Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.4 LAccepted-AOC NO 83 THAMMAIAH GARDEN ABBIGERE CHIKKABANAVARA PO BANGALORE 560 090 | BENGALURU URBAN | KARNATAKA | 560090 | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹49.3 L+₹32,780 (0.67%)Rejected-Finance | L2 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 3 | L3₹49.7 L+₹69,430 (1.42%)Rejected-Finance 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L3 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 4 | Rejected-Technical | - | Rejected-Technical Un enlisted and Documents not uploded as per NIT |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
13 May 2024, 6:00 pmClosed
Garrison Engineer M AF Jalahalli
Garrison Engineer M AF Jalahalli Bangalore 560013
REPAIR MAINT OF EXTERNAL ELECTRICAL DISTRIBUTION SYSTEM LT PANEL EARTHING LIGHTING SYSTEM AND OTHER MISC E M WORKS AT AFTC 2 DC AREA AND CQAE WE UNDER GE M AF JALAHALLI
2024_MES_650048_1
8919/E8
Open Tender
Electrical and Maintenance Works
Item Rate
181 days
Garrison Engineer M AF Jalahalli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE AF MAINT JALAHALLI PUBLIC FUND ACCOUNT
₹1 L
18 Jun 2024
13 Apr 2024
15 May 2024
13 Apr 2024
13 May 2024
27 Apr 2024
13 Apr 2024 - 20 Apr 2024
Amount
Excavation in trenches not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level and laying of pipelines etc in soft/loose soil, complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed.
Removing surplus excavated material (soil) from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and directed.
Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed. Note :- (i) Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment.
Material and labour for well burnt class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and directed.
Supply and laying in repair of GI pipe light grade for cable protection of size 80mm bore with fittings, complete all as specified and directed.
Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :- The tenderer shall take into consideration for following points while quoting rate for this item and the unit rate is deemed to be inclusive for :- (i) Earth work and excavation in any type of soil (ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed. (iii) Removing excavated material to out side MD land. (iv) Laying of any type/any bore of pipe in trenches including taking down. Supply of pipe shall be measured and paid separately (v) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
Material and labour in repair for 3 ½ core 185 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
Material and labour in repair for 3 ½ core 95 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
Material and labour for making straight through joint with suitable jointing kit consisting of water proof adhesives for UG cable of size 3.5 core 50 Sqmm to 185 Sqmm, complete all as specified and directed.
Material and labour for Boring of holes under road, pavement, hard standings by trenchless technology using ultra sound technique and necessary machine including HDPE pipes of 100 mm dia suitable for 0.4 Mpa working pressure, complete all as specified and directed.
Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thromoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 300 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM abobe ground level ,including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 160 Amps ,36 KA - 02 Nos (Incomer). (b) On Load Change over front operated of capacity 200 Amp,4 Pole ,415 V -01 No. (c) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 125 Amps ,10 KA - 01 No. (d) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 100 Amps ,10 KA - 02 Nos. (e) MCB SPN ,240 V of capacity 40 Amps ,10 KA - 01 No. (f ) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (h) Space for spare feeder -01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, wiring, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schenider/L&T/C&S. (iv) MCCB should be ICu = 100 % ICs . (v) Make of LT Panel /FPB shall be as per mentioned in list of makes (PS).
M &L for PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as in copping to pole including necessary form work slightly rounding or squaring, complete all as specified and as directed .
M & L for PCC 1:4:8 type D2 with (using 40mm graded stone aggregate) as in foundation of poles etc, complete all as specified and as directed
Supply and fixing LED flood light fitting of 70 watts pressure die cast housing with IP66 protection with efficient high output emitter LED for better distribution with all accessories pre wired including necessary electric connection and bracket for fixing the fitting, complete all as specified and as directed. Make :- Philips/ Bajaj/ CG
Suply and fix in repairs LED decorative post top lantern fitting 40W, 230V AC with IP 65 protection and resistant to impact and corrosion with necessary electrical connection, complete all as specified as directed. Make: CG/Bajaj / Philips/Havells
M & L for Sub main wiring complete with 2 runs of 2.5 Sqmm single core PVC insulated heavy duty unsheathed cable 1100 Volts grade multistranded copper conductor drawn through and including 20mm dia PVC conduit and conduit accessories fixed in wall /roofs/poles etc including provn of PVC insulated heavy duty ISI marked unsheathed copper conductor cable 2.5 Sqmm for earth continuity conductor for making connection from Jn box to street light fittings, complete all as specfied and directed by Enge- in- charge. Note : 3 Runs of 2.5 Sqmm cable and PVC conduit shall be measured as one unit.
Supply and replace in repair - MCCB 4 pole, 415 volts, adjustable type, 250 Amps, 36 KA including disconnecting and removing existing with necessary connected fastners, burnt cables, accessories etc,. all as per site requirement/existing make/model, complete all as specifed and as directed. Make : Indo Asian/ L&T/Legrand
Material and labour for outdoor type LED Street Light fitting of 35 watts comprising of epoxy powder coated hsg, enclosed with glass cover in frame, with protection IP66 complete with all accessories and lamp colour white and fixing including GI bracket of suitable size/ dia, complete all as specified and directed. Make :- Philips/ Bajaj/ CG
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thromoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 300 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 25 KA - 01 No (Incomer). (b) On Load Change over front operated of capacity 100 Amp, 4 Pole, 415 V - 01 No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 10 KA - 01 No. (d) MCB TPN, 415 V of capacity 40 Amps, 10 KA - 01 No. (e) MCB SPN, 240 V of capacity 40 Amps, 10 KA - 02 Nos. (f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (h) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as per mentioned in list of makes (PS).
Material and labour in repair for 3 ½ core 50 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
Material and labour in repair for 3 ½ core 35 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising of 17mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed. Make : Model HTSP 317 of safeTrode or equivalent in OBO Betterman/ FURSE/ERICO.
The quoted rate shall also deemed to be included the following :- (i) Prior to installation of maintenance free chemical earthing, soil resistivity test to be carried out at the location where earthing work to be done in presence of Engr-in- Charge/JE (E/M),user and the report has to submit to Garrison Engineer with recommendation of manufacturer, if required additional interconnection of earthing (not more than 04 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testing and submission of report with recommendation deemed to be included in the quoted rate.
(ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors.
(iii) Rate of earth energizer compound of 25 Kg of 02 bags and earth resistance reducing liquid 10 litre per cane for each pit deemed to be included in the quoted rate.
(iv) Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
(v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete.
(vi) Copper strip of size 20 x 3 mm should be fixed on proper post insulator at the instrument end ( copper strip upto 7.5 RM will be considered in unit quoted rate and extra will be measured and paid separately).
(vii) Testing of earth shall be carried out in presence of departmental and user representative and report shall be submitted to Garrison Engineer duly signed by all concerned.
(viii) Earth resistance tester will be provided by the contractor. Tester should be calibrated from authorised company/ lab.
(ix) Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintened duly signed by all concerned. After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
(x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
(xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock.
(xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained.
(xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing per each earthing shall be retained from payment due to the contractor from final bill for the guarantee period.
(xiv) The electrode shall carry manufacturer's name .
(xv) The connection clamp shall be permanentlly welded to the copper bounded rod to avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
(xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm.
(xvii) Earth work such as auguring and making good the surrounding area shall carried out in any type of soil.
(xviii) The contractor shall submit CPRI India certified document for copper bonded rod to ensure genuineness of material.
(xix) Sign board of mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide Zinc chrome primer showing result of earthing should be fixed near the earth pit after completion as directed by engr -in- charge.
Copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing one, complete all as specified and directed. Note : - All Joints should be joined by Exothermic Welding or Brazing.
Earth pit cover made of heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 9.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit, complete including taking down old one, complete all as specified and directed. Make : Model SEPC 250 of SAFE TRODE/ Electrogrip Model/ EGTEK3LC of ISG Global or equivalent in OBO Betterman/ ERICO. Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
Supply & erecting in replacement of Mild steel tubular swaged poles of 9.0 meter long 410, SP-31 complete with cast iron base plate, bracket, finial taper plug, bolt, nuts & screws and painted on both side (internally & externally), external surface painted with two coat of aluminium paint over a coat of red oxide primer and painting with black and white up to 1.5 meter from top of PCC coping white colour paint as in strips of equal width including marking pole numbers with one coat of synthetic enamel paint, complete all as specified and as directed including dismantling of old U/S poles of any height and any description all as directed.(Excavation and earth shall be measured and paid separately)..
Material and Labour for fabrication of GI pipe bracket of 32mm dia for street light fitting up to 1.5 mtr length with suitable size MS clamp with nuts and bolts, complete all as specified and as directed.
Supply and fixing moulded (FRP) junction box with IP 65 protection of size 230x170x105mm hinged type with 32 Amp 4 way heavy duty terminal block with 6Amp MCB SP and two number of cable entry gland of standard size with suitable stainless steel bracket to fix with pole complete all as specified and directed
Supply and fixing LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp, bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection, complete all as specified and directed. Make : Havells/ Philips/ CG/ Halonix
Supply and fix in repairs Power Contactor 3 pole,415 volts,50 Hz with AC coil,65 Amps rating suitable for street light timer DB including removing the old one complete all as specified and directed. Make : Havells/ L&T/Indo Asian
Supply and replace in repair - MCCB 4 pole, 415 volts, adjustable type, 160 Amps, 36 KA including disconnecting and removing existing with necessary connected fastners, burnt cables, accessories etc,. all as per site requirement/existing make/model, complete all as specifed and as directed. Make : Indo Asian/ L&T/Legrand
Material and labour for painting of steel tubular LT pole 9 mts above the ground level with two coat of aluminium paint after cleaning the existing surface of the poles/brackets/cross arm and marking the pole, numbers as per existing pattern including different colour 1.5 mtr from the bottom of pole complete all as per specified and directed.
Material and labour for painting of RCC pole 9 mts above the ground level with two coat of cement base paint over a coat of alkaline resistance paint preparation the existing surface of the poles and marking the pole numbers as per existing pattern, complete all as per specified and directed.
Material and labour in repair for 3 ½ core 25 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
Material and labour in repair for 4 core 16 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
Supply and laying in repair GI pipe light grade for cable protection of size 50 mm bore with fittings, complete all as specified and directed.
Material and labour for making straight through joint with suitable jointing kit consisting of water proof adhesives for UG cable of size 3.5 core 16 Sqmm to 35 Sqmm, complete all as specified and directed.
Supply, fabricating, installation, testing and commisioning Feeder Pillar Box of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather, vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thromoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclouser should be above 200mm for air ciruculation & to minimize temp rise. Panel should be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 200 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM above ground level ,including dismantling and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 100 Amps ,25 KA - 02 Nos (Incomer). (b) On Load Change over front operated of capacity 125 Amp,4 Pole ,415 V -01 No. (c) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 63 Amps ,10 KA - 01 No. (d) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 40 Amps ,10 KA - 03 Nos. (e ) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (f) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (g) Space for spare feeder -01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, wiring, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schenider/L&T/C&S. (iv) MCCB should be ICu = 100 % ICs . (v) Make of LT Panel /FPB shall be as per mentioned in list of makes (PS).
Supply and fix LED street light fitting 60 Watts, with powder coated pressure die cast aluminium housing and IP 66 protection, built-in control gear complete with anodised reflector, toughened heat resistant glass cover, LED 60 watts white colour lamp, connector block with all accessories pre wired including GI bracket of suitable size, complete all as specified and as directed. Make :- Philips/ Bajaj/ CG
Supply and fix in repairs Street light analogue timer switch 3 module,weekly programmable with battery back up of 100 hrs,current capacity 16 Amps with 1 changeover (1 CO) complete all as specified and directed. Note :- Make : Indo Asian/Havells / L&T
Supply and fixing of on load change over switch 415 volts in sheet metal enclosure four pole of capacity 200 Amps including taking down of old unserviceable change over switch, complete all as specifed and directed. Make : Havells/ L&T/Indo Asian
Supply, fabricating, installation, testing and commisioning Feeder Pillar Box factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather, vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thromoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with 01 No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 300 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) bedding upto a height of 45 CM above ground level ,including dismanting and taking out U/s old LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 200 Amps ,36 KA - 02 Nos (Incomer). (b) On Load Change over front operated of capacity 250 Amps,4 Pole ,415 V -01 No. (c) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 160 Amps ,25 KA - 02 Nos. (d) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 63 Amps ,10 KA - 02 Nos. (e) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 40 Amps ,10 KA - 01 No. (f ) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (h) Space for spare feeder -01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, wiring, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schenider/L&T/C&S. (iv) MCCB should be ICu = 100 % ICs . (v) Make of LT Panel /FPB shall be as per mentioned in list of makes (PS).
Supply and fixing LED flood light fitting of 120 watts pressure die cast housing with IP66 protection with efficient high output emitter LED for better distribution with all accessories pre wired including necessary electric connection and bracket for fixing the fitting, complete all as specified and as directed. Make :- Philips/ Bajaj/ CG
Supply and fix smart integrated solar all in one LED solar street light fitting 12 V,12 Watts with IP 66 protection, built-in MPPT charge controller,Lithium ion battery,mono crystalline solar panel, PIR motion sensor complete with anodised reflector, toughened heat resistant glass cover, LED 12 watts white colour lamp, connector block with all accessories pre wired including bracket,welding,drilling,bolts,nuts and any alteration required for fixing the panel with existing pole, complete all as specified and as directed. Make:Philips/CG/Havells/Bajaj
Supply, installation, testing and commissioning of smart street light control system using GSM/Lux based technology having 20 KW 3 phase 64 Amp load capacity per phase and can be operated by IVRS/SMS/lux based infrared sensor etc complete with following:- (i) Nature switch operation should be based on natural light lux level. Require illuminnance level for switching on is ≤ 60 lux and for switching off ≥ 10 lux. The smart unit should have 4 timers that can be set via SMS. (ii) Surge protection device (SPD) should provide protection agaist indirect lightning & switching surges. It should conform to IEC61643-11 and should have 40 KA capacity. (iii) The sensor & SPD along with suitable power contactors and incoming-outgoing MCCB/MCBs should be enclosed in a enclosure made of rust proof, electric shock proof , metal weather proof conforming to IP65 with angle iron frame of suitable size 04 Nos legs 600 mm long , PCC 1:2:4 type B 1using 20 mm graded aggregate for grouting of base including taking down old unserviceable panel. The scope of work also comprising the following :- The GPRS shall have seven segment display to show voltage, current, network and street light status , it should also have indicator for showing supply status , timer , overload or high low voltage. It should also able to measure voltage, current and automatic set street light overload current. Unit have facility to call back to registered number for power on/off and if any fault occurs at site.in SMS it should also monitor power/on/off time light on off time, ampere, voltage, unit mode, network percentage date and mobile number who called device number. The device should also have battery backup with minimum 24 hours backup capacity. The panel should have three operation mode :- 1. GSM mode -in this mode light should be switched as per GSM controller's preset time by user by sms , 4 clock base timer facility should be availble 2. Nature switch based-in this mode light will be switched as per nature light lux level 3. Bypass mode -in this mode light will switched on directly for testing purpose and emeregncy switching .In GSM controller there should be facility to register 4 user by sms/call and alerts will be sent on all registered number and also call back on power on/off and faults on first registered number.The GSM controller should also compatible for cloud based data transmission for interfacing with web for future use, Password protection for Accessing the control of device via SMS/IVRS, complete all as specified and directed including the following subcomponent, supply and fixing features :-
(a) TPN MCCB 100 Amps capacity, 10 KA, 415 Volts -01 No. (Incoming) with separate SPD of 40 KA capacity. (Make of MCCB- L & T, BCH, Havells) (b) Supply Resign cast CT'S - set of 3 (c) GSM based smart street light controller. (d) Lux based sensor to operate external as per light intensity. (e) Line Contactor, AC 3 duty, 3 phase, 415 volts. 50 Hz , 32 Amps -02 Nos (make - L & T, BCH, Havells) (f) MCB SP 32 Amps- 06 Nos (make -L & T, BCH, Havells) (g) Terminal block suitable for 100 Amp rating with brass contacts for INPUT/ and 63 Amp for OUTPUT termination. (h) GSM/Timer/Bypass Mode switch. (j) Panel wiring for control circuit with copper flexible 1.5 Sqmm & power wiring 10 Sqmm flexible. Make- Tricolite/ Kewintech/HPL
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thromoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out U/s old LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 36 KA - 02 Nos (Incomer). (b) On Load Change over front operated of capacity 400 Amp, 4 Pole, 415 V - 01 No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 36 KA - 01 No. (d) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (f) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as per mentioned in list of makes (PS).
Material and labour for Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of plate not less than 1.5 m below ground level connected to and including galvanised earth strip of size 25x6 mm (up to 7.5 mtr length) and GI pipe 40 mm light grade for protection of GI earth strip by means of bolts, nuts, check nuts and washers made out of galvanised iron and connected to earth test point as shown in electrical plate No. 3 of SSR Part-1-2009 and as specified or indicated and testing on completion including excavation and earth work in any in type of strata available at site, PCC (1:3:6) type C-1 using 20mm graded stone aggregate for earth chamber, precast RCC slab 50mm thick in cement concrete (1:2:4) type B-1 using 20mm graded stone aggregatereinforced with welded steel wire fabric (xpm) weight not less than (4kg/sqm), funnel with GI watering pipe of 20mm bore galvanised, medium grade, with nuts and lugs incl taking out old earthing of any description, complete all as specified and directed. Note:- (a) All Joints should be joined by Exothermic Welding or Brazing.
(b) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge, User and proper record shall be maintained duly signed by all concerned. (c) Earth resistance tester shall be provided by the contractor. It should be caliberated from authorised company/ lab. (d) After testing if desired earth resistance of less than 5 Ohm is not achieved, the earthing will be redone at no extra cost to Govt till desired result is achieved.
Material and labour in repairs Galvanised iron earth strip of size 25 x 6 mm fixed on proper post insulator at the instrument end, complete all as specified and directed. Note :- An amount of Rs 57295.00 on account of credit schedule for schedule 'A' part II shall be deducted from the total amount of BOQ to arrive at the contract sum.
Forge Engineering & Electricals
rvelectricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .