Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹262.5 CrAccepted-Finance | ₹262.5 Cr | L1 | Accepted-Finance Responsive |
Tender Value
₹75.8 Cr
EMD Value
₹1.5 Cr
Closing Date
8 Sept 2023, 5:00 pmClosed
SE(TW), JVVNL, Jaipur
Office of The Superintending Engineer (TW), Old Power House Premises, Near Ram Mandir, Banipark, Jaipur-302006
Survey, Design, Supply, Erection, Testing, Commissioning n afterward 10 years comprehensive Operation n Maintenance of 20 Nos. 33_11 KV Grid Sub-stations n associated Infrastructure on turnkey basis on BOOT model under Alwar, Bharatpur and Dholpur.
2023_JVVNL_355404_2
TN-545
Open Tender
Electrical Works
270 days
Jaipur Discom
As per bidding document
3 documents required · 3 mandatory
₹2,950
Jaipur Vidyut Vitran nigam ltd.,
₹1.5 Cr
Yes
9 Oct 2023
21 Aug 2023
11 Sept 2023
21 Aug 2023
8 Sept 2023
21 Aug 2023
21 Aug 2023 - 23 Aug 2023
Amount
Supply of 5 MVA 33/11KV Copper wound Power Transformer complete with first filling of transformer oil , OFF circuit tap changer and all fittings
Supply of outdoor 12 KV O/D VCB KIOSK complete with accessories including use of special tools & conducting all pre commissioning tests before energisation, complete in all respect
Supply of outdoor 36 KV O/D VCB KIOSK complete with accessories including use of special tools
Supply of 33/11KV S/S structure (Galvanized) on existing PCC Poles including necessary nut & bolts & clamps etc. steel wt. 4087 Kg. made of MS Channel 100x50, MS Flat 50x6 and MS Sheet as per approved design and drawing.
Supply of control Cable of size 2 X 2.5 SQ.MM. 1100 Volts PVC Insulated including supply of ferrules to design various cores of control cables by terminal no. of identification including utilisation of cable gland.
Supply of control Cable of size 4 X 4 SQ.MM. 1100 Volts PVC Insulated including supply and installation of ferrules to design various cores of control cables by terminal no. of identification including utilisation of cable gland.
Supply of control Cable of size 12C X 2.5 SQ.MM. 1100 Volts PVC Insulated including supply of ferrules to design various cores of control cables by terminal no. of identification including utilisation of cable gland.
Supply of overhead steel cord aluminium ACSR 200 sqmm [ 30+7 strand, 3+3 mm] Panther conductor, COMPLETE IN ALL RESPECT. (COST OF MATERIAL INCLUDES THE SAG AND JUMPERING)
Supply of PG Clamps for Panther conductor
Supply of T-Clamps for Panther Conductor
Supply of overhead steel cored aluminum ACSR DOG[100SqMM(6+7) /(4.72+1.57)] conductor complete in all respect as per latest specification and drawing
Supply of M.S. Flat 50 X 6 mm (Galvanised as per I.S) for earthing
Supply of HD Galvanised M.S.Rod type earthing set (including nuts & bolts) made up of M.S.Rod 20 mm dia. 3 meter long alongwith earthing clamp & 8 SWG earth wire 15 meter long and connecting the MS Rod type earthing set.
Supply of 11 /0.4 KV 25 KVA AL- wound, conventional outdoor type distribution transformers with all fittings and accessories and first filling of transformer oil alongwith MCCB. Protection on LV side with M&P BOX confirming to technical specification
Supply of 11/0.4 KV Sub-station structure set for mounting of 3 phase distribution transformer on double pole.
Supply of Metering equipments:
(a)11KV CT PT Set(200/5 Amp.)
(c)MIP meter box.
Supply of GO double break without EB Isolator on existing bracket complete in all respect as required including hardware etc.
A) 33KV (WITH 18 X 24 KV POST INSULATOR ) 800 AMP.
B) 11KV (with 9 x 12 KV Post Insulator ) 400 Amp. - as per latest specification, design & drawing approved by the NIGAM
Supply of horn gap sets on existing brackets in all respect as required including hardware nut & bolt & washer etc.
A) 33KV ( with 12 x 24 KV Post Insulator ) 1 Set=3 NOS
B) 11KV ( with 6 x 24 KV Post Insulator ) 1 Set=3 NOS
SUPPLY OF 11 KV ROASTER SWITCH WITHOUT ON EXISTING BRACKET COMPLETE IN ALL RESPECT AS REQUIRED INCLUDING HARDWARE NUT, BOLTS & WASHER ETC.
Supply of 11KV DOUBLE POLE LINE STRUCTURE SET FOR CUT POINT COMPLETE ON EXISTING POLES IN ALL RESPECT WITH CLAMP, NUT & BOLTS AS REQURIED MADE FROM M.S.CHANNEL 100 X 50 X ISMC (9.56 KG. PER MTR.) ISA M.S.ANGLE 65 X 65 X 6 MM, M.S.ANGLE 50 X 50 X 6 MM AND M.S.FLAT 50 X 6 MM (105 KG. APPROX.) (Galvanized as per IS) Total weight = 101.38 Kg +4 Kg (Approx.)
Supply of 33 KV Sub-station type (30 KV 10 KA Station class) (1 set=3 No.) lightening arrestors on the existing brackets in all respect as required including hardware, nut , bolt & washers etc. For O&M works.
Supply of 11 KV Sub-station type (9 KV 10 KA Station class) (1 set=3 No.) lightening arrestors on the existing brackets in all respect as required including hardware, nut , bolt & washers etc. For O&M works.
Supply of PCC Pole 9.0 mtrs long.(400 Kg.)
Supply of 45KN. porcelain disc.insulators for 33 KV ( each unit consisting of 3 disc insulators & one B&S Type hardware) on brackets complete including all acessories like hardware fitting etc.
Supply of 45KN. porcelain disc.insulators for 11 KV ( each unit consisting of 2 disc insulators & one B&S Type hardware) on brackets complete including all acessories like hardware fitting etc.
Supply of 33 KV porcelain Pin insulator with Pin on pole complete including all accessories like hardware fittings etc.
Supply of 11 KV 45KN porcelin Pin insulator with Pin on pole complete including all accessories like hardware fittings etc.
Supply of PG clamps (For Dog) made of aluminum alloy as per IS:617-1994 (with latest amendments if any). All ferrous metal part intended for outdoor use except those made of stainless steel shall be protected by hot dip galvanizing in accordance with IS 2633-1986(latest amended) com plete in all respect as required for ACSR conductor,
Supply of Danger plate of size 200 X 250 mm complete in all respect
Supply of 12.8 mtr. long lattice tower made of 65 x 65 x 5 mm m.s. angle with 50 x 6 mm m.s. flat for bracing with 3 nos. of 33- kv v-cross arm of m.s. channel (100x50x6 mm)- wt. approx. 580 kg as per approved design /drawing of discom
Supply of Under ground Cable of Size 33KV 3C X 300 SQ. MM HT XLPE CABLE
Supply of PN6 HDPE pipe 200 MM as per relevant IS for highway crossing
SUPPLY OF G.I. PIPE OF 150 MM DIAMETER, B-CLASS (IS:1239 MARK)
SUPPLY OF CABLE END TERMINATION KIT/ST JOINT FOR 33 KV ALUMINUM CONDUCTOR XLPE ARMOURED HT CABLE WITH OUTDOOR AND TERMINAL END PREPARATION OF JOINT AS PER MANUFACTURES KIT GUIDANCE AND DIRECTION INCLUDING PREPARATION OF CABLE END & TESTING ETC
XLPE 3X300 SQ.MM H.S. ON OUTDOOR TYPE
XLPE 3X300 SQ.MM H.S.S.T. JOINT
Supply of Under ground Cable of Size 11KV 3C X 185 SQ. MM HT XLPE CABLE
SUPPLY OF CABLE END TERMINATION KIT/ST JOINT FOR 11 KV ALUMINUM CONDUCTOR XLPE ARMOURED HT CABLE WITH OUTDOOR AND TERMINAL END PREPARATION OF JOINT AS PER MANUFACTURES KIT GUIDANCE AND DIRECTION INCLUDING PREPARATION OF CABLE END & TESTING ETC
XLPE 3X185 SQ.MM H.S. ON OUTDOOR TYPE
XLPE 3X185 SQ.MM H.S.S.T. JOINT
Supply of 33 KV double pole line structure set (Galvanized) on 9mtrs PCC poles for cut point complete on existing poles in all respect as required made from M.S. channel 100x50 X6 mm ISMC [9.56 kg. per mtr] ISA M.S. angle 65x65x6 ,M.S. Angle 50x50x6 mm and M.S. flat 50x6 mm [excluding cost of pole] weight(130.338 kgs.) Approx
Supply of 33 KV V Cross Arm with Top Hamper with clamps (Galvanized) made of MS Angle 75x75x6mm, clamp 50X10 mm, earth clamp 50X6 mm (wt.=23.486 approx)
Supply of of GS Stay set complete with 20 mm dia., 2.4 meter long stay rod with zinc coated steel Anchor Plate of size 300x300x4 mm with square hole of size 18x18 mm at centre in ground and including gs stay wire 7/8 SWG including stay insulator stay clamp for 9 mtr pcc pole/ lattice tower.
Supply of 6 SWG GI Wire for continuous earthing of 33 KV Line hot dip (Galvanised) as per technical specification, approved drawings and scope of work.
Supply of GS Wire 8 SWG (Galvanized)
Supply of PCC Pole 9 mtrs long (200 KG)
Supply of overhead steel cored aluminum ACSR Rabbit conductor in all respect
Supply of 11KV V Cross Arm with Top Hamper with clamps made of MS Angle 65x65x6mm, clamp 50X6 mm, earth clamp 50X6 mm (Galvanized)
Supply of GI stay set (Galvanized) complete (stay rod 16 mm dia,1.8 m long,anchor plate 300X300X4 mm,12 mm dia turn buckle) including stay clamps, strain insulator, Stay wire7/10 SWG
Supply of 11KV 45 KN T&C Type porcelain disc insulator complete including all accessories like hardware fitting (as per latest specifications and drawings adopted & approved by NIGAM)
Supply of PG clamps (For Rabbit) made of aluminum alloy as per IS:617-1994 .
Supply of 1.4 Mtr Channel bracket with clamp
Supply of 11.4 mtr. long lattice tower made of 50 x 50 x 6 mm m.s. angle with 50 x 6 mm m.s. flat for bracing with 1 no. of v-cross arm wt. -449.8 kg as per approved design/drawing of discom.
Supply of assorted Fabricated items
ISA M.S. Angle 50x50x6 MM(Galvanised as per I.S)
ISA M.S. Angle 65x65x6 MM(Galvanised as per I.S)
Supply of M.S. Flat 50 X 6 mm (Galvanised as per I.S)
ISA M.S .Channel 100x50x6 MM
A) Supply of Smart Feeder Monitoring and Control System with communication charges, Cloud and Software charges having i) Class 0.2s MFM with built in or external arrangements with Serial as well as LAN Connectivity ii) Data Acquisition System with 16 DI, 4 AI, 4 DO, 2 RS485 Serial Ports and Ethernet / Wi-Fi LAN connectivity iii) 4 Hours Rechargeable battery backup iv)CMR or isolators for Digital Inputs v)HDR (Heavy Duty Relays) for ADMS vi) Cabling and Installation vii) Configuration, Commissioning, Go Live viii)Local SCADA Platform as per detail technical specifications described in bidding documents B) Transmitter for Transformer OTI/WTI integration. C) Archive Backup Server with MySQL require for reports and analysis.
Description of Work / Item(s)
Amount
Grass cutting and surface dressing including removal of unwanted/rubbish plants with roots from open ground /yard and other Nigam premises with stacking of grass/plants at desired place near the ground.
Levelling of ground up to 30 cm.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting)
Erection, testing and commissioning of 5 MVA 33/11KV Copper wound Power Transformer complete with first filling of transformer oil , OFF circuit tap changer and all fittings
Erection of outdoor 12 KV O/D VCB KIOSK complete with accessories including use of special tools & conducting all pre commissioning tests before energisation,etc. complete in all respect with erection& grouting of structure (excluding civil works).
Erection of outdoor 36 KV O/D VCB KIOSK complete with accessories including use of special tools & conducting all pre commissioning tests before energisation, filling oil etc. complete in all respect with erection& grouting of structure (excluding civil works).
Fixing of 33/11KV S/S structure (Galvanized) on existing PCC Poles including necessary nut & bolts & clamps etc. steel wt. 4087 Kg. made of MS Channel 100x50, MS Flat 50x6 and MS Sheet as per approved design and drawing.
Laying, Testing Termination of control Cable of size 2 X 2.5 SQ.MM. 1100 Volts PVC Insulated including installation of ferrules to design various cores of control cables by terminal no. of identification including utilisation of cable gland.
Laying, Testing Termination of control Cable of size 4 X 4 SQ.MM. 1100 Volts PVC Insulated including and installation of ferrules to design various cores of control cables by terminal no. of identification including utilisation of cable gland.
Laying, Testing Termination of control Cable of size 12C X 2.5 SQ.MM. 1100 Volts PVC Insulated including and installation of ferrules to design various cores of control cables by terminal no. of identification including utilisation of cable gland.
Drawing of overhead steel cord aluminium ACSR 200 sqmm [ 30+7 strand, 3+3 mm] Panther conductor, COMPLETE IN ALL RESPECT.
Fixing of PG Clamps for Panther conductor
Fixing of T-Clamps for Panther Conductor
Drawing of overhead steel cored aluminum ACSR DOG[100SqMM(6+7) /(4.72+1.57)] conductor complete in all respect as per latest specification and drawing
fixing of earth mesh (Galvanized) at sub-station as per approved map & design using MS Flat 50 x 6 mm & MS rod 20 mm dia including laying of flat at the depth 0.65 mtr & MS rod at 3 metre depth Welding & jointing at joints, structures & equipments etc. in switch yard area of 35 M x 35 M as per drawing (Galvanized)
laying of M.S. Flat 50 X 6 mm (Galvanized) for earthing
Erection of earthing rod sets for S/S made with MS Rod (Galvanized ) 20 mm dia, 3 meter length
Erection & Insllation of HD Galvanised M.S.Rod type earthing set (including nuts & bolts) made up of M.S.Rod 20 mm dia. 3 meter long alongwith earthing clamp & 8 SWG earth wire 15 meter long (for earthing of 11 KV line) driven by mechanical means into earth hole (made by augering) and connecting the MS Rod type earthing set with cross arms, top hampers, PCC pole/structure & earth wire etc.
Supply and erection of earthing electrode shall consist of G.I. Pipe 100 mm,of 3 Mtr Length. The electrode shall be buried as far as practicable 3 meters below ground level. Wherever possible, earth electrodes shall be located as near the water tap, water drain or near down take pipe. Earth electrodes shall not be installed in proximity to a metal fence. It shall be kept clear of the buildings foundations and in no case it shall be nearer than 2 meters from the outer face of the wall. The electrode shall be surrounded with layer of charcoal dust and salt mixture through out the length. The 100 mm GI pipe shall be provided with holes of 12 mm dia. drilled at 75 mm interval upto 2.5 meters length from bottom. The top of the pipe shall be provided with a G.I. threaded cap for watering the earth through a pipe. A Clamp with Pati of 12" of M.S. Flat of size 50X6 mm shall be fixed (Bolted) on the top edge of the pipe which in turn shall be connected to Neutral / Body of the Power Transformer through M.S. Flat size 50X6 mm. The G.I. cap over the GI pipe shall be housed in a masonry chamber, approximately 300 mm x 300 mm x 300 mm deep. The masonry chamber shall be provided with a RCC inspection cover resting over a RCC frame, embedded in masonry. (The material shall be inspected).
Supply and Erection of Maintenance free Gel Earthing with Pipe in pipe / Pipe in strip technology filled with anti corrosive conductive compound ( CPRI Tested ) below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineral filling compound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone ) and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. The value of Earth resistance shall be obtained 0.5 Ohm in individual earthing. G.I Pipe (IS: 1239 marks) GI pipe 3000 mm long, 80 I 40 mm, Terminal 12 mm GI Strip. Earthing as per 18:3043-1987 (The material shall be inspected).
Installation, testing and commissioning of 11 /0.4 KV 25 KVA Al wound, conventional outdoor type distribution transformers with all fittings and accessories and first filling of transformer oil alongwith MCCB.
Fixing of Sub-station transformer structure/ Base Channel (Apprx unit Wt. 284 kg.) And 11 KV Isolators, 11KV Horn gap fuse Set, 11 KV Station Type LAs structures, Transformer mounting channel, DO mounting channel, transformer belting, DC cross arm, back clamps, insulator with hardware etc all complete as per technical specifications, scope of works and approved drawings.
Installation of metering points on 11 KV outgoing feeder at 33/11 KV S/S.The installation work to be carried out as per drawing/design,under the supervision of concern Assistant Engineer
(a) Supply and installation of Mounting structure (Galvanized)
(b) The requisite steel members will be supplied by contractor including the hardware.Contractor shall joint/weld the members to form the mounting structure as per drawing.Necessary tools,welding ,machines,lifting devics etc. shall be arranged by contractor.
Civil works
(c) Supply and Erection of lattices in alignment including excavation and concreting of structure foundation including cement, sand and grit 20 mm size (crusher broken) having ratio 1:3:6 and grit 40 mm size for ratio 1:5:10 and curing for period as required (21 days). Area of concreting will be as per the drawing.
Installation of Metering equipments:
(d) 11KV CT PT Set(200/5 Amp.)
(e) Installation MIP meter boxThe meter box will be fixed firmly with sufficient strength at a place as per drawing. The test terminal block(TTB) link type shall be provided by contractor in the meter box.
(f) The required cables from CTPT set to meter box laid down in 50 mm GI pipe with suitable bends & nipples, shall be provided by contractor alongwith the consumable items such as PVC tapes, petroleum jelly etc. The cable should be PVC multi strand copper 4 core 2.5/4 Sq. mm ISI marked and firm & tight connections shall be made by suitable connector e.g. at CTPT sets by using clamps and at meter/TTB by suitable lugs etc. The CTPT sets so installed shall be earthed by means of the MS Flat (size 50x6 mm) by joining it with the nearest earthing available at the sub-station. Requisite earthing material shall be made available by the contractor.
(g) Commissioning of Metering Equipments:Installed meters inside the box and metering equipments duly mounted on the mounting structure will be powered up by connecting load in the presence of the concerned Assistant Engineer who will arrange the necessary shut down. The completion certificate shall be furnised by contractor.be filled accordingly. Since the work involves higher A.C. voltage level, the contractor shall take full care regarding safety norms, so as to avoid any accidental hazards.
fixing of GO double break without EB Isolator on existing bracket complete in all respect as required including hardware etc.
A) 33KV (with 18 x 24 KV Post Insulator ) 800 Amp.
B) 11KV (with 9 x 12 KV Post Insulator ) 400 Amp. - as per latest specification, design & drawing approved by the NIGAM
fixing of horn gap sets on existing brackets in all respect as required including hardware nut & bolt & washer etc.
A) 33KV ( with 12 x 24 KV Post Insulator ) 1 Set=3 NOS
B) 11KV ( with 6 x 24 KV Post Insulator ) 1 Set=3 NOS
FIXING OF 11 KV ROASTER SWITCH WITHOUT ON EXISTING BRACKET COMPLETE IN ALL RESPECT AS REQUIRED INCLUDING HARDWARE NUT, BOLTS & WASHER ETC.
Erection of 11KV DOUBLE POLE LINE STRUCTURE SET FOR CUT POINT COMPLETE ON EXISTING POLES IN ALL RESPECT WITH CLAMP, NUT & BOLTS AS REQURIED MADE FROM M.S.CHANNEL 100 X 50 X ISMC (9.56 KG. PER MTR.) ISA M.S.ANGLE 65 X 65 X 6 MM, M.S.ANGLE 50 X 50 X 6 MM AND M.S.FLAT 50 X 6 MM (105 KG. APPROX.) (Galvanized as per IS) Total weight = 101.38 Kg +4 Kg (Approx.)
Fixing of 33 KV Sub-station type (30 KV 10 KA Station class) (1 set=3 No.) lightening arrestors on the existing brackets in all respect as required including hardware, nut , bolt & washers etc. For O&M works.
Fixing of 11 KV Sub-station type (9 KV 10 KA Station class) (1 set=3 No.) lightening arrestors on the existing brackets in all respect as required including hardware, nut , bolt & washers etc. For O&M works.
Erection of PCC Poles in all types of soil & allignment including excavation of pit size 1.2x0.6x1.5 cum. for 9 mtrs and 1.2x0.6x1.35 cum for 8 mtrs PCC poles in ground and back filling soil consolidating each deposit layer of 0.15 mtr. by watering and ramming etc. in the length.
PCC Pole 9.0 mtrs long.(400 Kg.)
In normal soil
In Hard Soil
In ordinary rock/Hard Soil which does not require blasting
Construction of 33/11KV Transformers plate form 3.0 x 3.0x 2.0 Mtrs. Including excavation in all type of soil up to the depth of 900 mm, foundation concrete in C.C. - 1 : 5 :10 for 150 mm thickness, stone masonary in cement mortar of mix. 1:8 with top of the plate form finished with 100 mm layer of C.C. 1:2:4 alongwith 2 NOS. M.S. Rails 90 Pounds of 2.4 Mtr. length each, alongwith cement plaster - 20 mm thick of mix ratio 1:6, on all the exposed surfaces of the plate form - complete in all respect. (All required material will be supplied by the contractor).
Constn. Of 11KV/ 36 KV VCB Kiosk Plate form 3.0 x 1.5 x 1.5 Mtrs. Including excavation in all type of soil up to the depth of 900 mm, foundation concrete in C.C. - 1 : 5 :10 for 150 mm thickness, brick masonary in cement mortar of mix. 1:8 with top of the plate form finished with 100 mm layer of C.C. 1:2:4 including fixing of foundation bolts and cement plaster - 20 mm thick of mix ratio 1:6, on all the exposed surfaces of the plate form - complete in all respect. (All required material will be supplied by the contractor).
Fixing of 45KN. porcelain disc.insulators for 33 KV ( each unit consisting of 3 disc insulators & one B&S Type hardware) on brackets complete including all acessories like hardware fitting etc.
Fixing of 45KN. porcelain disc.insulators for 11 KV ( each unit consisting of 2 disc insulators & one B&S Type hardware) on brackets complete including all acessories like hardware fitting etc.
Fixing 33 KV porcelain Pin insulator with Pin on pole complete including all accessories like hardware fittings etc.
Fixing of 11 KV 45KN porcelin Pin Insulator with Pin on pole complete including all accessories like hardware fittings etc.
Fixing of PG clamps (For Dog) made of aluminum alloy as per IS:617-1994 (with latest amendments if any). All ferrous metal part intended for outdoor use except those made of stainless steel shall be protected by hot dip galvanizing in accordance with IS 2633-1986(latest amended) com plete in all respect as required for ACSR conductor,
Fixing of 33 or 11 kV Danger plate of size 200 X 250 mm complete in all respect
Erection of 12.8 mtr. long lattice tower made of 65 x 65 x 5 mm m.s. angle with 50 x 6 mm m.s. flat for bracing including excavation of pit 1.50 x 1.50 x 2.10 m in ground including civil foundation work as per desceription below. "the tower should be erected by cc grouting & muffed in cement concrete of mix ratio 1:3:6 having size of 1.20 x 1.20 x 2.10 m over base concrete of 100 mm thick in mix 1:5:10 as per is specifications. the remaining position of the pit be back filled with watering & ramming and surplus material shall be dispose- off within lead of 50 m". (All required material will be supplied by the contractor).
IN ALL TYPES OF ORDINARY SOIL - TOWER WEIGHT - 580 KG
IN ALL TYPES OF HARD SOIL - TOWER WEIGHT - 580 KG
ORDINARY ROCK (WHERE BLASTING IS NOT REQUIRED) / PACCA ROAD -TOWER WEIGHT 508 KG.
LAYING, ENERGISATION & COMMISSIONING OF UNDERGROUND CABLE FOR WORKING VOLTAGE OF 33KV ALUMINIUM CONDUCTOR (IS 7098) CABLE XLPE ARMOURED IN EXCAVATED TRENCH AS PER IE RULES AND METHODS OF IS:1255, 25 CM. THICK UNDER LAYER OF SAND, II CLASS BRICK COVERING, REFILLING OF EARTH IN THE REMAINING PORTION, MAKING NECESSARY CONNECTION INCLUDING TESTING ETC. AS REQUIRED AND /FIXING CABLE ROUTE INDICATORS AT EVERY 30 MTR OF CABLE & AT EVERY TURN (AS PER LATEST SPECIFICATIONS AND DESIGN & DRAWING APPROVED BY NIGAM). [ROAD CROSSING OF CABLE SHALL BE IN DOUBLE WALLED CORRUGATED PIPE OF APPROPRIATE DIAMETER]
Under ground Cable of Size 3X300 SQ.MM for 33 KV
In open air and loop
Through open trench (Kaccha road/soil)
Through HDD Vermier(Hard Rock)
Through manual trench less (Bogie)
Fixing of PN6 HDPE pipe 200 MM as per relevant IS for highway crossing ( Erection cost includes laying of HDPE pipe and cables)
FIXING OF G.I. PIPE OF 150 MM DIAMETER, B-CLASS (IS:1239 MARK), AT THE STARTING AND FINISHING POINT OF 33 KV UNDER GROUND CABLES AND TO LAY & CLAMP VERTICALLY WITH THE EXISTING SUPPORT, INCLUDING LABOUR CHARGES.
GI PIPE for Cable Support at Pole ( Maximum 3.3 Mtr per pole/ tower shall be used )
Fixing of CABLE END TERMINATION KIT/ST JOINT, MAKING OUTDOOR JOINT FOR 33 KV ALUMINUM CONDUCTOR XLPE ARMOURED HT CABLE WITH OUTDOOR AND TERMINAL END PREPARATION OF JOINT AS PER MANUFACTURES KIT GUIDANCE AND DIRECTION INCLUDING PREPARATION OF CABLE END & TESTING ETC
XLPE 3X300 SQ.MM H.S. ON OUTDOOR TYPE
XLPE 3X300 SQ.MM H.S.S.T. JOINT
LAYING, ENERGISATION & COMMISSIONING OF UNDERGROUND CABLE FOR WORKING VOLTAGE OF 11KV ALUMINIUM CONDUCTOR (IS 7098) CABLE XLPE ARMOURED IN EXCAVATED TRENCH AS PER IE RULES AND METHODS OF IS:1255, 25 CM. THICK UNDER LAYER OF SAND, II CLASS BRICK COVERING, REFILLING OF EARTH IN THE REMAINING PORTION, MAKING NECESSARY CONNECTION INCLUDING TESTING ETC. AS REQUIRED AND /FIXING CABLE ROUTE INDICATORS AT EVERY 30 MTR OF CABLE & AT EVERY TURN (AS PER LATEST SPECIFICATIONS AND DESIGN & DRAWING APPROVED BY NIGAM). [ROAD CROSSING OF CABLE SHALL BE IN DOUBLE WALLED CORRUGATED PIPE OF APPROPRIATE DIAMETER]
Under ground Cable of Size 3X185 SQ.MM for 11 KV
In open air and loop
Through open trench (Kaccha road/soil)
Through HDD Vermier(Hard Rock)
Through manual trench less (Bogie)
Fixing of CABLE END TERMINATION KIT/ST JOINT, MAKING OUTDOOR JOINT FOR 11 KV ALUMINUM CONDUCTOR XLPE ARMOURED HT CABLE WITH OUTDOOR AND TERMINAL END PREPARATION OF JOINT AS PER MANUFACTURES KIT GUIDANCE AND DIRECTION INCLUDING PREPARATION OF CABLE END & TESTING ETC
XLPE 3X185 SQ.MM H.S. ON OUTDOOR TYPE
XLPE 3X185 SQ.MM H.S.S.T. JOINT
Conducting route survey as per approved route map and pegging of route with section point/double pole location
Trimming of tree branches and preparing route appraoches for the proposed line
Fixing of 33 KV double pole line structure set on 9mtrs PCC poles for cut point complete on existing poles in all respect as required made from M.S. channel 100x50 X6 mm ISMC [9.56 kg. per mtr] ISA M.S. angle 65x65x6 ,M.S. Angle 50x50x6 mm and M.S. flat 50x6 mm [excluding cost of pole] weight(130.338 kgs.) Approx
Fixing of 33 KV Cross Arm with Top Hamper with clamps made of MS Angle 75x75x6mm, clamp 50X10 mm, earth clamp 50X6 mm (wt.=23.486 approx)
Erection of of GS Stay set complete with 20 mm dia., 2.4 meter long stay rod with zinc coated steel Anchor Plate of size 300x300x4 mm with square hole of size 18x18 mm at centre in ground and gs stay wire 7/8 swg tightened through 33 kv stay insulator including clamps including excavation of pit size 0.75x0.5x1.6 CUM in ground for all type of soil refilling, grouted and muffed in cement concrete. (The cement, concerete & sand will be supplied by the contractor)
SOIL (EVERY TYPE)
HARD SOIL / PACCA ROAD
HARD ROCK/CC ROAD
Erection of 6 SWG GI Wire for continuous earthing of 33 KV Line hot dip (Galvanised) as per technical specification, approved drawings and scope of work.
Drawing and laying of Mesh using GS Wire 8 SWG (Galvanized) on the guarding for crossing as per standard or required as per location including binding as per drawing for road / P&T/ Power Line crossing.
Erection of PCC Poles in allignment including excavation of pit size 1.2x0.6x1.5 cum. for 9 mtrs 200 Kg in ground and back filling soil consolidating each deposit layer of 0.15 mtr. by watering and ramming etc. in the length.
PCC Pole 9 mtrs long (200 KG)
In normal soil
In Hard soil
In ordinary rock/Hard Soil which does not require blasting
Drawing of overhead steel cored aluminum ACSR Rabbit conductor in all respect
Fixing of 11KV V Cross Arm with Top Hamper with clamps made of MS Angle 65x65x6mm, clamp 50X6 mm, earth clamp 50X6 mm (Galvanized)
Fixing of GI stay set (Galvanized) complete (stay rod 16 mm dia,1.8 m long,anchor plate 300X300X4 mm,12 mm dia turn buckle) including stay clamps, strain insulator, Stay wire7/10 SWG
In normal soil
In Hard Soil
ordinary rock / PACCA road
Fixing of 11KV T&C Type porcelain disc insulator complete including all accessories like hardware fitting (as per latest specifications and drawings adopted & approved by NIGAM)
Fixing of PG clamps (For Rabbit) made of aluminum alloy as per IS:617-1994 .
Erection of 8 SWG (4mm dia) GI Wire for continuous earthing of 11 KV Line hot dip
Fixing of 1.4 Mtr Channel bracket with clamp
Erection of 11.4 mtr. long lattice tower made of 50 x 50 x 6 mm m.s. angle with 50 x 6 mm m.s. flat for bracing including excavation of pit 1.50 x 1.50 x 2.10 m in ground civil foundation work as per description below. "the tower should be erected by cc grouting & muffed in cement concrete of mix ratio 1:3:6 having size of 1.20 x 1.20 x 2.10 m over base concrete of 100 mm thick in mix 1:5:10 as per is specifications. the remaining position of the pit be back filled with watering & ramming and surplus material shall be dispose- off within lead of 50 m. (Cement, concrete and sand will be supplied by contractor)
IN ALL TYPES OF SOIL - TOWER WEIGHT - 449.85 KG
IN ALL TYPES OF HARD SOIL - TOWER WEIGHT - 449.85 KG
ORDINARY ROCK (WHERE BLASTING IS NOT REQUIRED) / PACCA ROAD -TOWER WEIGHT 449.85 KG.
ORDINARY ROCK (WHERE BLASTING/DRILLING IS REQUIRED) / PACCA ROAD -TOWER WEIGHT 449.85 KG.
fixing of Fabricated items
ISA M.S. Angle 50x50x6 MM(Galvanised as per I.S)
ISA M.S. Angle 65x65x6 MM(Galvanised as per I.S)
ISA M.S. Flat 50x6 MM(Galvanised as per I.S)
ISA M.S .Channel 100x50x6 MM
A) Installation, Testing, Commissioning & Go Live of Smart Feeder Monitoring and Control System site services for various breakers including Power Transformers, 33 kV Incomes, 11 kV Incomers, Station Transformers, Distribution Feeders and Capacitor bank each equipment having i) Class 0.2s MFM with built in or external arrangements with Serial as well as LAN Connectivity ii) Data Acquisition System with 16 DI, 4 AI, 4 DO, 2 RS485 Ports Serial and Ethernet / Wi-Fi LAN connectivity iii) 4 Hours Rechargeable battery backup iv)CMR or isolators for Digital Inputs v)HDR (Heavy Duty Relays) for ADMS vi) Cabling and Installation vii) Configuration, Commissioning, Go Live viii)Local SCADA Platform as per detail technical specifications described in 10.4, 10.5, 10.6 B) Transmitter for Transformer OTI/WTI integration C) Archive Backup Server with MySQL require for reports and analysis.
Description of Work / Item(s)
Amount
CIVIL WORK FOR CONSTRUCTION OF CONTROL ROOM AND ASSOCIATED WORK FOR 20 NO. OF 33/11 KV SUB-STATION
(1.8) Earth work in excavation by mechanical means (Hydraulic Excavator)/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sum on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter All kinds of soil.
(3.1.6) Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level.1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size).
(B) M15 grade Nominal Mix 1: 2: 4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size).
(6.1.6) Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in:Cement Mortar 1:6 ( 1-Cement : 6-Sand).
Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement. M20 grade Nominal Mix / Design Mix (4.1)
Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc. (4.9)
(6.18.1) Supplying and fixing stone lintels/bed plates of approved quarry rough dressed in cement mortar 1:4 :upto 15 cm thick.
(4.3) Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement for Beams, suspended floors, roofs, griders having slopes up to 15º, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases etc. M20 grade Nominal Mix / Design Mix
(4.10.2) Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates, anchor blocks, sills, chhajjas, lintel, beam, plinth beam etc.
(4.13.2) Providing and fabricating reinforcement for R.C.C. work includingstraightening, cutting, bending, placing in position and binding(including cost of binding wire) all complete up to floor five level.Hot rolled deformed bars (IS : 1139).
(5.8.3) Half brick masonry in Superstructure, using bricks of designation 75 in CM 1:6 upto third storey.
(5.2.2) Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level upto floor V level in all shapes and sizes in : Cement mortar 1 : 6 (1 cement : 6 coarse sand)
(10.17.1) Grading roof for water proofing treatment with water proffing compound Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
(3.8) Providing & fixing precast cement concrete coping 1 : 2 : 4 mix 50mm thick complete as per specification .
10.22 Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10mm and down gauge) including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :
(9.19.3) Providing and fixing steel glazed doors windows and ventilator shutters of standard rolled steel section joints mitred and welded with steel lugs 13x3mm, 10cm. long embedded in cement concrete block 15x10x10cm. of 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) or with wooden plugs and screws or rawl plugs and screws with fixing clips or with bolts and nuts as required including providing and fixing of plain glass panes 4mm thick with cooper glazing clips and special metal sash putty of approved make or metal beading with screws complete including priming coat of approval steel primer, excluding the cost of metal beading and other fitting except necessary hinges of pivots steel handles peg stay etc. as required :Windows side hung /Ventilators top or centre hung (openable) .
(9.26) Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance.
(9.27) Providing and fixing Square bars or other flat welded to window, ventilatiors etc.
(11.26) Random rubble dry stone Kharanja under floor.
(9.5) Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded with 15x3 mm lugs 10cm long embedded in cement concrete blocks 15x10x10 cm of 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) or with wooden plugs and screws or rawl plugs and screws or with fixing clips or with bolts and nuts as require including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer.
(6.17.3) Supplying and fixing in walls machine cut and polished stone shelves, tands and in CM 1:3 with machine cut edges : Kota stone minimum 30mm thick.
(8.13.2.1) Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure 'A' :comercial veneer both side 30 mm thick .
(9.17.1+9.17.2) Providing and fixing M.S. sheet double leaf door shutter in angle iron frame 35x35x5mm suitabilly diagonally braced with 25x3mm flat iron above and below lock rail of size 50x5mm beading extra including all fittings, as per direction of Engg. incharge but excluding cost of chowkhats: including two coats of anit-corrosive red oxide primer paint M.S. Shhet 20 S.W.G.
Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finish:(A) 20mm thick. (12.3.2)
(B) 12 mm thick (12.3.3)
6 mm thick cement plaster to ceiling of mix 1:3 (1 cement :3 fine sand). (12.5)
(7.14) Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades glazed tiles confirming to IS : 13753 & IS :15622 of size 200mm x 300mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar).
(7.15) Providing and fixing 1st quality MAT finished ceremic tile size 300x300mm confirming to IS : 13755 and IS : 15622 colour such as white, grey, ivory, fume red brown, light green, light blue and other light shades in floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (including the cost of cement mortar bed 1:4).
(11.18.2) Kota stone slab flooring 25 mm thick over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand)For area of each slab from 2001 to 5000 Sq.Cm
(11.19.1) Kota stone slabs 25 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete For area of each slab upto 2001 Sqcm
(9.39) Providing and fixing of double leaf steel shutter for cupboard the frame is made of pressed steel ISI section 80x25 mm x 1.25 mm thick with 1.00 mm MS sheet to spot welded includig holdfast of 15 x 3 mm, MS oxidized fittings such as butt hinges, sliding doors bolts, handles tower bolts and twin peg etc complete including applying priming coat of approved steel primer of red oxide zinc chromate and spray painting in approved shade with deco paint of approved quality complete as per direciton of Engineer in charge.
12.45.1 Applying priming coat : With ready mix pink or gray primer of approved brand and manufacture on wood work hard and soft wood.
(12.46.1) Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two or more coats on new work
(12.22.1) Providing and applying white cement based putty over plastered surface to prepare the surface even and smooth complete New Plastered Surface (three or more coats)
(12.37.1) Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding: New work (two or more coats) over and including scrapping and priming coat with cement primer.
(12.42) Finishing walls with Acrylic Smooth exterior paint of required shade including all scaffolding. New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including base coat of water proofing cement paint applied @ 2.20 kg/ 10 sqm ).
(12.20) Making of drip course (Tapka) in cement sand mortar 1:6 width upto 40 mm and 10 mm thick as per approved design
(12.19) Making grooves as per design in plaster 10mm to 20mm wide.
(11.3.1) Cement concrete flooring 1 : 2 : 4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, making of lines or groove etc complete but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm thick nominal size aggregate.
(R/4.9) Providing, laying spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the material with water at OMC in mechanical mixer (pug mill), carriage of mixed material by tipper to site, laying in uniform layers in sub base/base course on a well prepared sub base and compacting with smooth wheel roller of 80 to 100 KN weight to achive the desired density including lighting, barricading and maintenance of diversion, etc as per table 400.11 & 400.12 and MoRD specification clause 406. By mechanical means with 1 km lead.
R/6.7 (iii) (a) P & l of Interlocking M-30 grade concrete Block pavements having thickness 80 mm as per drawings & MoRD Specification Clause 1504 with M-30 Grade 0.30 Mtr X 0.30 Mtr X 0.15 Mtr Edge Blocks. Category 'A' Dentated units to key into each other on all four faces zigzag shape as per IRC: SP:63-2004.
(1.2.2) P & F Indian type white glazed vitreous china 1st quality W.C. orissa pan (IS :2556 Mark) with 100 mm vitreous china P or S trap including cutting and making good the wall and floor:Size 580x440mm.
(1.14.1) P & F lst quality WVC Urinal (IS:2556 mark) with 25mm dia G.I. waste pipe, dome waste couplings, concealed iron brackets or screws etc complete.Flat Back (small) size 456x355x265mm.
1.36.4 P & F WVC Wash basin (Ist quality IS:2556 Mark) of approved make with C.I. brackets duly painted 1 No. 15 mm C.P. Pillar cock (IS:8934 Mark) & 32 mm C.P. brass waste coupling of approved make, P.V.C Waste pipe with PVC nut 32 mm complete including cutting & making good the wall : Size 580 mm x 450 mm
P & F Towel Rail or Ring of approved quality/make (a) C.P. brass towel rail with brackets 600 x 20mm. (1.47.4):
2.26.2/S-2 P & F PVC Storage Tank ISI Marked (IS : 12701) indicating the BIS license No), of approved make with cover, 25mm dia 1M long G.I. over-flow pipe & 25 Cm. long wash out pipe with plug & socket, including making connection etc., complete of approved design: 500 ltr capacity
P & F looking Mirrors with P.V.C. frame of approved (Atul, Modi Guard, Saint Gobin or equivalent).Size 500 x 400 mm. (1.45.1)
P & F G.I. pipes (Internal Work) with G.I. Fittings excluding union (IS:1239 Mark) & MS clamps including cutting and making good the walls and floors: (Exposed on wall) (a)15 mm dia nominal bore'B' Class (2.1.1)
(B)25 mm dia nominal bore'B' Class (2.1.3)
2.2.1, 2.2.3 P & F G.I. Pipes (External Work) with G.I. fittings excluding union (IS : 1239 Mark) including trenching & refilling earth etc. (a)15mm dia nominal bore B- Class
(b)25mm dia nominal bore B- Class
2.3.1/S-1 Making connection of G.I. distribution branch with G.I. main including all fittings.upto 25mm dia.
2.7.3 /S-2 P & F Bib cock (IS: 8931 Mark), Superior quality of approved make: (A) C.P. brass bib cock 15mm nominal bore.
(2.11.1) P&F Ball Cock (IS:1703 Mark) with Rod & P.V.C. Ball complete:Brass wt. not less than 300 grm, 15mm.
P & F Full-way Valve (IS:778 Mark) or wheel valve of approved make : (a)Gun-metal 15mm nominal bore.(2.15.1)
(B)Gun-metal 25mm nominal bore.(2.15.3)
(2.14.9) P & F Flush Cock/Flush Valve(IS : 9758 Mark) for WC ofapproved quality make : Brass/Gun metal Half-turn wt. 1 Kg. of approved quality/make, 25mm nominal bore.
(2.12.1) P & F Inlet Connection (Angle Valves) Superior quality, of approved make, for Wash basin, Gyser etc.C.P. Inlet connection 15mm.Brass (IS : 8931 marked)
P & F 15 mm. Dia Connection Pipe of approved quality/make : (a) PVC pipe with C.P. Brass nuts upto length, 300mm(2.13.1)
(3.19.1) Construction of manhole in all type of soil inner size 90 X 60 Cm. 300 mm thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5:10 in foundation, 20 mm thick inside plaster in CM 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring, making channels, 80mm thick stone slab covering with 40mm thick M-15 grade C.C. flooring, Cement cover with frame of 450mm dia, earthwork etc. complete as per design including disposal of surplus earth within 50 mtr. lead. Depth up to 0.5 M
(3.22.3) Construction of soakage well in all type of soil with 300 mm thick dry masonry, top and bottom 300 mm course in CM 1:6, 80mm thick stone slab, jointing of slab in CM 1 : 3, Ralthal, Kharanja, 40 mm thick M-15 grade C.C flooring , earthwork complete as per approved drawing including disposal of earth within a lead of 50 mtr.: Size 240 Cm. dia outside & 240 Cm. depth.
(3.27.1) Construction of septic Tank in all types of soil with 40 Cm .thick masonry in CM 1:6, 15 Cm thick C.C bed of 1:5:10, M-15 grade C.C floor & RCC slab covering with M15 grade c.c. floor, 50 mm thick stone slab partition walls, 20 mm thick plaster in CM 1:6 finished with neat floating cement, 4 Nos stone foot rests of approved design ,two No. 450 mm dia each Ferro cement cover with frame, earth work etc. complete as per approved drawing including disposal of surplus earth within a lead of 50 mtr:- Size 200x100x130 cm.(for 10 users) with 115 mm thick RCC (M-20) slab with Tor steel reinforcement 8mm ϕ @15 cm c/c bothways including shuttering complete in all respect.
(3.3.1) Providing & Laying C.C. 1:5:10 (Stone aggregate 40mm nominal size) upto haunches of S.W. pipes including 150 mm thick bed concrete as per Rajasthan PWD specifications (Width W= Dia of pipe in Cm+ 30Cm.) concrete width to be reduced from width W at center of pipe to `0` at top of pipe. 100mm dia S.W. pipe
(3.16.2 , 3.16.3) P & F rigid PVC Pipe (IS : 4985 mark) class II / (4 Kg. / Cm2 .) approved quality / make including joining the pipe with solvent cement rubber ring and lubricant. (a)75 mm dia
(b)110 mm dia
P & F rigid pvc pipe fittings (IS : 4985 mark) of approved quality / make including joining the pipe with solvent cement rubber ring and lubricant :110 mm dia.(A) Bend 45˚ (3.17.8.ii)
(B) Bend 87.5˚ .(3.17.9.ii)
(C) Vent Cowel (3.17.12.ii)
(D) Gully trap (3.17.27)
Supply & Fixing G.I. Union ISI marked in G.I pipes line as required complete in all respect of size . (A)15 mm dia nominal bore 'B' Class. (2.32.1)
(B)25 mm dia nominal bore 'B' Class. (2.32.3)
P & F Grating of approved quality/ make Stainless steel sheet size 125 mm dia. (1.48.1)
(1.38.9.1) 1.0 mm thick stainless steel AISI -304 & IS 13983-1994 kitchen sink of approved make as per Engineer-in-charge with large waste coupling. Overall size 18 x 16 x 6 (inches) Bowl size 16x14x6 (inches)
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. (A) Short point (up to 3 mtr.) (1.1.1)
(B) Medium point (up to 6 mtr.) (1.1.2)
© Long point (up to 10 mtr.) (1.1.3)
Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR On board (1.3.1)
Providing and fixing of power plug point with non modular accessories as per PWD specification for electrical Works with Galvanized box of 1.2 mm thick with earth terminal with suitable size phenolic laminated sheet (IS : 2036 - 1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin 16 amp. socket outlet making connection , testing , etc. as required. . For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure 'A' attached with this BSR (7.36)
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR (A) 2 x 2.5 sq. mm. + 1x1.5sqmm (4.1.7)
(B) 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (4.1.14)
Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 8 SWG G.I. ( Hot Dipped ) Wire. (14.6.8)
14.2 Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Providing & Fixing of energy efficient direct fit (Retrofit) Polycarbonate/ Glass housing SMD Mid Power LED tube rod (with integral driver & alumn. heat sink ), on existing fixture. system lumen efficacy ≥ 100 lm/Watt output, internal surge protection of 2.5 KV ,THD < 20% ,p.f.≥0.95,CRI >80 , life time of minimum 35000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80)certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 1200mm , Min. Lumens output 2000 lm LED Tube rod with Polycarbonate Housing. (17.2.2)
Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 20 mm Dia. (18.18.1)
P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. (5.9)
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Single pole MCB (With B/C curve tripping Characteristics). 6 A to 32 A rating. (6.1.1.2)
Providing & Fixing of 240/415 V isolator ISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 35sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Four pole Isolator. 63 A rating. (6.2.3.2)
6.10.12, 6.10.1.3/ Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 8way
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 6.0 Sq. mm 2 core. (11.2.2.1)
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . (A)LED Street Light fixture with Minimum lumen output 11225 lm. (18.12.6)
Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR (19.1.1) 8.0 Mtr long PCC pole of 200 Kg Working Load
7.20 Providing & Fixing of IS 11037:1984 marked non modular socket size flush type 120 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material including making connection testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .(7.20)
Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) (15.7.1)
2.1.2 Const. of Tube- well from ground level & upto 100 Meter depth and above to accommodate housing & assembly pipe of following sizes in all type of alluviium strata by percussion / rotary drilling method & with gravel as per as per IS:4097-1967 & packing as per IS : 2800 (Part - I & II) 1979 as amended upto date (the work includes the cost of gravel & its primary packing & packing during development, lowering of housing & strainer assembly pipes, with supply & wrapping of coir-rope, wherever necessary, for arresting fine sand particles. The work will notinclude cost of housing pipe & strainer pipe assembly & development work, but work would be completed after obtaining sand free water). 200 mm dia. Nominal bore.
2.3.1+2.3.4 Const. of Tube- well upto 100 Meter depth and above in all type of Rocks by DTH system and over burden, to accommodate casing pipe of following sizes in all types of soils & over burden including lowering of casing pipes, but excluding cost of casing pipes as per IS : 2800 (Part - I & II) 1979 specifications. The work would be completed after obtaining sand free water.The tube-well should have a throughout bore as per nominal dia of casing pipe.150 mm dia. Nominal bore.
Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B" class), Steel tube as per IS:1239 or amended up to date and zinc coating as per IS 4736, threaded and double flanged (welded) on both ends and two number 25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect. 32 mm dia. (P 2.24.1)
Supply & Fixing M S clamp set of 50x6 mm flat from iron with nuts and bolts etc for holding the riser pipe assembly of submersible pump set. (P 2.22)
(4.8.4) S & F tube well cover of M.S.sheet (6mm thick) with nuts and boltscomplete for casing size:200mm dia Nominal bore
P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 10.0 Sq.mm 3 core flat / Round. (E 4.7.5)
Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to date of following sizes. 200 mm dia NB (Thickness of pipe 5.4mm & mass of tube 28.46 Kg/m) (P 2.11.2)
Labour charges for making slots on blank pipes made of ERW MS black pipe ISI marked of following sizes, the slotting should be as per IS:8110-1985. 200 mm dia nominal bore of 5.4mm thickness. (P 2.12.3)
Supply & Installation of 3 phase ISI marked submersible motor pump set of three star or better rating of BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. Up to 5.5 KW (7.5 HP) & head above 120 mtr. (2.15.2)
Providing and fixing steel gate, grating and grills made of angles , tees, square bars, flats, or black pipe with holdfast and fitting complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide. (9.8.1)
Structural steel work riveted or bolted in built up sections, trusses and frammed work, including cutting, hosting (height upto 10m), fixing in position and applying a priming coat of approved steel primer all complete. (9.2)
Add extra for Square or Rectangular pillars in S/S brick work upto V storey. Upto 45 cm length & all sides are free. (5.3.1)
Add extra if Square, Rectangular hollow tubelar section are or grill made by flats only. (9.8.2)
Add extra for RR stone masonry with hard stone in Wall upto 30cm & less thickness. (6.3.4)
Supply & laying of clean, clear sharp river sand of size 1 to 2mm coarse, without deduction of voids. (4.29)
9.38.3 Providing and fixing welded mesh/expanded metal mesh in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. complete (excluding frame work) of size. Welded mesh 25 mmx 25 mm x 2.1 mm
E/W in filling of excavated earth except black cotton soil with watering & compaction of spreaded earth in 15-30cm layers levelled & neatly dressed as per requirement of site & direction of E/I, work includes cost of earth with taxes, loading, unloading, transportation, labour, water & T&P etc. complete with all lead & lift.
P &F sign board as per approved drawing and specification made of M.S sheet of 1.6mm thick of size 1200X900 mm stiffened by flat 20X3mm on both sides all arround the plate & duly framed with 32mm dia medium M.S black pipe fixed on frame of 50mm OD medium pipe ( Vertical post 3600mm, 3000mm above ground level with angle iron hold fast 35X35X5mm with Horizantal member 1500mm to be jointed with flat 40X6mm and post embeded in cement concrete blook M-15 grade of 450X450X750mm size below ground level as directed by E/I. all MS will be stove enameled and both side lettering, figuring and border on sheet with ready mix synthetic enamelled paint of superior quality in required shade and colour etc. complete in all respect all support framed post & steel tubes will be painted with primer and two coats of enamel paint as per specification & Direction of E/I. Over all size 1500 X 1200mm.
Supply and spreading of crusher dust free of organic matter including stacking spreading and laying in yard as per standard specification including all lead and lift, Transportation, labour, loading unloading, T&P required for spreading of crusher dust work as per direction of Engineer in Charge including dressing ground upto 15cm depth.
S, S & S of graded crusher brocken hard stone aggregate free from organic matter including stacking & spreading in yard / trenches as per the standard specification of size 40mm to 63mm incl. all lead & lift, transportation, labour, loading, unloading & require for graveling work as per direction if Engineer in charge incl. dressing & levelling.
P & F four No. 10ltr. Capacity steel bucket & filling of bucket by sand & appropriate size of steel stand for fixing the steel bucket. The stand made by 65x65x 6mm M.S. angle with two or more coats of enamel paint including primer coat of all buckets & stand including all material labour T&P and other required accessaries. The size & shape of bucket & stand (Length of 2No vertical posts 1.50 mtr. length each, 2 No. horizontal member length 0.90 mtr each & hold fast 2 No. 0.15 mtr each including E/W & duly grouted in CC 1:2:4 (2x30x30x45 cm ) as per direction of Engineer in charge including painting with primer & postman red colour paint and letter writting "FIRE".
Supply of steel office table having top of 19mm thick laminated particle board of size 5'x2' having frame size 25x25mm square hollow pipe MS Pipe thickness 1.6mm frame size 4'10"x 1'10" x 2'6" (750mm hieght) duly welded, grinding and fine finished, fitted with two no MS box each having three drawers, openable opposite side with locking arangement and handle as per fitting arrangement dully coated with steel primer (two or more coats) and painted with powder coated paint
Supply of chair having frame of 19mm round pipe of (16 gauge) and having seat and back of 18 gauge perforated steel sheet of 16"x16" and 16"x8" (semicircular) respectively and dully painting with powder coating paint . (Size of chair LxBxH= 20"x18"x33")
Description of Work / Item(s)
Amount
A) Operation & Maintenance (O&M) of 33/11 kV Grid Sub-station (GSS) and Associated 33 kV Line for period of ten (10) years. This covers periodic maintenance, replacement of defective equipment / material including restoration of power supply in case of breakdown of 33kV line and substation. Restoration of power supply in line with SOP issued by RERC from time to time.
B) 10 Years CMC, Cloud hosting, and Communication Charges OF SFMS system for various substation incoming point of 33kV feeders and incoming as well as outgoing point of 11kV feeders at all 33/11 kV Sub Stations envisaged under this tender. Total CMC charges for 10 years should not be less than 25% of Total cost of Supply as well as installation & Commissioning charges (BOQ1 -item 66 + BOQ2-item 115)
Description of Work / Item(s)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid