Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹81.6 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | Rejected-Technical | - | Rejected-Technical not qualified as per terms and conditions of SBD and NIT |
| Sl No | Description | Qty | Unit | Trade Linkers Associates L1 |
|---|---|---|---|---|
| 1.0033kV equipment | ||||
| 2.00 | Supply, Installation, Testing and commissioning of 33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 31.5 KA for 3 sec) outdoor type with all accessories and auxiliaries along with supporting structures etc. complete in all Respects SS BODY, UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES if required, modification in the erection of vcb can be done as per approved design at site. | 1 | Nos | 3,65,000 ₹3,65,000 Lowest |
| 3.00 | Supply, Installation, Testing and commissioning of 2 core 6 sq.mm , 1100V .PVC insulated ,PVC sheathed FRLS Galvanized steel wire/strip armored stranded copper conductor control cable complete. | 1,000 | Mtrs | 220 ₹2,20,000 Lowest |
| 4.00 | Supply, Installation, Testing and commissioning of 4 core 16 sq.mm , 1100V,PVC sheathed FRLS Galvanized steel wire/strip armored copper conductor control cable complete. | 2,400 | Mtrs | 1,030 ₹24,72,000 Lowest |
| 5.00 | Supply, Installation, Testing and commissioning of 250 KVA oil cooled servo stabiliser 3-phase 4 wire copper wound indoor type, input voltage range 250-460V, output 415V ± 1%, having, Digital control, Response time <10ms Automatic Switch-Off against:· Under / Over-Voltage· Over Load & Short – Circuit· Single Phasing, Class C Type Secondary surge Protection | 1 | Nos | 5,75,000 ₹5,75,000 Lowest |
| 6.00 | Supply, Installation, Testing and commissioning of 185mm² 3½ Core,1.1kV Grade, Armoured,XLPE Insulated Stranded aluminium Conductor FRLS type | 0.38 | km | 11,50,000 ₹4,31,250 Lowest |
| 7.00 | Supply, Installation, Testing and commissioning of DC Distribution panel (110V DC) with 1NO 10Amp Air break ckt. Doublee pole for battery incoming supply with DP MCBs and indicating lamps | 1 | No | 2,25,000 ₹2,25,000 Lowest |
| 8.00 | 70 mm² 3½ Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type | 0.16 | km | 5,30,000 ₹85,860 Lowest |
| 9.00 | Supply, Installation, Testing and commissioning of AC Distribution Panel (415 V, AC) complete with ckt Breakers, indicating Lamps etc for 132/33KV Grid Station MS | 1 | Nos | 28,00,000 ₹28,00,000 Lowest |
| 10.00 | Supply, Installation, Testing and commissioning of 110 V,200 AH Battery charger (Three phase): (i) Float charging and load current ratings: 30 Amp /60Amp / 70Amp / 100Amp at 220 V to 252 V D.C.(ii) Boost charging current rating: 50 Amps / 55Amp /60Amp / 70Amp / 80Amp / 100 Amp at 198 V to 296/302 V D.C. | 1 | Nos | 4,25,000 ₹4,25,000 Lowest |
Tender Value
₹74.0 L
EMD Value
₹1.5 L
Closing Date
6 Oct 2025, 2:00 pmClosed
Executive Engineer TLMD-II, JKPTCL, Gladni, Jammu
Executive Engineer TLMD-II, JKPTCL, Gladni, Jammu
Replacement of battery charger and battery bank (110V,200AH), AC and DC board and commissioning of new VCB 33kv,commissioning of 132kv PT and servo voltage stablizer 250 Kva and power cables replacement along with allied works at GSS Miran Sahib
2025_PDD_284673_1
TLMD-II/J/07 of 2025-26 Dated 20-08-2025
Open Tender
Electrical Works
Turn-key
180 days
Miran Sahib
As Per NIT and SBD
3 documents required · 3 mandatory
₹2,360
Executive Engineer TLMD-II, JKPTCL, Gladni, Jammu
₹1.5 L
24 Oct 2025
20 Aug 2025
8 Oct 2025
20 Aug 2025
6 Oct 2025
21 Aug 2025
Amount
33kV equipment
Supply, Installation, Testing and commissioning of 33KV VCB (36 KV, 2000 Amps of 3 phase, 50 c/s and 31.5 KA for 3 sec) outdoor type with all accessories and auxiliaries along with supporting structures etc. complete in all Respects SS BODY, UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES if required, modification in the erection of vcb can be done as per approved design at site.
Supply, Installation, Testing and commissioning of 2 core 6 sq.mm , 1100V .PVC insulated ,PVC sheathed FRLS Galvanized steel wire/strip armored stranded copper conductor control cable complete.
Supply, Installation, Testing and commissioning of 4 core 16 sq.mm , 1100V,PVC sheathed FRLS Galvanized steel wire/strip armored copper conductor control cable complete.
Supply, Installation, Testing and commissioning of 250 KVA oil cooled servo stabiliser 3-phase 4 wire copper wound indoor type, input voltage range 250-460V, output 415V ± 1%, having, Digital control, Response time <10ms Automatic Switch-Off against:· Under / Over-Voltage· Over Load & Short – Circuit· Single Phasing, Class C Type Secondary surge Protection
Supply, Installation, Testing and commissioning of 185mm² 3½ Core,1.1kV Grade, Armoured,XLPE Insulated Stranded aluminium Conductor FRLS type
Supply, Installation, Testing and commissioning of DC Distribution panel (110V DC) with 1NO 10Amp Air break ckt. Doublee pole for battery incoming supply with DP MCBs and indicating lamps
70 mm² 3½ Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type
Supply, Installation, Testing and commissioning of AC Distribution Panel (415 V, AC) complete with ckt Breakers, indicating Lamps etc for 132/33KV Grid Station MS
Supply, Installation, Testing and commissioning of 110 V,200 AH Battery charger (Three phase): (i) Float charging and load current ratings: 30 Amp /60Amp / 70Amp / 100Amp at 220 V to 252 V D.C.(ii) Boost charging current rating: 50 Amps / 55Amp /60Amp / 70Amp / 80Amp / 100 Amp at 198 V to 296/302 V D.C.
Supply, Installation, Testing and commissioning of Battery Bank 110 V, 300 AH , of 55 No. cells of 2V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant
Dismentling of old equipmentas and shifting of the same to divisional store Gladni
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .