| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.5 LAccepted-AOC 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | ₹34.5 L Quoted ₹35.8 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹43.1 LRejected-AOC | ₹43.1 L | L2 | Rejected-AOC other than lowest |
| 3 | L3₹57.6 LRejected-AOC SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON W MUMBAI 400 104 | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹57.6 L | L3 | Rejected-AOC other than lowest |
| Sl No | Description | Qty | Unit | NOEL ENGINEERS L2 | ASHOK ENTERPRISES L1 | Shree Ayyappa Engineering L3 |
|---|---|---|---|---|---|---|
| 1.00 | Taking up old unserviceable XLPE insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor including old concrete cable cover from trenches/walls/ceilling/poles etc any size all as specified and directed. | 1,943 | RM | 7 ₹13,601 | 2 ₹3,886 | 4 ₹7,772 |
| 2.00 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of UG Electric cable / staying of steel tubular pole etc. and getting out in soft and loose soilcomplete all as specified and as directed . | 315 | Cum | 127 ₹40,005 | 160 ₹50,400 | 300 ₹94,500 |
| 3.00 | Removing the excavated material/ soil not exc 50m complete all as specified and directed . | 80 | Cum | 80 ₹6,400 | 160 ₹12,800 | 50 ₹4,000 |
| 4.00 | Returning & filling in, including spreading, levelling, watering & well ramming in layers not exc 25 cm as in soil complete all as specified & directed . | 235 | Cum | 20 ₹4,700 | 120 ₹28,200 | 50 ₹11,750 |
| 5.00 | Material and labour for dry clean sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning complete all as specified in SSR Part-I and as directed.
(Note :- Only compacted thickness of sand will be measured and paid.) | 22.5 | Cum | 475 ₹10,687.50 | 1,000 ₹22,500 | 1,000 ₹22,500 |
| 6.00 | Supplying and laying un-reinforced precast concrete cable cover, class LV Type I, flat, size 250 mm x 150 mm x 40 mm. laid in trenches complete all as specified and directed. | 3,558 | Each | 26 ₹92,508 | 25 ₹88,950 | 27 ₹96,066 |
| 7.00 | Supply and fixing, laying PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 4 core 16 Sqmm laid in trenches/ through pipe/ ducts or fixed on wall etc ,complete all as specified and as directed. | 850 | RM | 162 ₹1.4 L | 120 ₹1.0 L | 200 ₹1.7 L |
| 8.00 | S&F laying PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 4.0 core 25 Sqmm laid in trenches/ through pipe/ ducts or fixed on wall etc complete all as specified and directed . | 565 | RM | 236 ₹1.3 L | 160 ₹90,400 | 250 ₹1.4 L |
| 9.00 | S&F laying PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 35 Sqmm laid in trenches/ through pipe/ ducts or fixed on wall etc complete all as specified and directed. | 528 | RM | 261 ₹1.4 L | 180 ₹95,040 | 280 ₹1.5 L |
| 10.00 | Material and Labour required for Taking up loose XLPE cable from wall & Refixing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of sizes upto 50 Sqmm 3.5 Core complete fixed on wall with suitable size of clamps with anchor fastner or saddles & screw all as specified and directed. | 372 | RM | 316 ₹1.2 L | 20 ₹7,440 | 50 ₹18,600 |
Updated dates
Tender Value
₹50.0 L
EMD Value
₹99,980
Closing Date
9 Dec 2025, 6:00 pmClosed
GE (NW) NOFRA
Dr Homi Bhabha Road Navy Nagar Colaba Mumbai
REPAIR REPLACEMENT OF STREET LIGHT GARDEN LIGHT POLE LIGHT HIGH MAST LIGHT FITTINGS CABLE JUNCTION BOXES AT NOFRA WNC(O) MESS IMSC UNDER GE (NW) NOFRA
2025_MES_739565_1
8454/E8 GE (NW) NOFRA
Open Tender
Electrical and Maintenance Works
330 days
Mumbai
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (NW) NOFRA
₹99,980
Yes
31 Mar 2026
13 Nov 2025
11 Dec 2025
13 Nov 2025
9 Dec 2025
27 Nov 2025
13 Nov 2025 - 20 Nov 2025
Amount
Taking up old unserviceable XLPE insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor including old concrete cable cover from trenches/walls/ceilling/poles etc any size all as specified and directed.
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of UG Electric cable / staying of steel tubular pole etc. and getting out in soft and loose soilcomplete all as specified and as directed .
Removing the excavated material/ soil not exc 50m complete all as specified and directed .
Returning & filling in, including spreading, levelling, watering & well ramming in layers not exc 25 cm as in soil complete all as specified & directed .
Material and labour for dry clean sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning complete all as specified in SSR Part-I and as directed. (Note :- Only compacted thickness of sand will be measured and paid.)
Supplying and laying un-reinforced precast concrete cable cover, class LV Type I, flat, size 250 mm x 150 mm x 40 mm. laid in trenches complete all as specified and directed.
Supply and fixing, laying PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 4 core 16 Sqmm laid in trenches/ through pipe/ ducts or fixed on wall etc ,complete all as specified and as directed.
S&F laying PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 4.0 core 25 Sqmm laid in trenches/ through pipe/ ducts or fixed on wall etc complete all as specified and directed .
S&F laying PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 35 Sqmm laid in trenches/ through pipe/ ducts or fixed on wall etc complete all as specified and directed.
Material and Labour required for Taking up loose XLPE cable from wall & Refixing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of sizes upto 50 Sqmm 3.5 Core complete fixed on wall with suitable size of clamps with anchor fastner or saddles & screw all as specified and directed.
Supply and Fix in repair MCB TP/FP 63 Amps adjustable type with Breaking capacity 16 KA. (B series) .
Supply and Fix in repair MCB of size 40 Amps ,240 Volts B series all as specified and directed by engr-in-Charge.
Supply and Fix in repair MCBs of Size 6 to 32 Amps ,240 Volts all as specified and directed by engr-in-Charge.
Supply and Fix in repair MCCB 3P/4P 63 Amps adjustable type Breaking capacity 16 KA. (B series) .
Supply and fix in repair MCCB 3/4 Pole , 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA all as specified and directed by engineer in charge
Supply and fix in repair MCCB 3/4 Pole , 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA all as specified and directed by engineer in charge
Supply and fix in repair MCCB 3/4 Pole , 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA all as specified and directed by engineer in charge
Supply and fix in repair hydroblast Marine 5050 LED Deck Lightining Beveled Downward pitch technology, Black casing,warm white colour LED compatible with Hydoblast controllers with necessary arrangement for connecting the lights including terminal/junction boxes, ceiling roses for connection of lights complete all as specified and directed by Engineer-in-charge.
Supply and Fix in repair LED Post top Lantern with die cast aluminium spigot,spun AL powder coated top cover,AL clear acrylic and with holder and IP 65 protection with all accseeories including PCC foundation tapper plug bolts,Nuts,Screwed, complete all as specified and directed by engr-in-charge.
Supply and fixing in repairs LED light 9/10 Watt square shaped integral decorative LED bollard IP 65/IK10 With all acessories including PCC foundation tapper plug bolts, nuts, screwed complete all as specified and directed by Engineer-in-Charge and taking down old light complete.
Supply and Fixing in repair LED Bollard 'MONACO TYPE' with Decorative fixtures Die cast aluminium Housing Glass Diffuser,Black Colour all acessories including PCC foundation tapper plug bolts, nuts, Decorative Black Colour Pole for fixing the light(approx 1 Mtr), screwed complete all as specified and directed by Engineer-in-Charge and taking down old light complete.
Supply and fixing in repairs LED Post Top HERITAGE TYPE Ideal to Light up Parks/Streets, Gardens light 20 Watt s integral decorative IP 65/IK10 With all acessories including PCC foundation tapper plug bolts, nuts, screwed complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED Post Top TERRIAN TYPE Ideal to Light up Gates, Gardens light 40 Watt s integral decorative IP 65/IK10 With all acessories including PCC foundation tapper plug bolts, nuts, screwed complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED Post Top GLOBE TYPE Ideal to Light up Gates, Gardens light 25 Watt s integral decorative IP 65/IK10 With all acessories including PCC foundation tapper plug bolts, nuts, screwed complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED light 9/10 Watt City Cube LED bollard P with IP 65/IK10 With CCT Ranges from 3000K to 4000K and all acessories including PCC foundation tapper plug bolts, nuts, screwed complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED light 9/10 Watt City Cube LED bollard D with IP 65/IK10 With CCT Ranges from 3000K to 4000K and all acessories including PCC foundation tapper plug bolts, nuts, screwed complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED post top integral pole mounted decorative LED post top 50Watt with IP66/IK10 protection including fittings all accessories complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED Spike Light 8W with IP66/IK10 protection including fittings all accessories complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs LED bollard TWISTER TYPE light up Gardens light pathways 25 Watt s integral decorative IP 65/IK10 With all acessories including PCC foundation tapper plug bolts, nuts, screwed including fittings complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repairs Reach Elite HO/HP Light to illuminating the tallest structure and highlights details up to 564m of100 W to 300 W luminaire light up Gardens trees integral decorative IP 65/IK10 With all acessories including PCC foundation tapper plug bolts, nuts, screwed including light fitting complete all as specified and directed by Engineer-in-Charge.
Material and Labour required for checking serviceability of all garden lights and if minor fault find then inform to the concerned JE E/M and repair that garden light and all as specifien and directed by engineer-in-charge. (Note-: Quotated rate shall include minor spare parts which is required for the serviceability of that light.)
M & L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or burried in ground or drawn in conduit /pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6 mm galvanised iron strip.
Material and Labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed by engineer-in-charge.
M&L for Earthing with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, burried directely in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 32 x 6 mm with the help of bolts, nuts, and washers of galvanised iron or steel, including necessary excavation, PCC 1:3:6 type C2 and PCC cover 1:2:4 type B1 watering arrangement with GI pipe funnel, jali, complete all as specified and shown in electrical plate No. 5 of SSR Pt-1, including testing on completion.
Supply and lay in repair 40 mm dia GI tubing "light" grade for cable protection at road crossing/ hard standing/ plinth protection/ on the pole etc complete all as specified and directed.
Supply and fix in repair FRP type looping box of suitable size including necessary arrangement to fix the looping box with the suitable size of cable glands with entry, nuts,bolts, washers flat iron etc comprising of the followings:- (a) MCB,63 Amps, FP (10 KA) (C series) - 01 No. (b) MCB 5 to 30 Amps, SP (10KA) (C series)-01 No (c) Neutral link - 01 No
Supply and fixing in repair PVC insulated, stranded copper conductor of size 3 core 2.5 Sqmm in connection of FRP type looping box to light fitting connector, passing through GI pipe / tubular pole complete with fixing arrangement all as specified and directed.
Supply and fixing in repair PVC insulated, stranded copper conductor of size 3 core 1.5 Sqmm in connection of FRP type looping box to light fitting connector, passing through GI pipe / tubular pole complete with fixing arrangement all as specified and directed.
Dismantling connections & Taking out broken, damaged / rusted street light poles of any kind / make complete alongwith light fittings including necessary excavation, breaking PCC, returning/ filling and removing surplus soil out of MD land complete all as specified and directed.
M & L for preparation of deteriorated /rusted Feeder Pillers, scraping and applying two coat of aluminium paint and marking the panel numbers with Black/ yellow paint complete all as specified and directed by Engineer-in-Charge.
Supply and fixing Steel tubular swaged street light poles complete with cast iron base plate ,finial taper plug,bolts,nuts and screws as specified type 410 SP-31 9.0 mtr long and painting with two coat of aluminium paint over one coat of primer on exposed surface of pole all as specified and directed by Engr-in-Charge. (NOTE-Excavation & PCC will be measured and paid separately)
Supply & fixing hot dip galvanized anti corroded( Galvanized Iron Pole) weather proof octagonal mild steel electric poles 8 mtrs long top mounting on foundation complete with base plate and final including PCC foundation as per manufacturer design with 1500 mm long Arms bracket,tapper plug,bolts nuts and screws (Pole plate thickness - 04 mm , pole bottom dia - 135 mm top dia 70 mm ) etc complete all as specified and directed.
M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation, base foundation filling concrete including necessary form work.
M&L for PCC 1:3:6 type C2 using 20 mm graded stone aggregate block masonry with solid block ,exc 10 cm in width and setting in mortar complete for coping of pole including necessary from work and fair finish to the exposed surface area without using extra cement complete all as specified and directed.
M&L PCC 1:2:4 type D2 using 40 mm graded stone aggregate for coping of the poles as in foundation, filling mass concrete, coping including necessary form work.
Supply & fixing in repairs LED Street Light 75 Watt capacity in aluminium pressure die cast housing , High Power LED, secondary optics, IP 65/66, 10KV SPD, >100lm/Watt including wiring complete all as specified & directed.
Supply & fixing in repairs LED Street Light fittings 90 Watt capacity in aluminium pressure die cast housing , High Power LED, secondary optics, IP 65/66, 10KV SPD, >100lm/Watt including wiring complete all as specified & directed.
Supply & fixing in repairs LED Street Light fittings 90 Watt capacity(Warm white) in aluminium pressure die cast housing , High Power LED, secondary optics, IP 65/66, 10KV SPD, >100lm/Watt including wiring complete all as specified & directed.
Supply & fixing in repair LED Flood light fittings 120 Watt capacity in aluminium pressure die cast housing , High Power LED, secondary optics, IP 65/66, 10KV SPD, >100lm/Watt including wiring complete all as specified & directed.
Supply & fixing in repairs LED Flood light fittings 75 Watt capacity in aluminium pressure die cast housing, High Power LED, secondary optics, IP 65/66, 10KV SPD, >100lm/Watt including wiring complete all as specified & directed.
Supply & fixing in repairs LED Flood light fittings 250 Watt capacity in aluminium pressure die cast housing , High Power LED, secondary optics, IP 65/66, 10KV SPD, >100lm/Watt including wiring complete all as specified & directed.
Supply and fix in repair High intensity LED flood light fittings 400 W, specially designed for sports/Search etc. Alluminium housing , polycarbonate secondary optic cover, IP 66, > 110 lm/watt, 10KV SPD and wired with all acessories.
Taking down and refixing U/S high mast light fittings of height 15 meter after lowering the arm including taking out winch, gear box, from high mast pole, including following work:- i)M&L required for oiling, greasing and servicing of steel wire rope , complete double drum winch system, control gear box, checking the internal wiring and balancing the arms duly in vertical position for smooth functioning of high mast tower. ii)Supply and fix in replacement of complete control gear box for high mast lights of any height with all assessories as existing including alignment i.e. truly vertical in position, 2 point suspension system with steel wire rope 6 mm dia and suitable avaitiaon light as existing complete all as specified.
Taking down existing panel and Supply ,install,Testing and Commissioning of HIGH MAST PANEL with provison for switching on & off the mast fittings by automatic control using astronomical timer and contactor for automatic switch on & off of mast at present time over current and latch mechanism including 4 core PVC flexible cable 2.5 Sqmm multi stranded copper with 3 pin metal clad socket to plug the supply for luminaries shall be mounted on PVC rigid board of suitable size provided in the base compartment of mast to terminate the incoming power supply cable from junction box to incoming luminaries complete outdoor type weather proof with MCB 63 Amps 4 pole 35 KA for incoming all as specified and directed by engr-in -charge.
Supply and fix CC LED driver suitable for 45-75 W high power LED street light fittings, Vin- 230V, AC, 50Hz , Vout- 68-80V DC, PF > 0.95, Current (I in) : <1.25A, Current (I out) : 1.0-1.5A with IP rating 66 duly taking down the existing UNSV driver complete all as specified.
Supply and fix CC LED driver suitable for 90-165 W high power LED street light fittings, Vin- 230V, AC, 50Hz , Vout- 88-93V DC, PF > 0.95, Current (I in) : <1.7A, Current (I out) : 1.5A with IP rating 66 duly taking down the existing UNSV driver complete all as specified.
Supply and fix CC LED driver suitable for 400 W high power LED street light fittings, Vin- 230V, AC, 50Hz , Vout- 100-120V DC, PF > 0.95, Current (I in) : 0.110A, Current (I out) : 0.63 A duly taking down the existing UNSV driver complete all as specified.
Supply and fix CC LED driver suitable for 250 W high power LED light fittings, Vin- 230V, AC, 50Hz , Vout- 32-42V DC, PF > 0.95, Current (I in) : <1.25A, Current (I out) : 1.0-1.5A with IP rating 66 duly taking down the existing UNSV driver complete all as specified.
Supply and Fix in repair street light/Decorative Light timer astronomical type 230V,50Hz,1 Channel Control and automatic operating modes, IP rating 20 and fix timing according to sunrise and sunset which automatically switches on and switches off street Light/Decorative Light all as specified and directed by Engineer-in-Charge.
M & L for preparation of deteriorated /rusted poles, scraping and applying two coat of aluminium paint and for decorative pole black paint after one coat and marking the pole numbers with Black/ yellow paint complete all as specified and directed by Engineer-in-Charge.
M & L required for attending & restoring the short circuits/sparking/tripping complaints for street lights and landscaping lights and removing the burnt out parts, making proper insulation with insulating materials etc complete all as specified and directed by Engr - in - Charge.
M & L for replacement of old deteriorated street light brackets made out of GI pipe of 40 mm dia light grade, single arm of suitable size and shape complete including fabrication, fitting fixtures all as specified and directed at site by Engr - in- Charge
M & L for replacement of old deteriorated street light brackets made out of GI pipe of 40 mm dia light grade, Double Arm of suitable size and shape complete including fabrication fitting fixtures all as specified and directed at site by Engr - in- Charge
M & L for in Repair/replacement coping of existing street light /Garden Lights poles complete with PCC 1:2:4 D2 type 20 mm graded stone aggregate, painting after PCC work complete all as specified and directed at site by Engr - in- Charge.
Material and Labour required for servicing of heritage aesthetic look (RAL Color Code 9007) post top luminaire (including light pole and lights as per description) having symmetrical distribution beam angle of 120°X120° (±5%) with housing material of Die-cast aluminum, powder-coated finish, PC cover; system wattage not exceeding 33W and system lumen output of not less than 3900 lumens with efficacy not less than 118 lumens/W. CCT of 3000K and CRI>=70 with SDCM<5. Weight not more than 8.5 kgs. Fixture shall operate in a temperature range of 0°C to 50°C . Fixture shall have input voltage for 100 – 277 VAC, 50/60 Hz. Lifetime should be at least 50,000 burning hours at L70 at 40 degree centigrade ambient. Fixture shall equipped with total IP65 protection and mechanical impact of minimum IK08. The fixture should be capable of surge protection upto 20kV minimum with salt spray test of 50hr. Luminaire driver should be EMI/EMC Compliant Luminaire dia must be minimum 460mm. LM79 and LM80 reports must be submitted along with the bid. Luminaire and driver should be of same make. Luminaire ies file (photometry file) must also be submitted along with the bid. Similar to PHILIPS BSS461 LED40WW 110-277V UNICLASSIC all as aspecified and directed by engr-in-charge. (NOTE :- Excavation & PCC will be measured and paid seperately)
Supply and fix premium poles with base plate and all associated items made out of MS pipe (finished with P.U. painted shade) of 301cm height and window at the bottom for space for MCB and terminal block for fixing LED post top integral mounted decorative LED light post 24 Watt with IP65 protection suitable for 40/25/20 mm dia GI bend to desired shape as directd by Engineer-in-Charge. (Note- Excavation and PCC will be measured and paid seperately).
Supply and Fix in repair High density poly?ethylene pipes (HDPE) of pressure rating 6 kgf/cm2 laid in trenches of dia 32mm all as specified and directed by engr-in-charge.
NOEL ENGINEERS (BID ID -3486178)
Shree Ayyappa Engineering (BID ID -3487972)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf