Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.9 LAccepted-Finance | L1 | Accepted-Finance BEING LOWEST | |
| 2 | L2₹28.5 L+₹2.6 L (10.2%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹29.4 L+₹3.5 L (13.7%)Rejected-Finance | L3 | Rejected-Finance BEING NOT LOWEST | |
| 4 | L4₹29.8 L+₹3.9 L (14.9%)Rejected-Finance | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹31.8 L+₹5.9 L (22.7%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
7 Mar 2020, 6:00 pmClosed
MR ARIZ AHMED
GE U ELECTRIC SUPPLY DELHI CANTT-10
Provn Of SF6 Breakers for 8 10 Mva 33 11 Kv transformer at 33 KV Shankar Vihar Grid and Provn And Installation of 16 X Security lights alongwith fencing of 261 Arty Bde Camp Under GE U E S Delhi Cantt 10
2020_MES_311748_1
GE ELECT/D-93/2019-2020
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹56,000
Yes
14 Mar 2020
4 Feb 2020
9 Mar 2020
5 Feb 2020
7 Mar 2020
20 Feb 2020
Amount
Supplying , transporting, erectiong, testing and commissioning of 36 KV, 1800MVA, 1250A, 50Hz voltage class outdoor type Vacuum Circuit Breaker for use on system voltage 33 KV. The circuit breaker and accessories shall conform to IEC-62271-100 or IS 13118 and other relevant IEC/IS standard. The circuit breaker shall be complete with terminal connection, operating mechanism, control cabinets, cable from yard to control room along with accessories like gland, terminal block, lugs, necessary steel support structure and RCC foundation for CB and control cabinet The circuit breaker shall be required to performs as per technical parameters given below:-
(a) Installation - Outdoor, 3-pole, Vacuum Live-Tank, Porcelain Clad, Switchyard Breaker (b) Rated Voltage - 36 KV (c) Rated Current - 1250A or higher up to 2000Amps (d) Power frequency with stand voltage (KV rms)- 70 KV (e) 12/50 microsecond lighting impules with stand voltage (KV Peak)-170 kVp (f) Rated short circuit current breaking capacity (3 Sec ) at rated voltage specified 31.5 KA (g) Control Voltage incl. trip/close coil - 50V DC (h) Spring Charging Voltage - 230VAC (j) Symmetrical interrupting capacity (KA/RMS) 31.5 KA (k) Rated short circuit Making Current (KAP)-80A (l) Out of phase breaking capacity (KA rms) as per IEC (m) Rated operating duty as per IEC(o) Temp rise over the design ambient temperature -As per IEC 62271-100 (n) Operating Mechanism -Spring (o) Creepage distance as per IEC-900mm (p) No of trip/close coil 50 V DC-02 Nos (q) Tripping system - 50 V DC
Note:- (i) Cost of supply and fix of Outdoor type Terminal Kiosk (TK) having terminals/disconnecting-links for termination of CT/PT wiring including PT secondary fuses complete all as required at site are deemed to be included in the quoted rate. (ii) Cost of construction of foundation including construction material, necessary earth work and steel structure as per manufacturer design for breaker & TK complete all as required at site are deemed to be included in the quoted rate.
Supply, installation, testing & commissioning of air bake off load line isolator switch rotating type manually gear drive mechanism operated highest system voltage 36 KV rated current 1250 Amps triple pole with earthing device each pole consist of mechanical interlocks insulating pedestals 03 Nos on galvanized steel base as per BSS /IS incuding rotating blade of HDE copper & fixed contacts of same material, spring loaded arcing horns of adequate section to brake magnetizing current of transformer as directed with adequate 50mm dia GI operating pipe for operation from ground level & operating handle complete with both off & on positions complete all as specified & directed.
All as per item No 2 here in before but bus isolator without earthing device
Supplying and fixing , Stretching, Securing, Connecting & testing of Aluminium Conductor Steel Reinforced (ACSR) of size Zebra/Dog/Goat/Panther/Wolf for 33 KV yard for jumper complete all as specified and as directed. Note : Rate quoted include the cost of end connection as per site requirement
Supply, installation laying & testing of 33KV control & relay panel indoor type for Vaccum Circuit Breaker. The panel shall be with back access double door arrangement, dust and vermin proof , IP -54 class protection and made 2mm , CRCA MS sheet powder coated finsh over one coat of red oxide primer both side operating type, including internal wiring using 1.1kV FRLS insulated multistrand cable (2.5sqmm for CT/PT and control circuit, numbered and colour coded as per IS-5578/1984 having suitable entry for cable consisting of the following:-.
(A) Main, Numerical Protection Relay with LCD displaying mimic bay for ON/OFF control and monitoring of feeder current. Built in disturbance recorder and event logger to monitor the Sequence of Events (SoE) using upto 1000 event codes. The relay shall be communicable on IEC 61850 GOOSE platform, using RJ-45/USB/FO port and capable of Binary Signal Transfer between local and remote relay over Fiber Optic. (i) Line Differential with high set and low set (stabilized) with second harmonic restraint to bypass transformer inrush. The scheme will be implemented using Single Mode Fibre Optic protection communication link between local and remote relay.Suitable single mode Fiber optic port shall be part of the relay including connected items like LIU and Patch cord etc. (ii) Over current and earth fault protection with minimum pickup at low set of 5% and 1% respectively (iii) Transient/intermittent earth fault protection (iv) Phase discontinuity protection
(B) Flush mounted auxillary relays for:- (i) Trip Circuit Supervision (ii) Master Trip (iii) Fuse fail (PT) supervision operated (iv) SF-6 gas Presssure Low (v) DC supervision scheme
(C) Metering (i) Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-Vector-Meter (Acc.Cl.0.5). (ii) 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port.
(D) Indicating Lamp (i) Bus-01 Isolator ON/OFF (ii) Bus-02 Isolator ON/OFF (iii) Line Isolator ON/OFF/EARTH (iv) CB auto trip (v) CB ON (vi) CB OFF (vii) CB Spring Charge (viii) Trip circuit healthy (ix) DC Available LED with push-button (x) R-Y-B Phase LED Indication
(E) Semaphore indicator (i) Circuit Breaker ON, OFF (ii) Bus-01 Isolator ON, OFF (iii) Bus-02 Isolator ON, OFF (iv) Line Isolator ON, OFF, EARTH
(F) Control switches/Push Buttons (i) Trip-Neutral-Close Switch for Circuit Breaker Control - 01no. (ii) MCB for AC isolation - 01no. (iii) MCB for DC isolation - 01no. (iv) Heater switch with thermostat - 01no. (v) 3-pin socket with ON/OFF switch - 01no. (vi) CFL Lamp with ON/OFF switch - 01no.
(G) 08-Window Annunciator with hooter and Mute, Acknowledge, Reset and Test buttons for:- (i) OC Trip Alarm (ii) EF Trip Alarm (iii) Line Differential Trip Alarm (iv) PT Fuse Failure Alarm (v) SF6 Gas Pressure Low Alarm (vi) Trip Circuit Failure (vii) Spare.
(H) Test Terminal Block for CT
(I) Suitable terminal arrangement along with Light Interface Unit, Patch-cord and associated port for spliced connection with external armoured fibre-optic cable shall be provided for achieving pilot-wire connection (line-differential).
Supply, installation, testing and commissioning 33 KV current transformer oil cooled out door single phase, oil immersed and self cooled type of ratio 400-200/1-1-1-1 suitable for metering and protection equipment installed on control panels terminal block as specified below :- ( For 33/11 KV VCB) (a) Normal System Voltage-33 KV (b) Highest System Voltage-36 KV (c) Rated Primary current- 400-200 Amp (d) Rated secondary current- 1 Amp (e) Nos of Core - 4 (f) Core01: Accuracy class 5P10, 10VA, ALF ≥10 (g) Core02: Accuracy Class 1.0, 10VA, ISF ≤ 5 (h) Core 03 Protection core accuracy class -PS,Protection knee point voltage- 300 Volt at lower ratio (j) Core 04-Spare (k) Continuous thermal current rating 120 % of rated primary current (l)Temp rise at rated contineous thermal current over ambient at site - Less than or equal to 45 degree C (m) Insulation Level- 36/70 KV.170 KVP (n) 1.2/50 Micro second impulse withstand test voltage- 170 KV (peak) (o) Short time thermal current rating for one second - 25 KA/1 Second (p) Dynamic Current Rating - 62.5 KA ( peak) (q) Porcelain Bushing type - Hollow Cylinder (r) Creepage distance of HV bushing - 900 mm (min) (s) Primary & Secondary winding material - Copper
Supply installation, testing and commissioning Potential Transformer (PT) oil cooled out door single phase ( Earthed type) of voltage ratio 33 KV/110 V class 3P - 0.5-3, burden 50 VA insulation level of 70/170 KV as specified below:- (a) Normal System Voltage-33 KV (b) Highest System Voltage-36 KV (c) Rated Primary voltage- 33 KV/√3 (d) Rated secondary voltage- 110 V/√3 (e) Nos of Lt winding 2 (f) Metering Core Accuracy class - 0.5 (g) Metering Core Rated Burden- 50 VA (h) Nos of Phase- Single (Earthed Type) (j) Protection core accuracy class - 3P (k) Protection core rated Burden - 50 VA (l) Rated Voltage Factor - 1.2 continuous & 1.5 for 30 Sec (m) Insulation Level- 36/70 KV.170 KVP (n) Temp rise at rated contineous thermal current over ambient at site - 45 0C (o) Porcelain Bushing type - Hollow Cylinder (p) 1.2/50 mcro second impulse withstand test vol -170 KV (Peak) (q) Creepage distance of HV bushing - 900 mm (min) (r) Primary & Secondary winding material - Copper
Supply and erect steel Structures with ISMB/Channnel/Angle iron/Flat including necessary hard ware in any shape or size including GI Nut, bolts,washers, clamps such as "T" Clamps,PG Clamps,Isolator clamps,CT,PT,Transformers, VCB Breakers clamps and line seperator for Bus Bar of 33 KV made of any materials suitable for above structure/equipments as directed and inclusive of one primer coat, one under coat and one finishing coat of paint for a way extension at Shankar Vihar Grid complete all as specified and directed.
M & L control cable of 2.5 sqmm , 12 core 1100 volt pvc insulated with HDPE conduit buried in trench, fixed on walls , laying in cable ducts from the yard CT/PT to control panel/RTCC Panel of building
M & L for complete connection of the existing line bkeakers, CTs & PTs of 33 KV for line protection scheame by removal of existing required control cables & accessories carefully & refixing , testing to new installed RTCC line differential relay & control panel and making connection for the installed new vaccum breaker, CTs & PTs of 33 KV for transformer protection scheame with the existing RTCC panel with new provisioned control cables testing complete all as specified and directed, Note : Rate quoted included calibration of the line differential relay.
Material and labour for PCC 1:3:6 type C1 using 20mm graded stone aggregate for mounting of 33 KV CTs/PTs including necessary form work, finished the exposed surfaces fair without using extra cement including necessary form work complete all as specified and as directed.
Supply & installing steel tubular swaged poles type 410 SP-31 (9 mtr long) of approx wt.147 kg conforming to IS 2713 (Part-II) including excavation, earth work, PCC foundation, base plate,PCC coping,GI pipe for cable protection etc. and GI bracket for fitting mounting, complete all as per manufacturer's instructions and as specified and as directed by E-in-charge. NOTE:- The unit rate in this item is deemed to be included the cost of exacavation and earth work in soft/loose soil,PCC foundation 1:4:8 type D-2 (40 mm graded stone aggregate), PCC coping 1:2:4 type B-1 (20 mm graded stone aggregate) as in steel tubular pole and GI bracket made of GI pipe medium grade 40 mm bore, 1.5 mtr long for fixing of street light fitings . The steel pole shall be painted by bituminious paint total length inside and up to planting depth outside and remaining portion of pole painted with two coat of aluminium paint over a coat of red oxide complete all as specified and directed.
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge. Note : Measurement shall be taken after putting down.
Supplying, laying, jointing testing and connecting XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 marked, suitable for HT 1100 V system, laid in trenches fixed to pole, including jointing & testing complete all as specified and directed of following sizes:- Note :- Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately under respective items of schedule.
16 Sqmm 4 core
35 Sq mm 3.5 core.
50 Sq mm 3.5 core.
185 Sqmm 3.5 core
Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade size 185 sqmmx 3.5 core complete all as directed.
Supply, install, test and commissioning in replacement of factory made tested LT panel board cubical double door compartment outdoor type plate mounted suitable for , 415 volts 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bar of rating 800 Amp installed on proceline/ SMC insulator. The panel shall be dust and vermin proof IP -65 class protection and made of 3.15 mm CRCA sheet and inner compartment 2 mm thick, 40X40X6 mm thick MS angle iron frame work, powder coated finished over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer and rear opening type with apran for cable entery closing locking arrangement including internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked , 1100 volts grade of appropriate size (but not less than 4.0 sqmm) and comprising of the following including necessary PCC in 1:2:4 type B1 using 20mm graded stone aggregate for platform of suitable size:-
Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.25 m below normal ground level) with top edge of earth plate not less than 2.5m below normal ground level, connected to galvanized lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised ironside complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 15 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply & Fix fiber/GRP KIOSK box weather proof incluiding made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120 mm out side and 300x200x105 mm inside dimensions comprising of aluminium bus bar 4 strip for 3 phase and neutral 63 Amps and 02 A SP MCB with base incluiding embossing/ painting of danger notice of size not less than 10cm x 7.5 cm with letters,figures band conventional skull and bones in signal red colour on front face of KIOSK box body complete all as specified and directed.
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 40 to 100 mm bore and making good both ends all specified and directed
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of 50 mm bore sizes
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of 100 mm bore sizes
Supply, installation, commisioning and testing of LT 415 Volts 50 Hz, timer panel out door type made out of CRCA sheet 3.15 mm thick made to shape for fitted with the followiing:- (a) 3 pole power contactor ML-6 - 01 No (b) Intelligent light base outdoor lighting control switch three phase upto 20 amp per phase -01 No (c) Switch fuse disconnector (panel mounting cubical type ) TPN, 415 Volts open execution with 3 No HRC fuses, 125 Amps,-01 No (d) Panel wiring with single core copper flexible cable 1.5 Sqmm PVC insulated, 1100 volts grade from switch connector fuse to ML-6 contactor including copper lugs and timer wiring contactor coil wiring with 1.5 Sqmm copper cable PVC insulated including copper lugs of proper size. (e) Complete cable connections of incoming/outgoing cables and testing on load after completion of work all as specified
S&F LED street light fitting 45 watt pressure dia cast aluminum housing, heat resistant toughened class with frame, IP 66 protection and better optics for uniform distribution
S&F LED flood light fitting 200 watt pressure dia cast aluminum housing, heat resistant tempred glass for protection with integreated driver 5 KV surg protection applicable for large area lightning, IP 66 protection along with fixing bracket. Note : Rate quoted includes the GI pipe base & necessory PCC works as required at site.
S&F LED post top lantern light fitting 40 watt decorative for 360o indirect light, resistant to impact and corrosion, Glare free and better uniformity, IP-65 protection, M-Milky verson.
S&F PVC two core copper conductor 2.5 sqmm for connection of light fitting.
MV Engineers And Contractors
Buddham Builders
M/s Birja Nand
mayur enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .