| 1.00Inspection and rectification of gas leakage of 132 KV SF-6 Circuit breaker type 120-SFM-32B of 132 KV S/S Naini Complex and 132 KV Karchhana Prayagraj. The job includes opening of assembly from upper and lower terminal flanges cleaning of all groves of flanges and porcelain with petrol, scrubber pad and acrylic solution. Replacement of all O-ring of the pole and gas pipe fittings by applying annabond adhesive. Reassembly of pole then evacuation of pole upto 760 mm hg after testing of vacuum for 12 hours and satisfactory result, refilling of SF-6 gas upto required level Checking of proper operation of circuit breaker from local and remote all materials T&P except SF-6 gas required for execution of work will be arranged by the contractor at his own cost. | |||||
| 1.01 | 40MVA Transformer-2 bay (CGL Make) Mfd-2010 at 132 KV S/S Naini Complex. | 1 | Job | 39,990 ₹39,990 Lowest | 50,000 ₹50,000 |
| 1.02 | 132 KV Rewa Road Bay (ABB Make) Mfd-2018 at 132 KV S/S Naini Complex. | 1 | Job | 39,988 ₹39,988 Lowest | 50,000 ₹50,000 |
| 1.03 | 20 MVA Transformer Bay (CGL Make) Mfd-2008 at 132 KV S/S Karchhana. | 1 | Job | 39,970 ₹39,970 Lowest | 50,000 ₹50,000 |
Tender Value
₹2.3 L
EMD Value
₹2,700
Closing Date
5 Jan 2026, 5:00 pmClosed
Superintending Engineer
Electricity Transmission Circle-II, U.P. Power Transmission Corporation Ltd. 57- George Town, Prayagraj.
Rectification of Gas leakage of 145 KV SF6 circuit breaker at 132 KV S/S Naini Complex and Karchana, under ETD-III, Prayagraj.
2025_UPTCL_1102612_1
46/ETC-II(P)/2025-2026
Open Tender
Electrical Works
Item Rate
60 days
132 KV S/S NAINI, KARCHANA
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Executive Engineer Electy. Trans. Div. Naini Alld.
₹2,700
2 Jul 2026
30 Dec 2025
6 Jan 2026
30 Dec 2025
5 Jan 2026
30 Dec 2025
Inspection and rectification of gas leakage of 132 KV SF-6 Circuit breaker type 120-SFM-32B of 132 KV S/S Naini Complex and 132 KV Karchhana Prayagraj. The job includes opening of assembly from upper and lower terminal flanges cleaning of all groves of flanges and porcelain with petrol, scrubber pad and acrylic solution. Replacement of all O-ring of the pole and gas pipe fittings by applying annabond adhesive. Reassembly of pole then evacuation of pole upto 760 mm hg after testing of vacuum for 12 hours and satisfactory result, refilling of SF-6 gas upto required level Checking of proper operation of circuit breaker from local and remote all materials T&P except SF-6 gas required for execution of work will be arranged by the contractor at his own cost.
40MVA Transformer-2 bay (CGL Make) Mfd-2010 at 132 KV S/S Naini Complex.
132 KV Rewa Road Bay (ABB Make) Mfd-2018 at 132 KV S/S Naini Complex.
20 MVA Transformer Bay (CGL Make) Mfd-2008 at 132 KV S/S Karchhana.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.03 MB
TD1.pdf
Tender Documents • 0.35 MB
BOQ_2033041.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].