Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.2 CrAccepted-AOC | ₹25.2 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹26.7 CrRejected-Finance MATERE HOUSE SEC NO 14 PRADHIKARAN PUNE MAHARASHTRA INDIA 412105 | PUNE | MAHARASHTRA | 412105 | ₹26.7 Cr | L2 | Rejected-Finance other than L1 |
| 3 | L3₹27.3 CrRejected-Finance | ₹27.3 Cr | L3 | Rejected-Finance other than L1 |
| 4 | L4₹28.4 CrRejected-Finance | ₹28.4 Cr | L4 | Rejected-Finance other than L1 |
| 5 | L5₹28.7 CrRejected-Finance 35 B BHERU VILLAS SARDAR CLUB SCHEME AIR FORCE JODHPUR 342 011 RAJASTHAN | JODHPUR | JODHPUR | RAJASTHAN | 342011 | ₹28.7 Cr | L5 | Rejected-Finance other than L1 |
Tender Value
Refer Docs
EMD Value
₹15 L
Closing Date
10 Oct 2020, 6:00 pmClosed
Chief Engineer Pune Zone
Chief Engineer Pune Zone Dakshin Kaman Marg Camp Pune 411001
PROVN OF OTM ACCN FOR HQ 41 ARTY DIV AND ITS UNITS AT PUNE
2020_MES_311929_2
84440E8
Open Tender
Civil Works
745 days
PUNE
AS PER NIT
6 documents required · 6 mandatory
₹3,000
GE ( South) Pune
₹15 L
7 Dec 2020
12 Sept 2020
12 Oct 2020
12 Sept 2020
10 Oct 2020
30 Sept 2020
14 Sept 2020 - 21 Sept 2020
Amount
NOTE: Schedule ‘A’ Part I (SECTION 'A'), Part II to XIII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-13 only.
Total amount of Sch 'A' Part-I (Building Works)
Total amount of Sch 'A' Part-II (Internal water supply)
Total amount of Sch ‘A’ Part III (Internal Electric Supply)
Total amount of Sch ‘A’ Part IV (External Water Supply)
Total amount of Sch ‘A’ Part V (External Electric Supply)
Total amount of Sch 'A' Part-VI (Road, Path, Hardstanding and Culverts)
Total amount of Sch 'A' Part-VII (Sewage Disposal)
Total amount of Sch ‘A’ Part VIII (Area drainage)
Total amount of Sch ‘A’ Part IX (Boundary wall, fencing & steel gate)
Total amount of Sch ‘A’ Part X (Lightning Protection)
Total amount of Sch ‘A’ Part XI (Solar Water Heater System)
Total amount of Sch ‘A’ Part XII (Excavation, Earthwork & Site Clearance)
Total amount of Sch ‘A’ Part XIII (Demolition of existing building)
SCH 'A PART XIV (Miscellaneous B/R and E/M works) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
Taking down electric geyser any type after disconnecting the water and electrical connections and hand over to AGE E/M (North) store yard complete all as specified and as directed.
Taking down KWH electrical meters after disconnecting the wire from mains and MCB DB and hand over to AGE E/M (North) store yard complete all as specified and as directed.
Taking down the existing unserviceable main switch/ cut out / DBs of any type / capacity/ description as existing at site including making good the disturbed surfaces to match with the existing finish all as specified and as directed.
Taking down the existing service cable/ sub main wiring of any type/ description as existing at site all as specified and as directed.
Taking out existing Transformer step down type 3 phase 250 KVA, 22 KV 50 HZ 433 Volts from its Position, installed at WT Stn Nagar Road (SM No : 120784, MES No : 7618-S of Make : NEI ) by disconnecting /opening HV, LV Electrical connections, earthing connections and hand over to store yard of AGE E/M (North) complete all as specified and as directed.
Dismantling existing two Pole Structure 22 KV with GOD, Cross-Arms, stay assembly, Insulators, LA etc including demolition of cement Concrete with necessary excavation of earth work complete all as specified and as directed.
Taking down/out unserviceable UG Cables of any description and any type, any Cross Sectional Area and Connections and joints including Pipes, Bricks, etc of any description laying in trenches or fixing with Walls/Poles, complete including necessary excavation of earthwork complete all as specified and as directed.
Taking out existing LT Panel board complete with all its control gears, Amperemeter, volt meter etc including demolition of Cement Concrete (as/if required) complete all as specified and as directed
Dismantling existing Steel Tubular LT Poles of any description and any size with junction boxes including demolition of Cement Concrete (as/if required) complete all as specified and as directed.
Taking down street light fitting of any description and any type from pole/Bldg of any height alongwith connector cable, junction box, clamps, brackets etc complete all as specified and as directed.
Taking down capacitor bank 15 KVAR after disconnecting the wire from mains complete all as specified and as directed.
Taking down lightning conductor with angle iron of any size complete all as specified and as directed.
S & F sub main wiring with 2 single core flame retardent (FRLS)PVC insulated,unsheathed multistranded flexible copper conductor cable, of 2 runs of 2.5 sqmm and one single core 2.5 sqmm flame retardent PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694 / 1990 drawn through & including concealed PVC conduit and conduit accessories all as specified and as directed.
S & F sub main wiring with 2 single core flame retardent (FRLS)PVC insulated,unsheathed multistranded flexible copper conductor cable, of 2 runs of 4 sqmm and one single core 4 sqmm flame retardent PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694 / 1990 drawn through & including concealed PVC conduit and conduit accessories all as specified and as directed.
S & F sub main wiring with 2 single core flame retardent (FRLS)PVC insulated,unsheathed multistranded flexible copper conductor cable, of 2 runs of 6 sqmm and one single core 6 sqmm flame retardent PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694 / 1990 drawn through & including concealed PVC conduit and conduit accessories all as specified and as directed.
S & F sub main wiring with 4 single core flame retardent (FRLS)PVC insulated,unsheathed multistranded flexible copper conductor cable, of 4 runs of 6 sqmm and two single core 6 sqmm flame retardent PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694 / 1990 drawn through & including concealed PVC conduit and conduit accessories all as specified and as directed.
S & F sub main wiring with 4 single core flame retardent (FRLS)PVC insulated,unsheathed multistranded flexible copper conductor cable, of 4 runs of 10 sqmm and two single core 10 sqmm flame retardent PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694 / 1990 drawn through & including concealed PVC conduit and conduit accessories all as specified and as directed.
S & F sub main wiring with 4 single core flame retardent (FRLS)PVC insulated,unsheathed multistranded flexible copper conductor cable, of 4 runs of 16 sqmm and two single core 16 sqmm flame retardent PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead, all as per IS 694 / 1990 drawn through & including concealed PVC conduit and conduit accessories all as specified and as directed.
S & F ceiling fan 1200 mm (48") sweep, 5 star rating (2019) BEE mark (after assembling the same) with the fan hook/box, and connecting up complete with & including electronic regulator and including three core copper conductor flexible cord of 0.5 Sqmm cross sectional area, of reqd length from ceiling rose to connector block of the fan, all as specified and directed.
S & F ceiling fan 1200 mm (48") sweep, 5 star rating (2019) BEE mark (after assembling the same), and connecting up regulator but without fan regulator and including three core copper conductor flexible cord of 0.5 Sqmm cross sectional area, of reqd length from ceiling rose to connector block of the fan, all as specified and directed. Make as given in Appx 'C'.
S & F LED Tube along with CRCA LED Batten complete LED light fitting fixture including LED Tube and Batten ,LED Tube fitting consist of heatsink for mounting LED chip,LED tube system wattage consist of 18 / 20 W,140-260V AC, system Lumen output min 1800 Lumen in 18 W and 2000 lumen in 20 W with 5700-6500 K CCT with PF>0.95 CRI>=80 and with <=10 % THD ,with Min 2.5 KV Surge protection in Built LED Batten consist of powder coated CRCA box type batten with decorative end caps should be supplied for installing above LED tubes all as specified and directed. Make as given in Appx 'C'.
Supply of 10 w LED bulk head fitting including LED Lamp,pressure die cast aluminium housing with IP65 rating,LED Fixture system wattage of 10 w ,140V-260V AC,System lumen output min 950 Lumen with 5700-6500 K CCT with PF>0.95 and with <=15% THD ,with Min 2.5 KV Surge protection in built and complete LED fixture with BIS R mark and R Registration number all as specified and directed.Make as given in Appx 'C'.
S & F 25 Watt LED street light Pressure die cast aluminium alloy for housing (heat sink) for effective thermal management with LED PC lens LED Street Light system wattage consist of 25 Watt ,140-260 V AC,System Lumen Out put min 2550 Lumen in 25 w with 5700-6500 K CCT with PF >0.95 CRI >=70 and with <=10 % THD,with Min 2.5 KV Surge protection in Built and LED Street Light with BIS R Registration number and necessary brackets , GI pipe 32 mm dia medium grade 1.2m, duly bended to shape including provision of clamps of suitable size all as specified and diretced. Make as given in Appx 'C'.
S & F Lamp holder ,angle / straight pin type PVC / polycarbonate type with back plate including LED 1X9 W lamp complete all as specified. Make as given in Appx 'C'.
S & F 10-12 w LED Circular Surface mounted fitting Pressure die cast aluminium heat sink with PC Diffuser, LED Fixture System wattage of 10-12 w, 140-260V AC, System Lumen Output min 1000 Lumen in 10 w and 1200 lumen in 12 w with 5700 -6500 K CCT with PF >0.95 CRI >=80 and with <=10 % THD,WITH mIN 2.5 KV Surge protection in built and complete LED fixture with BIS R mark and R Registration no.all as specified and directed. Make as given in Appx 'C'.
S & F square 2 ft x 2 ft ,36 w-42 w recess mounted bottom opening LED fitting including ,LED Lamp with powder coated CRCA housing and polycarbonate diffuser,ED Fixture system wattage 36 -42 w,140V -260 V AC ,System lumen out put min 3600 lumen in 36 w and 4200 lumen in 42 w with 5700-6500 K CCT with PF>0.95 CRI>=80 and with <=10 % THD,with Min 2.5 KV surge protection in Built complete LED fixture with BIS Mark and R Registration no. all as specified and diretced. Make as given in Appx 'C'.
S & F 2 x 6 w double head mirror ight LED Batten fixture with IP20 moisture protection, Premium opal glass housing and chrome mounts, LED fixture system wattage of 06 w each, 140V-260V AC, System Lumen output min 600 Lumen in 06 w with 5700-6500 KCCT, all as specified and diretced. Make as given in Appx 'C'.
S & F MCB TPN 415 Volts, 63 Amps, with rupturing capacity of 10KA all as specified and directed. Make as given in Appx 'C'.
S & F MCB TPN 415 Volts, 40 Amps, with rupturing capacity of 10KA all as specified and directed.Make as given in Appx 'C'.
S & F MCB SPN 240 Volts, 6 amps to 32 Amps, with rupturing capacity of 10KA all as specified and directed. Make as given in Appx 'C'.
S & F MCB SP 240 Volts, 6 amps to 40 Amps, with rupturing capacity of 10KA all as specified and directed. Make as given in Appx 'C'.
S & F blanking plate, made of PVC all as specified and directed. Make as given in Appx 'C'.
S & F exhaust fan 250 mm sweep, 1400 RPM, single phase, light weight, White/Ivory Plastic rust proof body & blades, self opening louvers for protection from birds and rain water, fixing by means of rugged bolts, nuts and washers etc on the round hole cut in the wall, including three core copper conductor flexible cord of 0.5 Sqmm cross sectional area of required length from ceiling rose to the porcelain connector block of the exhaust fan complete all as specified and directed. Make: Any of make listed in Appx 'C'.
M & L LED flame proof 1 x 20 watt LED tube light fixtures luminaire complete suitable for illuminating hazardus area laden with gases or vapors including flamr proof flexible pipe all as specified Cat No;-EXTN1LT8-16/20 Make Crompton Greaves or equivalent in any of make listed in Appx 'C'.
Supply, installing, testing and commissioning, dust and vermin proof LT distribution panel (Office building) factory made cubicle/modular fully compartmentalized with bus bar chamber and locking arrangement, indoor type of suitable size so as to accommodate the following accessories, depth not less than 500mm, IP 54 and all as per IE rules, prewired and fabricated with 2.00mm thick CRCA sheet, exoxy power coated after seven tank process with aprons, duly powder coated wall mounted, semi-concealed type, CPRI type tested, AC 430 V, 50 Hz, complete with the following accessories:-
(a) Copper strip bus bar 300 Amp(04 Nos)- 03 Nos for phase and 01 Nos for neutral duly colour sleeved mounted on epoxy insulator - 01 Set
(b) Incoming - MCCB 200 Amps, FP, 415V, 50Hz ICU 25 KA thermally adjustable between 70-100% - 01 No
(c) Outgoing
(i) MCCB 63 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 10 Nos
(iv) RYB indicator lamp- Set of 3
Note : Panel shall be manufactured by the reputed manufacturer who is possession of type test certificate by CPRI not older than ten years.
Supply, installing, testing and commissioning, dust and vermin proof LT distribution panel (27 Hav & 164 OR) factory made cubicle/modular fully compartmentalized with bus bar chamber and locking arrangement, indoor type of suitable size so as to accommodate the following accessories, depth not less than 500mm, IP 54 and all as per IE rules, prewired and fabricated with 2.00mm thick CRCA sheet exoxy power coated after seven tank process with aprons, duly powder coated wall mounted, semi-concealed type, CPRI type tested, AC 430 V, 50 Hz, complete with the following accessories:-
(a) Copper strip bus bar 200 Amp(04 Nos)- 03 Nos for phase and 01 Nos for neutral duly colour sleeved mounted on epoxy insulator - 01 Set
(b) Incoming - MCCB 160 Amps, FP, 415V, 50Hz ICU 25 KA thermally adjustable between 70-100% - 01 No
(c) Outgoing
(i) MCCB 63 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 08 Nos
(iv) RYB indicator lamp- Set of 3
Note : Panel shall be manufactured by the reputed manufacturer who is possession of type test certificate by CPRI not older than ten years.
Supply, installing, testing and commissioning, dust and vermin proof LT distribution panel (6 Hav & 40 OR) factory made cubicle/modular fully compartmentalizd with bus bar chamber and locking arrangement, indoor type of suitable size so as to accommodate the following accesoris, depth not less than 500mm, IP 54 and all as per IE rules, prewired and fabricated with 2.00mm thick CRCA sheet exoxy power coated after seven tank process with aprons, duly powder coated wall mounted, semi-concealed type, CPRI type tested, AC 430 V, 50 Hz, complete.
(a) Copper strip bus bar 100 Amp(04 Nos)- 03 Nos for phase and 01 Nos for neutral duly colour sleeved mounted on epoxy insulator - 01 Set
(b) Incoming - MCCB 63 Amps, FP, 415V, 50Hz ICU 16 KA thermally adjustable between 70-100% - 01 No
(c) Outgoing
(i) MCCB 40 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 03 Nos
(iv) RYB indicator lamp- Set of 3
Note : Panel shall be manufactured by the reputed manufacturer who is possession of type test certificate by CPRI not older than ten years.
Supply, Lay, joint, test & commissioning Ductile Iron pipes S/S, class K-7 with cement mortar lining inside the pipe and zinc coated out side as per IS 8329/2000, laid in trenches or any other locations all as specified & directed of 150 mm bores complete all specified and as directed. (Excavation and earthwork and cost of MS work shall be measured and paid seperately under relative items of this schedule).
Supply, Lay, joint, test & commissioning Ductile Iron pipes S/S, class K-7 with cement mortar lining inside the pipe and zinc coated out side as per IS 8329/2000, laid in trenches or any other locations all as specified & directed of 100 mm bores complete all specified and as directed. (Excavation and earthwork and cost of MS work shall be measured and paid seperately under relative items of this schedule).
M & L for ductile iron fittings such as bends, (any type, radius and angle), heavy duty for spigot & socketed or flanged pipes, tapers any type, radius and angle like straight, bend, increasing, decreasing or double socket etc. tee piece, single branch 'Y' junction double branch, coller etc. Caps and plugs etc. as per IS 9523-2000 of class K-12 PN 10 with internal cement mortar lining and external Zinc and black bitumen coated of dia upto 300mm complete all as specified and as directed.
Supply, install, test & commissining of manufacturer's factory assembled and tested electric driven centrifugal monoblock pump set with moter capable of delivering at 52 mtr Head, 3 phase, 415 V to match with the capacity of 567 LPM discharge complete comprising of the following:-
(i) PCC foundation as per manufacturer specification minimum 250 mm height above floor level
(ii) ISMC 75 mm channel as base frame for pump set duly grouted/bolted in PCC foundation
S & F multi standard copper cable of size 10 sqmm 3 core laid in suitable dia PVC pipe, fixed on floor/wall complete all as specified and directed.
S & F Pressure guage of 10 kgf/sqcm with control valve complete all as specified and directed
S & F CI Foot valve 100 mm dia complete all as specified and directed
S & F Non return valve 100 mm dia complete with by pass arrangement all as specified and directed
Supply, installing, testing and commissioning of free standing floor mounted, dust and vermin proof LT cubicle/ Modular construction fully compartmentalized panel, indoor type, fabricated with 2 mm thick CRCA sheet for load bearing members and 1.6 m thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. The panel shall be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles, AC supply. The panel shall be provided with Base channel of ISMC75 all around with cable ally at side and bottom 600 mm width and bus bar chamber and comprising the following:-
(a) 250 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB TPN 125 Amps, 16 KA with thermal magnatic release and rotery handle - 1 Nos.
(c ) On load change over Switch TPN of capacity 100 Amps - 01 No (in coming)
(d) MCCB TPN 63 Amps with thermal magnatic release breaking capacity 10 KA at 415 volts - 3 Nos.
(e) MCB SPN 25 amps 10 KA - 02 Nos.
(f) Star delta starter suitable for 20 HP centrifugal pump set 3 phase 415 volts with illuminated push button on/off - 02 No.
(g) Single phase preventor - 02 No
(h) LED Indicating lamp RYB 01 Set.
Earthing complete with galvanised steel earth plate electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of plate not less than 1.50 m below normal ground level connected to GI earth strip 25x4 mm connected to the plate by means of GI bolts & nuts complete all as per Electrical plate No. 5 of SSR Part - I, connected to earthing test point including testing on completion including main earthing, charcoal, common salt, PCC 1:3:6, Type C-2 earth pit with RCC cover, MS funnel with GI watering pipe, GI Strip protection pipe 40 mm, wiremesh, earth work excavation etc complete all as specified and as directed by the Engineer - in - Charge. (Note :- GI earth strip with protection pipe will be measured beyond 7.50 mtr.)
Supply and fixing GI strip 25 mm x 4 mm complete and buried in ground as ground conductor complete all as specified .
Material & labour for construction of valve pit chamber having internal dimensions 900mmx900mmx900mm in PCC 1:4:8 type D-2 using 40mm stone aggrgate for foundation of 150mm thick, 150mm wide offses around over 100mm thick hard core, 200mm thick PCC solid block walls in cement mortar 1:4, PCC coping 50mm thick in cement concrete 1:2:4 using 20mm graded stone aggregate finished smooth, rendering cement plaster 10mm thick in cement mortar 1:4 and finished even and smooth without using extra cement internally all round and externally upto 300mm from top including fabrication of MS cover embedded to chamber, using 45x45x5mm angle iron,MS plate of size 1200mmx1200mm and 3.00mm thick,handle made out of flat iron of size 25x4mm, butt hinges heavy weight, cold rolled mild steel of size 125mm-2Nos,including painting to steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer including excavation and earth work in hard /dense soil complete all as specified and directed by Engr-in-charge.
Material & labour for construction of valve pit chamber having internal dimensions 600mmx600mmx600mm in PCC 1:4:8 type D-2 using 40mm stone aggrgate for foundation of 150mm thick, 150mm wide offses around over 100mm thick hard core, 200mm thick PCC solid block walls in cement mortar 1:4, PCC coping 50mm thick in cement concrete 1:2:4 using 20mm graded stone aggregate finished smooth, rendering cement plaster 10mm thick in cement mortar 1:4 and finished even and smooth without using extra cement internally all round and externally upto 300mm from top including fabrication of MS cover embedded to chamber, using 45x45x5mm angle iron,MS plate of size 1200mmx1200mm and 3.00mm thick,handle made out of flat iron of size 25x4mm, butt hinges heavy weight, cold rolled mild steel of size 125mm-2Nos,including painting to steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer including excavation and earth work in hard /dense soil complete all as specified and directed by Engr-in-charge.
Supply install, testing and commsiioning plinth mounted step-down outdoor type distribution transformer HT 22KV, 3Ph, LT 433V, 4wire, capacity 400KVA copper wound, oil immersed, naturally cooled with external cooling tubes, core type, delta connected on primary (HV) side and star connected on secondary (LV) side in accordance with vector symbol DYN-11(Vector ground -4) with neutral brought on secondary (LV) side & having tapping in equal steps of 2.5% from (+/-) 5% to (+/-) 7.5% to be changed by means of hand operated off load tap changing gear, so as to change /correct LT voltage on secondary side confirming to IS 1180 part-I 2014 level -3, including provision of all necessary standard fittings and mainly comprising of the following :-
(a) One cable box on HT side (Primary side consisting of 3 Nos porcelain bushings with copper rods complete with nuts & bolts.
(b) One cable box on LT side (secondary side consisting of 4 Nos porcelain bushing with copper rods complete with nuts & washer).
(c) Oil conservator oil level gauge.
(d) Dehydrating breather with first fill of dehydreting agent (Silica Gel).
(e) Explosion vent, thermometer pocket on tank cover, oil drain filter valve, lifting lugs, oil filling hole with cap/ plug, air release valve plug & 4 Nos plain solid cast steel detachable rollers.
(f) One 100mm dia dial type thermometer, vapour pressure type, having range 0-120 degree Celsius having maximum temperature reading indicator with resetting.
(g) Two earthing terminals on tank cover to facilitate fixing of 32X6 mm galvanised iron earth strip for earthing of body.
(h) Rating plate & terminal marking plate.
(j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral
(k) First filling of transformer oil, IS-335 Marked within (Make -savita/power link) filter & tested upto 50 KV di electric strength at 2.5 mm air gap between testing electrodes.
(k) PCC foundation of transformer will be provided as per CEPZ TD Drg.
Supply,installing, testing and commissioning of Indoor type free standing floor mounted, dust and vermin proof LT cubicle/ Modular construction fully compartmentalized panel , IP-54 and all as per IE rules fabricated with 2.0 mm CRCA double door type Sheet for load bearing members and 1.6 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with Base channel of ISMC75 all around with cable alley at side and bottom cable alley (min. 600 mm width at the bottom) and bus bar chamber and comprising the following : ( Tranformer Main Panel)
(a) 1000 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) ACB 4 pole 630 Amps with Thermal magnatic release(manual drawout type) 415 V, 50 KA breaking capacity- 01 No (in coming)
(c) MCCB 4 Pole 350 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 02 No (out going)
(d) MCCB 4 Pole 250 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 03 No (out going)
(e) MCCB 4 Pole 200 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 01 No (out going)
(f) MCCB 4 Pole 160 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu - 01 No (out going)
(g) MCCB 4 Pole 125 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 No (out going)
(h) MCCB 4 Pole 63 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos (out going)
(j) MCB SPN 25 amps with breaking capacity 10 KA at 230 volts - 01 nos.
(k) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(l) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set
(m ) Internal wiring of panel with stranded copper cable of suitable size.
Supply, installing, testing and commissioning of free standing weather proof, dust and vermin proof LT panel cubicle/ Modular construction fully compartmentalized panel out door type with bus bar chamber and cable alley on both side, IP-54 and all as per IE rules fabricated with 3.0 mm CRCA double door type (Front side ; out side with main panel door and inside with compartmentlised door for each cubicle ) (Rear side main panel door and inside bolted door for each cubicle) Sheet for load bearing members and 2 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with MS angle iron frame 50x50x6mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 with using 20mm graded coarse stone aggregates completed with legs 30Cm in ground and 40Cm above ground icluding connecting to cable with cable gland, lugs etc. and comprising the following : ( panel near MES Estb)
(a) 400 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB 4 Pole 200 Amps, 36 KA with Rotary Handle, microprocessor release adjustable amp Ics = 100% Icu as per IEC 60947-2 , Adjustable Over load from 0.5 to 1*In , Adjustable Short Circuit from 2 to 10*Ir , Adjustable Neutral Protection - N, N/2,OFF for 4 Pole MCCB , Inbuilt Thermal Memory- 01 No (in coming)
(c) MCCB 4 Pole 100 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos (out going)
(e) MCCB 4 Pole 63 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 03 Nos (out going)
(f) MCB SPN 25 amps with breaking capacity 10 KA at 230 volts - 03 nos.
(i) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(j) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set
(k) Internal wiring of panel with stranded copper cable of suitable size.
Supply,installing, testing and commissioning of free standing weather proof, dust and vermine proof LT panel cubicle/ Modular construction fully compartmentalized panel out door type with bus bar chamber and cable alley on both side, IP-54 and all as per IE rules fabricated with 3.0 mm CRCA double door type (Front side ; out side with main panel door and inside with compartmentlised door for each cubicle ) (Rear side main panel door and inside bolted door for each cubicle) Sheet for load bearing members and 2 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with MS angle iron frame 50x50x6mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded stone aggregates completed with legs 30Cm in ground and 40Cm above ground including connecting to cable with cable gland, lugs etc. and comprising the following ( panel near Div OR Accn)
(a) 700 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB 4 Pole 350 Amps, 50 KA with Rotary Handle, microprocessor release adjustable amp Ics = 100% Icu as per IEC 60947-2 , Adjustable Over load from 0.5 to 1*In , Adjustable Short Circuit from 2 to 10*Ir , Adjustable Neutral Protection - N, N/2,OFF for 4 Pole MCCB , Inbuilt Thermal Memory- 01 No (in coming)
(c) MCCB 4 Pole 200 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 No (out going)
(d) MCCB 4 Pole 100 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos (out going)
(k) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(l) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set
(m ) Internal wiring of panel with stranded copper cable of suitable size.
Supply, installing, testing and commissioning of free standing weather proof, dust and vermine proof LT panel cubicle/ Modular construction fully compartmentalized panel out door type with bus bar chamber and cable alley on both side, IP-54 and all as per IE rules fabricated with 3.0 mm CRCA double door type (Front side ; out side with main panel door and inside with compartmentlised door for each cubicle ) (Rear side main panel door and inside bolted door for each cubicle) Sheet for load bearing members and 2 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with MS angle iron frame 50x50x6mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded stone aggregates completed with legs 30Cm in ground and 40Cm above ground including connecting to cable with cable gland, lugs etc. and comprising the following : ( panel near Div HQ office)
(a) 500 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB 4 Pole 250 Amps, 50 KA with Rotary Handle, microprocessor release adjustable amp Ics = 100% Icu as per IEC 60947-2 , Adjustable Over load from 0.5 to 1*In , Adjustable Short Circuit from 2 to 10*Ir , Adjustable Neutral Protection - N, N/2,OFF for 4 Pole MCCB , Inbuilt Thermal Memory- 01 No (in coming)
(c) MCCB 4 Pole 160 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos (out going)
(d) MCCB 4 Pole 100 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 Nos (out going)
(e) MCB SPN 25 amps with breaking capacity 10 KA at 230 volts - 04 nos.
(f) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(g) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set
(h ) Internal wiring of panel with stranded copper cable of suitable size.
Supply,installing, testing and commissioning of free standing weather proof, dust and vermine proof LT panel cubicle/ Modular construction fully compartmentalized panel out door type with bus bar chamber and cable alley on both side, IP-54 and all as per IE rules fabricated with 3.0 mm CRCA double door type (Front side ; out side with main panel door and inside with compartmentlised door for each cubicle ) (Rear side main panel door and inside bolted door for each cubicle) Sheet for load bearing members and 2 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with MS angle iron frame 50x50x6mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded stone aggregates completed with legs 30Cm in ground and 40Cm above ground including connecting to cable with cable gland, lugs etc. and comprising the following: ( panel near PRO unit office)
(a) 500 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB 4 Pole 250 Amps, 50 KA with Rotary Handle, microprocessor release adjustable amp Ics = 100% Icu as per IEC 60947-2 , Adjustable Over load from 0.5 to 1*In , Adjustable Short Circuit from 2 to 10*Ir , Adjustable Neutral Protection - N, N/2,OFF for 4 Pole MCCB , Inbuilt Thermal Memory- 01 No (in coming)
(c) MCCB 4 Pole 100 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 03 Nos (out going)
(d) MCCB 4 Pole 63 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos (out going)
(j) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(k) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set
(l ) Internal wiring of panel with stranded copper cable of suitable size.
Supply,installing, testing and commissioning of free standing weather proof, dust and vermine proof LT panel cubicle/ Modular construction fully compartmentalized panel out door type with bus bar chamber and cable alley on both side, IP-54 and all as per IE rules fabricated with 3.0 mm CRCA double door type (Front side ; out side with main panel door and inside with compartmentlised door for each cubicle ) (Rear side main panel door and inside bolted door for each cubicle) Sheet for load bearing members and 2 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. . the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with MS angle iron frame 50x50x6mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded stone aggregates completed with legs 30Cm in ground and 40Cm above ground including connecting to cable with cable gland, lugs etc. and comprising the following: ( MI Room Sub Panel)
(a) 300 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB 4 Pole 160 Amps, 50 KA with Rotary Handle, microprocessor release adjustable amp Ics = 100% Icu as per IEC 60947-2 , Adjustable Over load from 0.5 to 1*In , Adjustable Short Circuit from 2 to 10*Ir , Adjustable Neutral Protection - N, N/2,OFF for 4 Pole MCCB , Inbuilt Thermal Memory- 01 No (in coming)
(c) MCCB 4 Pole 100 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 No (out going)
(d) MCCB 4 Pole 63 Amps, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 05 Nos (out going)
(g) MCB SPN 25 amps - 01 nos.
(j) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(k) Indicator Lamps (LED type) & bakelite fuse showing R,Y, B phase - 01 set
(l ) Internal wiring of panel with stranded copper cable of suitable size.
Supply,installing, testing and commissioning of free standing weather proof, dust and vermine proof LT panel cubicle/ Modular construction fully compartmentalized panel in door type, fabricated with 2 mm thick CRCA sheet for load bearing members and 1.6 m thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with Base channel of ISMC75 all around with cable ally at side and bottom (min. 600 mm width at the bottom) and bus bar chamber and comprising the following(for street light)
(a) 200 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.
(b) MCCB TPN 63 Amps, 10 KA with thermal magnatic release and rotery handle - 1 Nos.
(c ) On load change over Switch TPN of capacity 63 Amps - 01 No (in coming)
(d) MCCB TPN 32 Amps with thermal magnatic release breaking capacity 10 KA at 415 volts - 4 Nos.
(h) LED Indicating lamp RYB - 02 Set.
(i) Analog time switch 3 phase power contactor 32 Amps - 01 Nos.
(j) Digital multi function meter showing voltage, current, power etc. - 01 nos.
(k ) Internal wiring of panel with stranded copper cable of suitable size.
Supply and install indoor automatic power factor correction (APFC) panel factory made dust and vermin proof capacitors bank, fully compartmentalized construction, heavy duty of 150 KVAR capacity suitable for variable correction (1 x2 KVAR + 1 x 3 KVAR +1 X 5 KVAR + 2 X10 KVAR + 2 X 15 KVAR + 2 X 20 KVAR + 2 x 25 KVAR) and suitable for 415/440 Volts, 3 phase 50 Hz, AC and housed in elegant enclosure fabricated from minimum 2.0 mm thick CRCA sheet and min 1.6 mm thick for partitions with base channel, danger plate, earth bus bar chamber and cable ally at bottom etc, duly powder coated after 7 tank process comprising of the following:-
(a) APFC Relay - 12 stage
(a) MCCB, Four Pole,350 Amp with thermal magnatic release, 36 KA - 01No (incoming)
(b) Digital multi function meter showing voltage, current, power, PF etc. - 01 nos.
(c) Phase indicating LED lamps (R-Y-B) -01 set
(d ) 1 set of 2 KVAR heavy duty cylindrical capacitor with capacitor duty contactor and suitabe MCB TP
(e ) 1 set of 3 KVAR heavy duty cylindrical capacitor with capacitor duty contactor and suitabe MCB TP
(f ) 1 set of 5 KVAR LTXL ultra heavy duty capacitor with capacitor duty contactor and suitabe MCB TP
(g ) 2 set of 10 KVAR LTXL ultra heavy duty capacitor with capacitor duty contactor and suitabe MCB TP
(h ) 2 set of 15 KVAR LTXL ultra heavy duty capacitor with capacitor duty contactor and suitabe MCB TP
(j ) 2 set of 20 KVAR LTXL ultra heavy duty capacitor with capacitor duty contactor and suitabe MCB TP
(k ) 2 set of 25 KVAR LTXL ultra heavy duty capacitor with capacitor duty contactor and suitabe MCB TP
(l ) Illuminated push on/off switch for each capacitor bank
(m ) Internal wiring of panel with stranded copper cable of suitable size.
S & F HT 22 KV insulators PIN type, polymer type including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut of standard size complete all as specified and directed.
Supply and install HT 22KV outdoor type gang operated air break switch, triple pole, 3 insulator double stalk type suitable for horizontal or verticle mounting with complete accessories such as mounting channels, bolts & nuts, washers, GI operating rod of suitable length etc of rating upto 200 Amps including locking arrangements including godrej 7 lever lock navtal with 3 keys, connecting up complete all as specified and directed.
Supply and install drop out fuse unit expulsion type outdoor type 200 Amps rating single pole mounted on two insulators fixed to and including MS channels with nut bolts washers etc synthetic bounded fuse carrying tube complete with HT fuse elements 25A capacity for HT 22 KV working pressure all as specified and as directed.
Supply and fixing lightning arrestor non linear type with mounting accessories complete, fixed on cross arms of pole and connected with alluminium conductor with all fittings transmission class earth system, having discharge capacity of 10 kilo amps and suitable for working pressure of 22 KV grade all as specified and as directed.
Supply and fixing aluminium bus bar for 2/4 pole structure made out of aluminium tube having outer dia 32mm and 6mm thick suitable for 22 KV complete with all suitable joints including all fittings/couplings and stainless steel nut, bolts, washers etc and insulated with colour sleevs as per colour code complete all as specified and as directed.
M&L for aluminium strip 25x3.15 mm with PVC sleeves for jumper purpose etc all as per the direction of Engineer-in-charge
Supply, lay and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire earthed, electric power cables (heavy duty) with stranded aluminium conductor, 22000 volts grade, of size 3 core x 120 sq mm .
Supply and fix cable end jointing kit for 22 KV grade cable for outdoor termination (cold shrink push on type) joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 3 core x 120 sqmm complete all as specified.
Supply and fix cable jointing kit for 22 KV grade cable for straight through (cold shrink push on type) joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 3 core x 120 sqmm complete all as specified.
Supply and fix HT cable route indicator duly painted with grey colour synthetic enamel paint two coats over one coat of red oxide primer, oval shape of size 200mmx150mmx6mm thick cast iron disc with letters embossed and fixed on 25mmx25mmx5mm thick MS angle iron for 50mm long including necessary PCC in 1:3:6 type C1 cement concrete 20mm aggregate and 15mm thick plastering all around below ground level of size 650mmx300mmx250mm embedded in PCC block all as specified.
S & F Energy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 security light fitting luminaire with high power LEDs as light source and electronic driver of capacity 36 watts with pre wired and necessary mounting arrangements and provision of 2.5 sq mm twin core copper conductor cable multi stranded from fitting to cable termination and testing complete all as specified. Make as listed in Appx 'C'.
S & F Energy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 security light fitting luminaire with high power LEDs as light source and electronic driver of capacity 72 watts with pre wired and necessary mounting arrangements and provision of 2.5 sq mm twin core copper conductor cable multi stranded from fitting to cable termination and testing complete all as specified. Make as listed in Appx 'C'.
Supply and fixing LED post top lantern 40 watt light fitting made of cast aluminium spigot housing with decarative opal acrylic diffuser with IP 65 protection complete with all accessories fixed on GI pipe 50 mm dia complete all as specified and directed. Make as listed in Appx 'C'.
S & F LED aviation lights luminaries integral LED aviation light comprising of aluminium housing with polycarbonate enclosure ,302 nos LED are provided, thick glass dome mounted on cast aluminium ring and complete with spring loaded high tension porcelain socket with neon spiral light sources 40 mm dia GI pipe entry and 19 mm dia cable gland complete fitted on OHT of any hight including twin core copper cable of 2.5 sqmm dia from aviation light to LT Panel all as directed by Engrs-in-Charge. Make as listed in Appx 'C'.
S & F Junction Box for Street Lights of size 300 x 250 x 150 mm made out of CRCA sheet 2 mm thick totally enclosed, dust and vermin proof, rain protected slanted roof top, door pasted with rubber gasket, water tight IP 42 protection single leaf shutter in front having proper locking arrangements, and powder coated and suitable size of "connectwell" stud teriminal (provision for socket bolting)- 05 Nos suitable for 415 volts, 50 Hz, 3 phase 4 wire internal wiring system including MCB SP 06 amps- 01 No and mounted on security light pole with suitable nuts, bolts complete all as specified and directed.
Supply of 8mtr high hot dip galvanised octagonal poles with 130mm bottom A/F & 70mm top A/F made up of 3mm thk. HT sheet alongwith base plate of size 200X200X16mm thk, including of 4Nos of M20X700mm long 'J' type EN 8 grade foundation bolts along with template and 1000mm Single arm standard bracket with tilt angle of 5-10 degree with connect well stud terminal ( Provn for socket bolting - 05 Nos suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system including MCB SP 06 Amps Nos and mounted inside pole complete including necessary Excavation, earth work and PCC work as per manufacturer"s drawing all as directed
M& L for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.3 mm thick, buried vertically in ground (Earth pit not less than 2.25 metres deep below normal ground level and top edge of the plate not less than 1.5 m below ground level), connected to and including Galvanised steel earthing wire 4mm dia by means of bolts, nuts & checknuts and washers etc; GI pipe 15 mm dia medium grade pipe for protection of G.I earth wire, both to be provided to the extent of 7.5 metres, all as shown on electrical plate No 3 of MES SSR-2009 Part-I, other end connected to electrical main switch board (inside the bldg) GI protection pipe buried in ground, laid under floors/plinths or fixed on walls or concealed in walls etc; with provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate , including PCC 1: 2 : 4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with G.I 20 mm dia medium grade pipe and M.S funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of strata & testing on completion.
M& L for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.3 mm thick, buried vertically in ground (Earth pit not less than 2.25 metres deep below normal ground level and top edge of the plate not less than 1.5 m below ground level), connected to and including GI strip 32x6 mm by means of bolts, nuts & checknuts and washers etc; GI pipe 40 mm dia medium grade pipe for protection of G.I earth strip, both to be provided to the extent of 7.5 metres, all as shown on electrical plate No 3 of MES SSR-2009 Part-I, other end connected to electrical main switch board (inside the bldg) GI protection pipe buried in ground, laid under floors/plinths or fixed on walls or concealed in walls etc; with provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate , including PCC 1: 2 : 4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with G.I 20 mm dia medium grade pipe and M.S funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of strata & testing on completion.
Supply, laying, testing and commissionnig of UG LT cables 1100 volts grade, XLPE insulated, screened and PVC sheathed, galvanised steel strip or wire armoured with multi stranded aluminum conductor, ISI marked, heavy duty including cable glands, cable lugs in LT panel/MDB in building etc to suit the cable including material and labour for all jointing/connecting material as required size, cables laid in trenches/ducts/under plinth floors passing through pipes etc, fixed on wall complete of following sizes :-
(a) 300 sqmm x 3.5 core (LT panel to LT sub Station)
(b) 3.5 core x 240 sqmm ( Transformer to LT Panel, and Sub Panel)
(c) 3.5 core x 150 sqmm ( LT Panel to LT Sub Panel)
(d) 3.5 core x 120 sqmm ( LT Panel to Bldg supply)
(e) 3.5 core x 70 sqmm ( LT Panel to Bldg supply)
(f) 3.5 core x 50 sqmm ( LT Panel to LT Sub Panel)
(g) 35 sqmm x 3.5 core (LT pole to Bldgs supply)
(h) 25 sqmm x 4 core (LT pole to Bldgs supply)
(j) 16 sqmm x 4 core (LT pole to Bldgs supply & Security lights)
(k) 10 sqmm x 4 core (LT pole to Bldgs supply & Security lights)
(l) 10 sqmm x 2 core (LT pole to Bldgs supply )
(m) 6 sqmm x 2 core (LT pole to Bldgs supply )
Supply, install, testing and commissioning silent Diesel Engine driven generating set 415 Volts, 3 phase 4 wire with 5 Yrs warranty as per BS 5514/IS-10002 complete with automatic ON/OFF on main failure (AMF) panel, complete with all standard accessories as per IS and norms, the capacity of DG set shall be continuous rating 50 KVA at NTP conditions with acoustic enclosure and canopy cover considering all derating factors and as applicable at Pune comprising of the following :-
(a) Alternator : Self regulated with brushless self excitation 415 V, 3 Phase, 4 wire 50 Hz, 0.8 PF, 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted screen protected drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft with necessary controls as recommended by manufacturers confirming to BS-5000/IS-4772/13364, capable of supplying unbalanced load.
(b) Engine : Multi Cylinder compression Ignition, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump, hydraulic governing mechanism, all as per BS - 5514/ IS - 3046 : 1500 RPM class A-1, governing/control guages, RPM / Hours meters etc. shaft H.P suitable for generating application and capable of giving an output of 50 KVA for coupled alternator under NTP conditions, complete with following : -
(i) Flywheel housing with flywheel to suit double bearing coupled alternator.
(ii) Flexible coupling set directly mounted to engine and alternator with coupling guard.
(iii) Air cleaner dry type with vacuum indicator.
(iv) Fuel pump and fuel piping 15 mm dia MS pipe with bends, flanges etc.
(v) Fuel filter with water separator and filter element.
(vi) Lub - Oil filter with filter element.
(vii) D.C starter 12 Volts.
(viii) Maintenance free Storage type Batteries of suitable voltage and Ampere - hours as recommended by the manufacturers.
(ix) Industrial type silencer including MS exhaust pipe lagged with asbestors rope of 5 mm dia all around and over this 50mm thick flat mineral wool insulator sheet cover and then, 24 SWG Aluminium sheet cladding with rivets, all over the length.
(x) Support / fixing arrangement for muffler with ceiling through anti vibration pads.
(xi) Engine overspeed stop / trip switch.
(xii) Radiator with fan.
(xiii) Dynamo for battery charging.
(xiv) Corrosion inhibitor coolant.
(xv) Engine control panel electronic, digital display type consisting of battery voltage indicator, lub oil temp and pressure guages, coolant water temp guage, RPM indicator-cum-hour meter etc.
(xvi) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP)
(xvii) Any other devices /accessories recommended / supplied by the manufacturers as standard eqpt.
(c) Skid : The engine and alternator shall be coupled, aligned and mounted on a specially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads. Make : - Anti vibration pads:-Dunlop / Polybond of required size and numbers as recommended by the manufacturers for mounting of 50 KVA DG set.
(d) Alternator control Panel: Floor mounted, vertical, totally enclosed cubicle, out door type, dust and vermin proof, standard industrial pattern, factory fabricated out of 2mm thick CRCA steel sheet duly painted with powder coated paint of approved colour, complete with all mounting structures, insulators, bolts, nuts, washers etc, with necessary control wiring / internal connections with proper size of copper conductor cables, suitable for 3 phase, 4 wire, 50HZ, 440 volts AC system, comprising of required Nos / rating / capacity of MCCBs for Incoming cables (Main / DG) and out going cables, multifunction meter displaying KWH, hours, current, voltage etc, set of LED type indicating lamps "LOAD ON" "SET RUNNING", power contactor suitable for 50 KVA DG set including over current, earth-fault protection realys, high voltage, No voltage, single phasing, relay. (OEM/CPRI Panel). 1 No battery charger, control circuit fuses, reverse power relay, alarm for high water / lub oil temp and low lub oil pressure, push buttons for start / stop, any other control devices / measuring instruments as recommended / supplied by the standard equipment manufacturers, complete with cable glands with gland plate for cable entry, control cabling with copper conductor armoured mult-core cables of required cross sectional area from DG set to control panel, including taking out of manual panel after disconnecting incoming and outgoing cables and reconnecting the same cables in new panel complete all as specified and directed.
(e) Diesel tank of adequate capacity for 12 hours continuous run on full load with caliberated scale (fuel level indicator) dip stick, fuel inlet / outlet, Air vent, drain plug and inlet arrangement for direct filling, including suitable size gun metal gate valve in outlet, tank shall be fitted all as per manufacturer's requirements / specification.
(f) Acoustic enclosure with canopy cover shall be provided as per latest CPCB norms.
(g) PCC platform for instalation of DG set as per specification and design given by the manufacturer.
(h) Documents : Three sets of following documents : - Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty / test certificates, schematic diagrams of control panels.
(j) Connecting cable in new panel with required accessories etc complete.
(k) Optional items : list of tools and as per manufacturers recommended lists, duly priced, item wise.
Make of DG Set :- Any of the Make listed in Appx 'C' enclosed herewith.
Notes:- (i) Contractors shall satisfactorily conduct load test of each DG set for 12 hours including run on 10% overload for 1 hour.
(ii) Testing eqpt will be arranged by the Contractor under his own arrngement and cost.
(iii) A Common PCC platform / foundation for DG sets shall be provided for above DG sets as per manufacturers instructions. Rate quoted shall be deemed to include for the same.
Supply, install, testing and commissioning silent Diesel Engine driven generating set 415 Volts, 3 phase 4 wire with 5 Yrs warranty as per BS 5514/IS-10002 complete with automatic ON/OFF on main failure (AMF) panel, complete with all standard accessories as per IS and norms, the capacity of DG set shall be continuous rating 35 KVA at NTP conditions with acoustic enclosure and canopy cover considering all derating factors and as applicable at Pune comprising of the following :-
(a) Alternator : Self regulated with brushless self excitation 415 V, 3 Phase, 4 wire 50 Hz, 0.8 PF, 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted screen protected drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft with necessary controls as recommended by manufacturers confirming to BS-5000/IS-4772/13364, capable of supplying unbalanced load.
(b) Engine : Multi Cylinder compression Ignition, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump, hydraulic governing mechanism, all as per BS - 5514/ IS - 3046 : 1500 RPM class A-1, governing/control guages, RPM / Hours meters etc. shaft H.P suitable for generating application and capable of giving an output of 35 KVA for coupled alternator under NTP conditions, complete with following : -
(i) Flywheel housing with flywheel to suit double bearing coupled alternator.
(ii) Flexible coupling set directly mounted to engine and alternator with coupling guard.
(iii) Air cleaner dry type with vacuum indicator.
(iv) Fuel pump and fuel piping 15 mm dia MS pipe with bends, flanges etc.
(v) Fuel filter with water separator and filter element.
(vi) Lub - Oil filter with filter element.
(vii) D.C starter 12 Volts.
(viii) Maintenance free Storage type Batteries of suitable voltage and Ampere - hours as recommended by the manufacturers.
(ix) Industrial type silencer including MS exhaust pipe lagged with asbestors rope of 5 mm dia all around and over this 50mm thick flat mineral wool insulator sheet cover and then, 24 SWG Aluminium sheet cladding with rivets, all over the length.
(x) Support / fixing arrangement for muffler with ceiling through anti vibration pads.
(xi) Engine overspeed stop / trip switch.
(xii) Radiator with fan.
(xiii) Dynamo for battery charging.
(xiv) Corrosion inhibitor coolant.
(xv) Engine control panel electronic, digital display type consisting of battery voltage indicator, lub oil temp and pressure guages, coolant water temp guage, RPM indicator-cum-hour meter etc.
(xvi) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP)
(xvii) Any other devices /accessories recommended / supplied by the manufacturers as standard eqpt.
(c) Skid : The engine and alternator shall be coupled, aligned and mounted on a specially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads. Make : - Anti vibration pads:-Dunlop / Polybond of required size and numbers as recommended by the manufacturers for mounting of 35 KVA DG set.
(d) Alternator control Panel: Floor mounted, vertical, totally enclosed cubicle, out door type, dust and vermin proof, standard industrial pattern, factory fabricated out of 2mm thick CRCA steel sheet duly painted with powder coated paint of approved colour, complete with all mounting structures, insulators, bolts, nuts, washers etc, with necessary control wiring / internal connections with proper size of copper conductor cables, suitable for 3 phase, 4 wire, 50HZ, 440 volts AC system, comprising of required Nos / rating / capacity of MCCBs for Incoming cables (Main / DG) and out going cables, multifunction meter displaying KWH, hours, current, voltage etc, set of LED type indicating lamps "LOAD ON" "SET RUNNING", power contactor suitable for 35 KVA DG set including over current, earth-fault protection realys, high voltage, No voltage, single phasing, relay. (OEM/CPRI Panel). 1 No battery charger, control circuit fuses, reverse power relay, alarm for high water / lub oil temp and low lub oil pressure, push buttons for start / stop, any other control devices / measuring instruments as recommended / supplied by the standard equipment manufacturers, complete with cable glands with gland plate for cable entry, control cabling with copper conductor armoured mult-core cables of required cross sectional area from DG set to control panel, including taking out of manual panel after disconnecting incoming and outgoing cables and reconnecting the same cables in new panel complete all as specified and directed.
(e) Diesel tank of adequate capacity for 12 hours continuous run on full load with caliberated scale (fuel level indicator) dip stick, fuel inlet / outlet, Air vent, drain plug and inlet arrangement for direct filling, including suitable size gun metal gate valve in outlet, tank shall be fitted all as per manufacturer's requirements / specification.
(f) Acoustic enclosure with canopy cover shall be provided as per latest CPCB norms.
(g) PCC platform for instalation of DG set as per specification and design given by the manufacturer.
(h) Documents : Three sets of following documents : - Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty / test certificates, schematic diagrams of control panels.
(j) Connecting cable in new panel with required accessories etc complete.
(k) Optional items : list of tools and as per manufacturers recommended lists, duly priced, item wise.
Make of DG Set :- Any of the Make listed in Appx 'C' enclosed herewith.
Notes:- (i) Contractors shall satisfactorily conduct load test of each DG set for 12 hours including run on 10% overload for 1 hour.
(ii) Testing eqpt will be arranged by the Contractor under his own arrngement and cost.
(iii) A Common PCC platform / foundation for DG sets shall be provided for above DG sets as per manufacturers instructions. Rate quoted shall be deemed to include for the same.
Supply and Installation, commissioning of wall mounted inverter split AC unit outdoor/indoor complete with cordless remote control unit of capacity 1.5 TR, working with R410A refrigirent and defrosting sensor technology copper condenser coil, BEE 5 star rating complete all as specified of make as listed in Appendix 'C'.
Supply and Installation, commissioning of wall mounted inverter split AC unit outdoor/indoor complete with cordless remote control unit of capacity 2 TR, working with R410A refrigirent and defrosting sensor technology copper condenser coil, BEE 5 star rating (2019) complete all as specified of make as listed in Appendix 'C'.
Supply and fix voltage stablizer for automatic operation, single phase naturally air cooled indoor type and designed for inpur variation between 170 volts to 250 volts with out put voltage stablized at 230 volts with accuracy of + 2.5% and capacity 5 KVA suitable for A/C complete all as specified of any of make listed in Appendix 'C'.
Supply and Installation, commissioning of Inverter Refrigerator, electric driven, single phase, 230 volts, 50 Hz, direct cool single door, having capacity 215 Ltrs working with non CFC refrigirent and 5 star rating (2019) with PVC stand for resting the refrigerator complete all as specified and as directed. MAKE- model no. GL-B221AASY of LG or equivalant in Voltas, Blue star, Carrier,Samsung
Supply and Installation, commissioning of Inverter Refrigerator, electric driven, single phase 230 Volts. 50 Hz, direct cool, double door, having capacity 290 to 315 Ltrs, frost free working with non CFC refrigirent and 4 star or above (2019) rating complete all as specified and as directed. MAKE- Voltas, Blue star, Carrier,Whirlpool
Supply and Installation, commissioning of Deep freezer, electric driven, single phase, having capacity 400 Ltrs metal top, double door working with non CFC refrigirent MAKE- Blue star model CHF400 or equivalant in Voltas, Lloyd
Supply and fixing desert cooler, electric driven (single phase), PVC body having nominal air flow capacity of 4700- 5000 Cum per hour (or nearest size) including MS stand of height upto 1 Mtr complete all as specified and directed. MAKE- crompton ozone 55 ltrs or equivalent in Havells, Bajaj, Symphony
Supply and fixing self contained drinking water cooler fully stainless steel body, working with non CFC refrigerent suitable for operation on 230 Volts, 50 cycles, AC supply having approx storage and nominal cooling capacity 40/80 Ltrs including connecting the itmes complete all as specified and directed of make:- Voltas, Blue star, Carrier
Supply and fixing self contained drinking water cooler fully stainless steel body, working with non CFC refrigerent suitable for operation on 230 Volts, 50 cycles, AC supply having approx storage and nominal cooling capacity 60/120 Ltrs incl connecting the itmes complete all as specified and directed of make :- Voltas, Blue star, Carrier
Supply and fix voltage stablizer for automatic operation, single phase naturally air cooled, indoor type and designed for input variation between 170 volts to 250 volts with output voltage stablized at 230 volts with accuracy of + 2.5% and capacity 1 KVA suitable for above water cooler of any of make listed in Appendix 'C'.
Supply and fix modular box with inner and outer plate including telephone socket 1 module complete all as specified and as directed. Make: Legrand/ Havells/HPL/Anchor
Supply and laying synthetic insulating mat of thickness 3mm complete all as specified and as directed.
M & L for 200 mm thick (compacted thickness) Granular Sub Base (GSB) of Grade I as per Table 400-I of MORT&H, IRC specification laid with mechanical paver rolled and compacted to required gradient and camber with 8 to 10 tonne power roller and vibratory roller complete complete as per MORT&H specification clause-401 including all tools and plant and managing diversion all as specified and as directed. complete all as specified and as directed.
M & L for 150mm thick (compacted thickness) Wet Mix Macadam (WMM) laid in two layers 75mm each layer, laying spreading (with paver finisher only) and compacting base course of graded stone aggregates and granular material conforming to MORT&H specifications,(Table 400-II) in layers of equal compacted thickness each, consolidated, including pre-mixing the material with water at OMC in mechanical mixer, carriage of mixed material by tippers to site, laying in uniform layers in base course on a well prepared sub base/ base course and compacting with power vibratory roller to achieve the desired density complete as per MORT&H specification clause -406 including material, labour, machinery, lighting, guarding and maintenance of diversion, complete all as specified and as directed.
M&L for 60mm thick machine pressed pre-cast cement concrete interlocking paver blocks with grey cement and pigment, rubber moulded any shape and size confirming to IS 15658-2006, M-35 grade as in floor/pavement laid over and including 30mm thick crushed stone sand complete all as specified and as directed.
M & L for 5500 Ltrs capacity LLDPE septic tanks with item code RLSMSST5501B of Make Supreme or Sintex Model No CCST-500-01 Septic Tank including exc in any type of soil, PCC 1:2:4, 50 mm thk floor over 100mm thk hardcore of stone aggregate around 1mtr of septic tank complete all as specified and as directed. Note- All necessary pipes and fittings to accommadate inlet and outlet pipes shall be included in the rates quoted.
M & L for soakage well of size 1.8m diax 3.0m effective depth, excavation in any type of soil, foundation in PCC 1:3:6 type C-2 using 40mm graded coarse stone aggregates, walls of honey combed masonry with top ring of M-25 concrete including intercepting chamber and screen chamber made of fly ash brick masonry in CM 1:4, RCC cover slab in M-25 grade concrete /SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats all as specified and as directed.
Preparation of newly plastered surfaces of walls and applying two coats of weather coat paint over a coat of primer ( Apex of Asian Paint or equivalent of Make given in Appx C) over a coat of wall care putty in plain surfaces of walls.
M & L for 20 mm thick thermocol sheets as in expansion joints of columns all as specified and as directed.
Cutting of whole Jungle/ babool/ Ber/ Subabool/ Neem/ Hivar / Safeda/ Khajoor/ Jalibi/ Emli trees of girth exceeding 30cm and not exceeding 100cm including cutting of branches, trunk etc. complete and grubbing up tree trunk including cutting of trunk portion protruding over ground, digging out roots, filling holes and levelling off ground, staking of serviceable material and removing of unserviceable material from site and clearing the site complete, all as specified and as directed.
Cutting of whole Jungle/ babool/ Ber/ Subabool/ Neem/ Safeda/ Khajoor/ Jalibi/ Emli trees of girth exceeding 100cm and not exceeding 150cm including cutting of branches, trunk etc. complete and grubbing up tree trunk including cutting of trunk portion protruding over ground, digging out roots, filling holes and levelling off ground, staking of serviceable material and removing of unserviceable material from site and clearing the site complete, all as specified and as directed.
Cutting of whole Jungle/ Ber/ Subabool/ Emli trees of girth exceeding 150cm and not exceeding 200cm including cutting of branches, trunk etc. complete and grubbing up tree trunk including cutting of trunk portion protruding over ground, digging out roots, filling holes and levelling off ground, staking of serviceable material and removing of unserviceable material from site and clearing the site complete, all as specified and as directed.
Cutting of whole Jungle/ Subabool/ Emli trees of girth exceeding 200cm and not exceeding 250cm including cutting of branches, trunk etc. complete and grubbing up tree trunk including cutting of trunk portion protruding over ground, digging out roots, filling holes and levelling off ground, staking of serviceable material and removing of unserviceable material from site and clearing the site complete, all as specified and as directed.
Grubbing up tree having girth of tree exc 30cm and n exc 300cm including digging out roots, filling holes and levelling off ground, and replacement of the same upto 1.00km radius within the same location in defence land including maitenance of same trees during defect liability period (rates deemed to be included all T & P, machinery for transporting and implantation including fertilizers etc). Note- Replantation shall be carried out as per the Min of Forest and Environment guidelines at the time of shifting.
Ashoka Tree (4.00 to 7.00m ht appox)
Mango Tree (4.00 to 7.00m ht appox)
Pipal Tree (4.00 to 8.00m ht appox)
Bahava Tree (4.00 to 7.00m ht appox)
Chandan Tree (4.00 to 5.00m ht appox)
Shisham Tree (4.00 to 6.00m ht appox)
Jammun Tree (4.00 to 7.00m ht appox)
Bell Tree (4.00 to 6.00m ht appox)
Vilaiti emmli Tree (4.00 to 7.00m ht appox)
Shisham Tree (4.00 to 7.00m ht appox)
Bargad Tree (7.00m ht appox)
Chafa Tree (6.00 to 7.00m ht appox)
Golmohar Tree (7.00m ht appox)
Drumstick Tree (5.00m ht appox)
V M MATERE INFRASTRUCTURES INDIA PVT LTD
GANGA INFRABUILD PVT LTD
MANGLA AMIT BUILDERS PVT LTD
RAGHUSONS INFRA ENGINEERING PVT. LTD
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
DHARIWAL TRADERS PRIVATE LIMITED
TAPI PRESTRESSED PRODUCT LTD.
Som Projects Pvt Ltd
SOOD ASSOCIATES PVT LTD
surendra infrastructure pvt ltd
stage.html
html • 0.09 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid