Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹1.6 L+₹7,885.05 (5.27%)Rejected-Finance H NO 861 SECTOR 1 4 HOUSING BOARD COLONY NEAR POLY CLINIC HISAR HARYANA | HISAR | HARYANA | 125001 | L2 | Rejected-Finance L2 | |
| 3 | L3₹1.7 L+₹21,756.05 (14.5%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹2.2 L+₹66,506.15 (44.4%)Rejected-Finance DSS 110 GROUND FLOOR SHOPPING COMPLEX SECTOR 15 125001 | HISAR | HARYANA | 125001 | L4 | Rejected-Finance L4 |
Tender Value
Refer Docs
EMD Value
₹3,450
Closing Date
18 Jan 2021, 5:00 pmClosed
Executive Engineer Elect Divin PWD B and R Hisar
Executive Engineer Elect Divin PWD B and R Hisar
Construction of Divisional Store Cum EVM Storage Godown at Ch. Dadri in Provl. Division Ch. Dadri (Pdg. Security Light only).
2021_HRY_155819_1
PWD/Elect-GGN/Elect-HSR/100115
Open Tender
Electrical Works
Works
120 days
HISAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
₹3,450
23 Apr 2021
11 Jan 2021
19 Jan 2021
11 Jan 2021
18 Jan 2021
11 Jan 2021
Amount
Main Switches: Supply and erection of metal clad switches / B.D.Bs with rag bolts on wall or on existing angle iron board / pedestal including bonding to earth and necessary connections. (HSR 31.12 (a). v) Double pole switch 32 amp. 415 Volts Cat-B.
Miniature Circuit Breaker and Isolator: Supply and erection of miniature circuit breaker / isolator 240 /415 V in the existing distribution board including making necessary connections. (HSR 31.17) Miniature circuit breakers of 9 KA breaking capacity. ii) SP MCB 6 amp. to 32 amp.
iii) SPN MCB 6 amp. To 32 amp.
Pipe Laying: Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. (HSR 31.21) xii) Galvanized iron pipe 40 mm dia on flushed.
xxvii) Galvanized iron flexible pipe complete with socket nipples and check nuts etc. at both ends ( upto length of 1 meter.) b) Size 20 mm dia.
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections. (HSR 31.26) v) 16 Sq. mm 2 Core Ard. Cable.
Supply and erection of suitable compression type brass cable glands for underground Cable. (HSR 31.28) ii) 10 Sqmm to 16 Sqmm Cable 2 to 4 Core .
Street Light (HSR 31.30) IV) Supply and erection of weather proof M.S.Box of size 20 cm x 15 cm x 10 cm. covered with 3.00 mm thick M.S.sheet hinged cover, locking arrangements , housed in wall , including the cost of 1 no. 16 amp. 415 volts kit-kat and 2 nos. 63 amp. 415 volts neutral links fixed on hard wood board in the M.S.Box including painting and necessary connections.
S/E of PVC unsheathed copper conductor cable single core 1100 volts grad in pipe of suitable size excluding cost and erection of pipe. (HSR 31.40). i) Cable size 1.5 sqm(3/0.81 mm)
S/E of double door sheet steel enclosure distribution board suitable for MCBs and ELCBs recessed in wall including bonding to earth with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-Charge of the work. (HSR 31.41) ii) 8-way, SP&N (Horizontal)
S/E of MS saddles and clamps on wall/ RCC parapet for fixing underground cable at a distance of 0.60 meter centre to centre fixed by means of rawl plug including the cost of all labour and material required to complete the job in all respect upto the Engineer-in-Charge of the work. (HSR 31.48).
Supply and errection of double walled corrugated (DWC) HDPE pipe laid 1 meter below ground level including diging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including the cost of the labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work. (HSR 31.67) HDPE pipe 63/50 mm outer dia/ inner dia
Supply and errection of Hot Dip Galavanized octagonal pole 3 thichness, with base plate including of nut and bolts and all accessories as supplied by the manufacture including cost of fundation accessories etc. The foundation bolts as per manufacturer design should be hot dipped galanized pole complet of 2 nos. 100 A, 4 pole nature links including connection etc with suitable connection arrangments for 2 no. MCB/ kit kat including cost of RCC 1:1:5:3 for foundation of size 0.7 m x 0.7m x 1.8 m with minimum 8 Nos. 12 mm dia longitudinal MS reinforcement rods with rings of 8 mm dia not more than 200 mm CC for fixing the pole with all labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work.(Philips/ Vipin ST poles/ Bajaj/ Valmont). 9 M long pole with top dia 70 mm and bottom dia 155 mm with base plate of size 260 x 260 x 16 mm
S/E of round bracket for erection of LED flood light suitable for 4/6 Nos. fittings on existing 7/9 M long Pole/ high mast pole including all labour with the help of 50 mm dia round bracket, 1 Meter radius, duly painted with 2 coats of Red oxide & G.I. paint and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work.
Supply and erection of 25 W LED Post lantern new generation energy saving envirmental friendly long life aesthetically designed with symmetrical light distribution, spen aluminum land scap luminaries with high power LED as light source with the protection of IP-65 of LHEVBGP7PN 6K 025 (Rubby clear) of Havell's make/ BLPTSP 25 W NW LED of Bajaj make/ LPTH-20- CDL of Crompton make complete with all accessories and labour to complete the job upto the entire satisfaction of Engineer-in-charge of the work.
S/E of 120 W LED Flood light luminaries with high power LED < 120 Lumens per Watt Philips / Havell's / GE/ Wipro make in aluminum pressure die casting housing toughened glass cover with IP-66 protection With Lense and dual surge protection device internal 5 KV and external 10 KV including all petty material with labour for errection, complete in all respect of Engineer-in-Charge of the work.
M/S NATWADIA ELECTRICAL COMPANY
INFERNO POWER AND SAFETY
M/S SHIV ELECTRICAL AND CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .