO 14001: 2004, ISO 18001, RoHS and OHSAS 18001
CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture)
MAXCOOL REFRIGERATION CO.
P. M. COOLING AND ENGINEERING CO
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .