| 1 | L1₹22.4 LAccepted-AOC 307 SADAR BAZAR LUCKNOW UP 226002 | LUCKNOW | UTTAR PRADESH | 226002 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹23.5 L+₹29,225 (1.26%)Rejected-Finance | L2 | Rejected-Finance Not Being Lowest Bidder | |
| 3 | L3₹25.9 L+₹2.6 L (11.3%)Rejected-Finance | L3 | Rejected-Finance Not Being Lowest Bidder | |
| 4 | L4₹26.9 L+₹3.7 L (15.7%)Rejected-Finance | L4 | Rejected-Finance Not Being Lowest Bidder | |
| 5 | L5₹29.7 L+₹6.5 L (27.8%)Rejected-Finance | L5 | Rejected-Finance Not Being Lowest Bidder |
Tender Value
Refer Docs
EMD Value
₹79,400
Closing Date
20 Mar 2021, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/REPLACEMENT OF OLD/ UNSV LT PANEL AT OLD SHIA LINE, NIRBHAY VIHAR, NEW BS MARG, GGS, RAJIV SANDHU VIHAR AND PREM NAGAR PUMP HOUSES AND OTHER CONNECTED WORKS AT WATER SUPPLY INSTALLATION UNDER GE (E/M), LUCKNOW
2021_MES_424975_1
GE/EM/LKO/EXT(WS)/T-95 OF 2020-2021
Open Tender
Miscellaneous Works
Item Rate
180 days
Lucknow
Class D or above category b (i)
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹79,400
Yes
30 Mar 2021
23 Feb 2021
22 Mar 2021
23 Feb 2021
20 Mar 2021
8 Mar 2021
Amount
Supply, installation, testing and commissioning indoor type LT cubical panel size not less than 1.5 Mtrx 1.2 Mtr x 0.40Mtr depth shall be factory fabricated as per IS-8623 powder coated with structureal siemens grey RAL 7032 paint front and back openable and lockable by key from both side having louvers and air vent gasket and totally vermin proof made out of 2.0mm thick MS sheet duly compartmentalized for incoming and outgoing laminated copper busbar duly insulated with colour coded heat shrinkable sleeves and mounted on DMC/epoxy insulators size not less than 50x50x conical type at a maximum interval of 500mm ). The incomer and outgoing shall have extension link two times the rating of individual feeder. The length of extension should not be less than 200mm long copper strip. All links shall be insulated with colour coded heat shrinkable sleeves having provision for termination of incomers and outgoing cables. All control wires shall be not less than 2.5 Sq mm multi stranded copper conductor and properly bunched/tied, ferruled for proper identification and crimpled with adequate size of lugs.
INCOMING Changeover switch on load in open execution 4 pole 415 V, 50 cycles-160 Amp -02 Nos
Busbar 4 pole (three phase and one for neutral) made out of laminated copper size 40mmx6mm
MCCB Cap 160 Amp, 4 pole, 415V, 50 c/s 36 KA-01 No
OUTGOING MCCB Cap 100 Amp, 4 pole, 415V, 50 c/s 36 KA-01 No
MCB TPN capacity 32 Amps, 415V, 50 c/s 16 KA-01 No.
MCB SPN capacity 32 amp, 'C' series-02 Nos
Star/delta soft starter suitable upto 36KW /50HP 3 phase, 415V, 50 c/s induction motor including protection against over voltage, under voltage, over current under current reverse phasing, single phasing, earth fault with required PLC
DOL starter suitable for 3 phase 50 Hz 400V, not less than 5 HP induction motor.-01 No
Set of indicating lamp LED type-01 Set.
Civil work PCC 1:2:4 for grouting of panel complete including excavation, earth work.
Disconnecting of existing LT UG cable from old panel and connecting in new panel including connected work such as excavation of cable loop, relaying/refixing of cable in trench/floor as per site requirement, earth work & repair damaged trench/floor to match the existing surface complete all as specificed and directed by Engineer-in-Charge.
Digital Multi function meter for Ammeter, Volt, KWH, PF, frequency etc 3 phase 4 wire of suitable capacity.-01 No
Earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 32x6mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 5 of SSR Part-I and testing ,including dismanteling of old unserviceable earthing , complete all as specified and as directed by Engineer-in-Charge.Note : (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point.(ii) Earth pit shall be constructed minimum 1.00 metre away from earth.
Fixing only in repair, connecting, testing and commissioning rupturing capacity MCCB 100 Amps , TP , 415 Volts, 16 KA, 50 Hz including spreader terminals complete all as specificed and directed by Engineer-in-Charge. (To be issued under Sch B)
Fixing only in repair, connecting, testing and commissioning rupturing capacity MCCB 125 Amps , TP , 415 Volts, 16 KA, 50 Hz including spreader terminals complete all as specificed and directed by Engineer-in-Charge. (To be issued under Sch B)
Fixing only in repair, connecting, testing and commissioning rupturing capacity MCCB 160 Amps , FP , 415 Volts, 36 KA, 50 Hz including spreader terminals complete all as specificed and directed by Engineer-in-Charge. (To be issued under Sch B)
Changeover switch on load in open execution 4 pole 415 V, 50 cycles-100 Amp -02 Nos ( One for commercial & DG Set Supply & other for phase changing) complete all as specificed and directed by Engineer-in-Charge.
MCB TPN capacity 32 Amps, 415V, 50 c/s 16 KA-01 No complete all as specificed and directed by Engineer-in-Charge.
MCB SPN capacity 32 amp, 'C' series-02 Nos complete all as specificed and directed by Engineer-in-Charge.
MCB single pole 5 to 30 amp rating 'B' Series 240 Volt complete all as specificed and directed by Engineer-in-Charge.
Gate light in repair LED-40 WATT 215 V, 50 HZ, post top made in cast aluminium spigot housing with decorative clear acrylic diffuser and IP65 protection fix with GI Pipe 40 mm dia 30 cm long (15 cm under the pillar & 15 cm above the pillar ) with proper connecting with existing electric complete all as specificed and directed by Engineer-in-Charge.
Sheet metal enclosre for DB's(when MCBs to be used) single pole and neutral 240 Volts 2 way without bus bar complete all as specificed and directed by Engineer-in-Charge.
Sheet metal enclosre for DB's(when MCBs to be used) single pole and neutral 240 Volts 8 way with 200 Apms rated bus bar complete all as specificed and directed by Engineer-in-Charge.
Flourescent LED tube light fitting as in repair Surface mounting , 1X/36 Watt ,energy efficient,,ceiling /wall mounting box type fitting complete , with decorative serrated acrylic cover diffused illumination elegantly designed, spring loaded, rotary type lamp holder, , connector block etc. and all accessories with 1 No 40/36 watt tube rod including provn of two core flexible copper cable of size 1.5 Sqmm from ceiling rose/connector complete all as specificed and directed by Engineer-in-Charge.
LED street / bldg light fitting luminaire 70 Watt IP65, 230 volts, new generation energy saving & enviormental friendly long life versatile pressure die cast aluminium roadway luminarie with high power LEDs as light source and electronic driver complete all as specificed and directed by Engineer-in-Charge.
Point wiring in repair including taking out complete with PVC insulated and unsheathed cable 1.5 sqmm (nominal area) ,ISI marked,stranded copper conductor single core including ISI marked 20mm dia PVC conduit concealed in wall and MS conduit in roof/floorslab,pressed GI concealed terminel boxes 60 mm deep for mounting switches, fan regulator ,etc . of reqd size and with top cover 3 mm thick of plastic laminated sheets of required colour complete,including 1.5 Sqmm PVC insulated unsheathed copper earth wire to the common earth and connecting to earth dolly,including colour coding of cable shall be Phase-red,Neutral-black and Earth- green with all accessories complete all as specificed and directed by Engineer-in-Charge.
One light/Fan/Exhaust fan point controlled by one switch
One 5 pin 5 Amp switch socket out let point on an independent board including 1.5 Sqmm PVC insulated and unsheathed copper wire to common earth and connecting to earth dolly complete all as specificed and directed by Engineer-in-Charge.
One 5 pin 5 Amp switch socket out let point on same board including 1.5 Sqmm PVC insulated and unsheathed copper wire to common earth and connecting to earth dolly complete all as specificed and directed by Engineer-in-Charge.
M&L for point wiring complete in repair with PVC insulated and unsheathed cable 2.5 sqmm (nominal area) ,ISI marked,stranded copper conductor single core including ISI marked 20mm dia PVC conduit concealed in wall and MS conduit in roof/floorslab,pressed GI concealed terminel boxes of reqd size and with top cover 3mm thick of plastic laminated sheets of required colour complete,including 1.5 Sqmm PVC insulated unsheathed copper earth wire to the common earth and connecting to earth dolly,including colour coding of cable shall be Phase-red,Neutral-black and Earth- green with complete all as specificed and directed by Engineer-in-Charge.
Switch piano, flush type, 5 amps single pole, one way complete all as specificed and directed by Engineer-in-Charge.
Switch piano, flush type, 15 amps single pole, one way complete all as specificed and directed by Engineer-in-Charge.
Socket, flush type,2 in 1, 5 pin, 5 amp multi purpose complete all as specificed and directed by Engineer-in-Charge.
Socket 2 in 1, 3 pin, 5 and 15 Amps flush type complete all as specificed and directed by Engineer-in-Charge.
Stepped type electronic fan regulator,flush type ,5 step complete all as specificed and directed by Engineer-in-Charge.
Ceiling rose ,2/3 Point ,polycorbonate,isolated body complete all as specificed and directed by Engineer-in-Charge.
Supply, laying in repair incluiding taking out & connecting PVC insulated, armoured, heavy duty electric cable with aluminium conductor 1100 volts grade 3.5/4/02 core with stranded aluminium conductor complete all as specified and directed by Engr-in-charge of following sizes. (Note :- Excavation & earth work will be measured and paid separately under respective item).
10 Sqmm 02 core
50 Sq mm 3.5 core
70 Sq mm 3.5 core
95 Sqmm 3.5 core
Fixing only Submersible flat copper stranded cable 1100 Volt grade of size 16 sqmm 3 core, complete all as specificed and directed by Engineer-in-Charge. (To be issued under Sch B)
Fixing only Submersible flat copper stranded cable 1100 Volt grade of size 10 sqmm 3 core , complete all as specified and directed by Engineer-in-Charge. (To be issued under Sch B)
Excavation in trenches not exc 1.5m wide and and not exc. 1.5m depth wide in soft/loose soil for laying electric cables/pipes etc including getting out excavated earth and trimming the sides and bottoms of trenches , complete all as specificed and directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested, complete all as specified and directed by Engineer-in-Charge.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point , complete all as specified and directed by Engineer-in-Charge.
Sand cushioning to cables with a layer of sand 8 cm deep before laying the cable and 15 cm depth (punned down to 10 cm depth after laying and stretching of cable), complete all as specificed and directed by Engineer-in-Charge.Note: Punned thickness (over all 18 cm) shall be measured & paid.
Protection of cable with one layer of bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ‘B’ bricks, complete all as specified and as directed by Engineer-in-Charge.
Shree Tirupati Associates
M/S AMARJIT SINGH
DEV INFRATECH
Sanjai sales and services
M/S Nav Jyoti Enterprises
Shailza Traders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .