Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.6 CrAccepted-AOC NO 1387 1 EDICIA JEEVANANDHAM STREET MOSAKKAVUNDANPALAYAM ERODE 638002 TAMIL NADU | ERODE | ERODE | TAMIL NADU | 638002 | ₹45.6 Cr Quoted ₹47.9 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹48.5 CrRejected-AOC | ₹48.5 Cr | L2 | Rejected-AOC Rejected |
| 3 | L3₹49.2 CrRejected-AOC NO 1 8 SENTHILAGAM AINDHUPANAI KADACHANALLUR ERODE 638 008 | NAMAKKAL | TAMIL NADU | 638008 | ₹49.2 Cr | L3 | Rejected-AOC Rejected |
| Sl No | Description | Qty | Unit | PRIYA ENGINEERING PROJECTS PRIVATE LIMITED L3 | K.K. ARUMUGAM AND CO L2 | SREE BALAJI ASSOCIATES PRIVATE LIMITED L1 |
|---|---|---|---|---|---|---|
| 1.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness of pressed tiles and weathering course | 3,012 | Sqm | 55 ₹1.7 L | 52 ₹1.6 L | 50 ₹1.5 L |
| 2.00 | Dismantling, clearing away and carefully stacking materials useful for re-use false ceiling with include GI perimeter channel of size 45mm thick | 963 | Sqm | 135 ₹1.3 L | 135 ₹1.3 L | 130 ₹1.3 L |
| 3.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness of Reinforced cement concrete | 476 | Cum | 4,930 ₹23.5 L | 4,850 ₹23.1 L | 4,900 ₹23.3 L |
| 4.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness Wrought & putup framed timbers in roofs / floors | 61 | Cum | 860 ₹52,460 | 840 ₹51,240 | 850 ₹51,850 |
| 5.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness of Brick / stone masonry in lime mortar walls | 595 | Cum | 264 ₹1.6 L | 265 ₹1.6 L | 260 ₹1.5 L |
| 6.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness of Brick wall in cement mortar | 3,104 | Cum | 324 ₹10.1 L | 350 ₹10.9 L | 300 ₹9.3 L |
| 7.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness of plain Cement concrete | 435 | Cum | 560 ₹2.4 L | 575 ₹2.5 L | 550 ₹2.4 L |
| 8.00 | Dismantling, clearing away and carefully stacking materials useful for any thickness of Random Rubble masonary in cement mortar | 203 | Cum | 325 ₹65,975 | 320 ₹64,960 | 300 ₹60,900 |
| 9.00 | Removal of windows and doors including Frames hinges and fastenings | 1,421 | Sqm | 185 ₹2.6 L | 175 ₹2.5 L | 170 ₹2.4 L |
| 10.00 | Dismantling, clearing away and carefully stacking materials useful for re-use for Floor finish and dadooing walls in cement mortar with mosaic tiles / glazed tiles / cuddapah slabs | 3,065 | Sqm | 70 ₹2.1 L | 68 ₹2.1 L | 70 ₹2.1 L |
Tender Value
₹45.6 Cr
EMD Value
₹22.9 L
Closing Date
10 Feb 2026, 3:00 pmClosed
Joint Commissioner/Executive Officer
Head Office, ADS TEMPLE, North Giriveethi, Adivaram, Palani
DISMANTLING EXISTING DAMAGED KANDAN ILLAM, KADAMBAN ILLAM, IDUMBAN KUDIL AND CONSTUCTION OF NEW PILGRIMS REST HOUSE
2026_HRCE_646484_1
5/2025-2026
Open Tender
Civil Works - Buildings
450 days
Giriveethi, Palani
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹22.9 L
Joint Commissioner / Executive Officer
5 Mar 2026
24 Jan 2026
10 Feb 2026
24 Jan 2026
10 Feb 2026
3 Feb 2026
30 Jan 2026
Dismantling, clearing away and carefully stacking materials useful for any thickness of pressed tiles and weathering course
Dismantling, clearing away and carefully stacking materials useful for re-use false ceiling with include GI perimeter channel of size 45mm thick
Dismantling, clearing away and carefully stacking materials useful for any thickness of Reinforced cement concrete
Dismantling, clearing away and carefully stacking materials useful for any thickness Wrought & putup framed timbers in roofs / floors
Dismantling, clearing away and carefully stacking materials useful for any thickness of Brick / stone masonry in lime mortar walls
Dismantling, clearing away and carefully stacking materials useful for any thickness of Brick wall in cement mortar
Dismantling, clearing away and carefully stacking materials useful for any thickness of plain Cement concrete
Dismantling, clearing away and carefully stacking materials useful for any thickness of Random Rubble masonary in cement mortar
Removal of windows and doors including Frames hinges and fastenings
Dismantling, clearing away and carefully stacking materials useful for re-use for Floor finish and dadooing walls in cement mortar with mosaic tiles / glazed tiles / cuddapah slabs
Collecting the scattered debris from the campus and conveying away the same to out side by lorry to a lead of 3km (entirely with in the city limit)including loading and un loading charges and dumping in low places and levelling neatly etc., complete complying standard specification
Earth work excavation and desposting on banks with initial lead of 10m and initial lift of 2m in hard stiff clay, stiff black cotton soil, hard red earth, shales, murram, gravel, stony earth and earth mixed with small size boulders et., As per SS 20B excluding hard rock requiring blasting inclusive of shoring shuttering, baling ojut water where ever necessary and including refilling consolidation etc., complete in all respects complying with relevent standard specifications and as directed by departmental officers.
Providing Pre-constructional anti- termite treatment and creating a chemical barrier to the building by injecting chemical emulsion of required concentrations raft slab and beam, under Cellular raft slab, around the footings, column pits, trenches, pits, wall trenches, back fill, plinth filling, junction of wall and floor, side walls of foundation, external perimeter of building,surrounding of pipes expansion joints, etc. as per IS specification and as per the instructions of chemical manufacturer and all as directed.The treatment shall be carried out strictly in accordance with the technical specification and conforming to IS 6313 (PART-2) or equivalent BS specification.
Supplying and Filling with M - sand in foundation and others sub structures for 100mm thick and well watered, rammed and consolidated by power compacter. The rate includes the cost of M sand, compacting with mechanical compactors, labour charges for leveling, loading & Unloading and Transportation charges etc., complete and as per the standard specification.
Plain Cement Concrete 1 : 5 :10 ( one part of cement, five parts of sand and ten parts of hard broken stone ) using 40 mm gauge hand broken hard broken granite stone jelly complying with standard specifications in foundations and basement.
Supplying and Filling Gravel in 'foundation and basement with filling crushed stone sand in layers of not more than 15cm.thick well rammed watered and compacted -1m3 etc., complete complying with standard specification.
Refilling the approved good quality earth in plinths, area development etc. wherever specified in layers of not exceeding 200 mm thick., with available earth at site.
Supplying and erecting centering for sides and soffits including supports and strutting up to 3.30 m height with all cross bracing for plane surfaces as detailed below, using mild steel sheets of 90 X 60 cm 10 gauge stiffened with MS angle of 25 X 25 X 3mm for boarding, laid over adjustable span & jacks and supported by 50mm dia pipes for general pipes scaffolding systems @ a spacing of 1.20m c/c and vertical connected at a height of 2.0m c/c including 'C' & 'U' clamps and base receiver cup at bottom for connecting pipes etc and removable systems etc., the rate including cost of all materials, labour charges, wastages, placing, transportation, lead & lifts, tools & plants, fuels, fixing in position at all levels, heights, masking tape in sheet joints, consumables, etc. as complete with all respects complying with relevant standard specification, as directed by the Engineer-in-charge.
For Column footing, plinth / grade beam, bed blocks, template surfaces, steps, piers, raft slab / beams and such other members
For Vertical surfaces such as vertical slab, side slabs of boxing, vertical drops, facia, vertical walls etc.
for plane surfaces such as rectangular or square rcc columns, sunshades, top and bottom slab of rcc boxing, etc.
For Plane surfaces such as RCC floor slab, roof slab, beams, lintels, bed blocks, landing slab, waist slab, portico slabs and beams, etc.
Providing additional strutting to centering of RCC slabs of plain surface for every additional 1.0 metre height or part thereof but not less than 30 cm, over the initial 3.00 metre height from floor level using casurina props of 10cm to 13cm dia including cross bracing etc., complete complying with standard specification and as directed by the department officers.
Providing and laying in position, Standardised Concrete Mix M-25 Grade in accordance with IS:456-2000 using 20mm and down graded hard broken granite stone jelly for all RCC items of works with minimum cementcontent of 350 kglms and maximum water cement ratio of 0.50, including admixture (plasticiser / superplasticiser) in recommended proportions as per IS:9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability with about (5.0 cu.m.) 7730 kg. of 20mm machine crushed stone jelly and with about (3.3 cu.m.) 5156 kg. of 10-12mm machine crushed stone jelly and with about (4.79 cu.m') 7670 kg. of crushed stone sand, but excluding cost of reinforcement grill and
Foundation & Basement
Ground Floor
First Floor
Second Floor
Terrace Floor
Cement Concrete Road
Supplying, fabricating and placing in position Mild Steel / Ribbed Tor Steel grills for all RCC works as per design given including cost of steel and G.I. binding wire in all floors etc. complete complying with standard specification. (Contractor has to make his own arrangements for the supply of steel and binding wire)
Foundation basement
Ground Floor
First Floor
Second Floor
Terrace Floor
Brickwork in Cement Mortar 1:5(One cement and five sand) using II Class Ground Moulded Chamber Burnt Bricks of size 9" x 43/8" x 23/4" in foundation, basement and superstructure including curing etc. complete complying with standard specification.
Foundation & Basement:-
Brickwork in Cement Mortar 1:6(One cement and six sand) using II Class Ground Moulded Chamber Burnt Bricks of size 9" x 43/8" x 23/4" in foundation, basement and superstructure including curing etc. complete complying with standard specification.
Ground Floor:-
First Floor:-
Second Floor
Terrace Floor
Brick partition walls of 11.50cm thickness using best quality II Class Ground Moulded Chamber Burnt Bricks of size 9" x 41/2" x 3" in Cement Mortar 1:3 (One Cement and Three Sand) and both side plastering with CM 1:5 12mm thick using hoop iron reinforcement if found necessary including curing etc.complete and as directed by the departmental officers. (Hoop iron reinforcement will be measured and paid for separately).
Ground Floor
First Floor
Second Floor
Special ceiling plastering and finishing the exposed surface of all RCC items of work such as slabs, beams, sunshades, facia, canopy slab, staircase waist slab, landing slab etc., with Cement Mortar 1:3 (One Cement and Three Plastering Sand) 10mm thick including hacking the surfaces, providing cement mortar nosing, beading for sunshades, staircases, steps, landing slabs and curing, etc., in all floors complying with standard specification and as directed by the departmental officers
Plastering with Cement Mortar 1:5 for Internal walls & External walls (One cement and Five Plastering sand), 12mm thick in all floors including curing etc. complete complying with standard specification and as directed by the departmental officers.
Dadooing walls with best approved quality, white / colour glazed tiles of size 450x300x8mm set in Cement Mortar 1:2 (One Cement and Two crushed stone sand) 10mm thick and pointing the joints with white cement mixed with colouring pigments at the rate of 0.40 Kg. / sq.m. neatly in all floors, curing, etc., complying with standard specification and as directed by the departmental officers.
Flooring with Joint free double charged vitrified tiles of approved quality, colour and design joint free of size 600 x 600 x 8mm thick of approved make, quality and colour in all floors over a base layer of cement mortar 1:3 (one cement three sand) 20mm thick and laid straight alignment and pointed neatly with colour cement at the rate of 0.40 kg/Sqm laid without any air gap in the tiles neatly and fixing in position as per standard specifications and as directed by the departmental officers. The rate including cost of all materials, labour charges, wastages, necessary lead and lifts, working at all levels, transportaion charges, loading, unloading, the same before handing over as complete with all respects complying with relevant standard specification and as directed by the Engineer-in-charge. (Including Skirting work)
Paving the floor with best approved quality fine polished Kota stone slabs of size 600 x 600 of 18 / 20mm with machine cut edges and matching marble slab not less than 100mm width other than Adanga Marbles as border laid over a cement mortar bed of 20mm thick using cement mortar 1:3 (One cement and three sand) fixing the slabs in true right angles with minimum possible width of joints and pointing the joints with white cement mixed with mathcing colouring pigments and polishing with floor polisher to a high degree of finish etc., The kota stone slabs and other materials to be used shall be got approved by the Executive Engineer concerned before use on work, etc., complete as per standard speicification
Flooring with following ceramic tiles of size Joint Free Rectified Ceramic tile of Size- 305 x 305 x 8mm laid over 20 mm thick cement mortar 1:3 (One Cement and Three crushed stone Sand) base mortar over the existing slab / floor including cutting the tiles to the required size with special cutter wherever necessary, laying in position and pointing with white cement mixed with colouring pigment at the rate of 0.3 Kg. / sq.m. etc., complete complying with standard specification. (The make and brand of the tiles should be got approved by Executive Engineer before use on works)
Paving the floor with best approved quality Natural flammed finish granite for flooring/ steps & Landing of 18 / 20mm thick of with machine cut edges laid over a cement mortar bed of 20mm thick using cement mortar 1:3 (One cement and three crushed stone sand) fixing the slabs with required cement slurry and laid in true right angles with minimum possible width of joints and pointing the joints with white cement mixed with mathcing colouring pigments etc., The granite stone slabs and other materials to be used shall be got approved by the Executive Engineer concerned before use on work, etc., complete as per standard speicification
Paving the floor with best approved quality fine polished Granite Stone Slabs of size 1200 x 600 of 18 / 20mm thick of Synthetic Grey, Paradise and similar varieties with machine cut edges laid over a cement mortar bed of 20mm thick using cement mortar 1:3 (One cement and three crushed stone sand) fixing the slabs with required cement slurry and laid in true right angles with minimum possible width of joints and pointing the joints with white cement mixed with mathcing colouring pigments etc., The granite stone slabs and other materials to be used shall be got approved by the Executive Engineer concerned before use on work, etc., complete as per standard speicification.
Paving the floor with pre-polished concrete anti-skid tiles (Required shape and design) of 20mm thick of approved quality and colour laid in Cement Mortar 1:3 (One Cement and Three crushed stone sand) 20mm thick and pointed with white cement mixed with colouring pigment at the rate of 0.40 Kg. / sq.m., curing, etc., complete complying with standard specification and as directed by the departmental officers. (The make and brand of the tiles should be got approved by Executive Engineer before use on works)
Supplying and Paving the Paver Block flooring using Rubber mould paver block (Colour) of standard size over the sand filling of 83mm thick, including laying Compacting with power machine including loading transportation and colour pigments of paver blocks, including cost and conveyance of all materials labour etc complete with standard specification.
Plain Cement Concrete 1:2:4 (one cement, two crushed stone sand and four hard broken stone jelly) using 20mm jelly for wearing coat including laying, compacting, finishing and curing, etc., complete as per standard specificatins and as directed by the departmental officers.
Providing Polymer Coating (Water Proof Coating) for sunken portion of toilet with following specification and the surface shall be cleaned to remove all dust, foregin, matters lose materials or any other deposits of contamination by rubbing with wire brush. Slurry: Dry blend and polymer liquid blend shall be mixed into the desired ratio as per recommendation of the supplier.The mix shall be stirred thoroughly until no bubbles remain in the mix. Any lumps found in mix shall be removed.Apply first coat of polymer modified cementitious slurry by brush on wet cleaned surface. After drying, second coat shall be applied on the first coat as directed by the departmental officers etc. The rate inclusive of cost of materials and labour, etc., complete.
Paving the Top of roof with Solar refelective tiles of size 305 x 305 x 7mm thick of approved quality and colour laid in Cement mortar 1:3 (One cement and three crushed stone sand) 12mm thick and pointed with tile grout (Nitotile Grout or equivalent) and cement in the ratio of 1:3 for joint, curing etc., complete complying with standard specification and as directed by the departmental officers. (The make and brand of the tiles should be got approved by the Executive Engineer before use on works)
UPVC Window :Supplying and fixing UPVC (Un-Plasticized PolyvinylChloride) Windows of casement type (open) from the profile the size of outer frame 60mm x 58mm and shutter profile are reinforcement with GI/1mm125GSMand 100% corrosion free, the profiles are multichambered sections with wall thick of 2mm. The EPDMrubber (black colour) covered with over all the edges offrame and shutter the shutter will be provided withEspag multi power point locks and also it operates ashandle. The corners and joints should be welded andcleaned. Radiations free pin headed plain or browncolour glass 4mm thick should be provided to theshutter and it should not allow leakage of water evenat most ranging storms and should have key lockableaction, security protective hinges, strong lockingsystems and as per size for arresting noise and energyloss. The connecting mechanism between sash andouter frame that enables opening of the window. Thewindow should be fixed to the wall with 100% packingwith screws and silicon packing all round the frames.The window should be got approved from the Executive Engineer before use on work.
Supplying and fixing UPVC (Un-Plasticized Polyvinyl Chloride)Louvered Ventilators of from the profile the size of outer frame 60mm x 58mm and shutter profile size of 60 x 78mm both profiles are reinforced with GI/1mm 125GSM and 100% corrosion free, the profile are multi chambered sections with wall thick of 2mm. The EPDM rubber (blackcolour) covered with all over the edges of frame and shutter.The corners and joints should be welded and cleaned.Radiations pin headed glass 4mm thick should be provided in the louvers. The window should be fixed to the wall with 100% packing with screws and silicon packing all round the frames. The ventilator should be got approved from the Executive Engineer before use on work
Designing the Semi Unitised Structural Glazing System with open groove joint as per design intent,preparation of shop drawings for approval, supply,fabricate, erect as per approved shop drawings at all floor levels and all floor heights including conducting field test as per the test criteria set out in the particular specification (Metholodgy should be got approved by the Dept. Officials.) Design the framing system (i.e. male & Female frame) to support vision panels, spandrel panels either with glass or aluminium composite panel, openable, window panels on a continuous framing supported between floors. Also design the split framing unutilized glazing system in case of strip or punched windows with vision panel proposed with either insulated / Monolithic glass, groove width in the system both in horizontal and vertical shall not be more than 20mm. Glazing of panel shall be done only at factory at the controlled atmosphere
Solid PVC door shutters Toilet door using 19 Gauge 19mm MS square tubes for styles and outer frames. 15mm MS square tubes for top, lock and bottom rails. The steel tubes shall be covered with 5mm thick solid PVC sheets. Shutter using 5mm thick solid PVC sheets for panelling shall rigidly fixed in position including necessary furniture and fittings. The over all size of styles shall be 50mm x 30mm. The over all size of top rail, Lock rail and bottom rail shall be 75mm x 30mm. The over all size of frames shall be 50mm x 45mm, with suitable rebate for housing the shutter.
Door Frame: Supplying and fixing first quality teak wood frames for doors, windows, ventilators and other similar joinery works with the following sizes and sections including labour charges for wrought and put up in position and also for fixing hold fast in frames and masonry etc. complete in all floors.
Teak wood Scantings up to 2M
Teak wood Scantings over 2M and below 3M
Supply & Fixing of Single Leaf Solid core Flush shutters with Teak ply on both side with teak wook lipping alround 35 mm thick, with necessary adhesives and CP screws complying with standard specification.The cost is inclusive of 1 No Lock arrangement, handel, tower bolt ,approved equivalent make SS ball bearing hinges of quivalent make of aproved make, 2 no floor mounted SS door stoper ect.complete as per drawing.
Supply & Fixing of 35mm thk.Double leaf high density interior grade marine plywood shutters pasted both sides 1.5mm thk.laminate approved design with 35x12mm T.W.lipping on all edges with necessary adhesives and CP screws complying with standard specification.The cost is inclusive of 1 no Lock arrangemen,handel,tower bolt ,approved equivalent make SS ball bearing hinges of quivalent make of aproved make,2 no floor mounted SS door stoper ect.complete as per drawing. Make:Kutty,Sharon,Trojan. Accessories Make:Dorma, Godrej.
Providing and fixing welded M.S. grills to the window openings,along the details as per drawing with necessary screws, bolts and fixed with necessary M.S. lugs embedded in masonry with C.C. 1:2:4 and finishing the surface neatly. Rate shall welding and consumables, etc. complete, as directed. Design of grills and the size of members to be used shall be got approval before put into use & as directed by the Engineer-in-charge.
Manufacturing, Supplying and Fixing of Stainless Steel Hand rails for staircase using 50mm dia 304L Grade Stainless Steel pipe of 1.60mm thick at required locations to a height of 900mm from finished floor level welded to 38mm dia Stainless Steel pipe post of 1.00mm thick as vertical at 900mm centre with 2 Nos. of 25mm dia intermediate horizontal stainless steel pipe of 1.60mm thick in between. The vertical pipe has to be welded to the 100 X 100 X 6mm MS base plate encased in the base concrete. The rate is inclusive of all materils, Labour charges for cutting, bending, welding, grinding, polishing, Transportation, electrical charges, etc. complete with all respects complying with relevant standard specification, as directed by the Engineer-in-charge.
Supply and fixing by using the Glass partition of required size with 12mm thick approved quality, including necessary screws and nails labour charges etc., complete complying with standard specification and as directed by the departmental officers.
Supplying and fixing in position of Gyp board false ceiling made with 10mm thick Gyp board and standard size GI channels at a spacing of not more than 1200mm c/c, on longitudinal directions and 600mm c/c on lateral directions with necessary fasteners for fixing the frames. The Gyp board sheet shall be fixed in the frames with necessary star screws and to be used for joining the frames. The rate is including cost and conveyance of all materials complying with standard specification.
Painting new iron works such as steel doors, windows, ventilators, window bars, balustrades etc., with two coats of best approved first quality and colour of synthetic enamel paint over the existing red oxide priming coat in all floors including cost of priming coat etc., complete complying with standard specification. ( The make quality and colour of paint should be got approved by the executive Engineer before use on works.)
Painting new wood work with two finishing coats of synthetic enamel ready mixed paint of approved quality and colour over one coat priming coat in all floors including the cost of primer etc., complete complying with standard specification. (The make, quality and colour of paint should be got approved by the Executive Engineer before use on works.)
Supplying and painting the walls with two coats of oil bound distemper over one coat of water based cement primer including cost for distemper, primer, cleaning and scrapping the walls, rendering the walls smooth with necessary putty, brushes, scaffolding arrangements, labour charges, etc., as per standard specification. (The colour and shade of the distemper shall be got approved by the Executive Engineer before use of work).
Providing and applying Emulsion paint finish of approved make & shade in two coats over a coat of approved primer and 2 coats of patty to give an even shade as per manufacturer's instruction to the internal plastered surfaces including preparation of surfaces, scaffolding etc. all complete as per drawings and specification for all heights.
Painting two coats of newly plastered wall surface with weather proof ready mixed Exterior Emulsion paint of first class quality and of approved colour over a priming coat including thorough scrapping, clean removal of dirt, and including necessary plaster of paris putty, wherever required etc., complete complying with standard specification.
PLUMBING WORKS:-EWC:- Supplying and fixing in position white / colour glazed European Water Closet of best quality and approved make with 100 mm "P" or "S" trap connecting with CI pipe of 100mm dia / PVC pipe of 110mm dia, double flapped rigid PVC black seat and seat cover with CP brass hinges including cost of white cement, cement for packing, spun yarn, teak wood plugs, brass screws, etc., including supplying and fixing 10 litres capacity PVC / 12.5 litres capacity porcelin low level flushing tank with a pair of CI brackets, etc., complete with all fittings such as 15mm brass ball valve with polythene float with brass handle, union, coupling connected by means of 40mm white PVC flush hand using Indian adopter joint including all internal fittingssuch as 15mm brass connections, 15mm GM wheel valve, 15mm brass nipple (2 Nos.), 15mm nylon connection, TW plugs, screws and also giving necessary connection to the PVC pipe including cost of 600mm length of 110mm dia PVC pipe and painting the CI brackets with 2 coats of approved paint over one coat of red oxide primer, dismantling the masonry and re-doing the dismantled masonry to original condition etc. complete complying with standard specifications. (The EWC and flushing tank wiht all accessories should be got approved by the Executive Enginer before use on works)
Supplying and fixing of 15mm CP two way bib cock with health faucet of parryware or equivalent make conforming to BIS specification and quality including cost of shellac, thread etc., complete complying with standard specification and including cutting and threading wherever necessary.
WASH BASIN:- Supplying and fixing in position best quality and approved make Indian made white / colour glazed earthernware wash hand basin of size 550 x 400mm (with pedestal / without pedestal) with a pair of cast iron brackets, including cost 15mm dia brass CP pillar tap, 32mm dia "B" class GI waste pipe with rubber plug and chain, 15mm dia GM wheel valve, 15mm brass nipple, 15mm dia nylone connection, 32mm dia CP brass waste coupling including fixing of wash basin using CI brackets on to the wall in position with TW plugs and screws, rubber washers, white lead and giving necessary water supply connection and painting the brackets with two coat of painting over a priming coat of anti-corrosive paint including testing for leakages etc., complete complying with standard specification and as directed by the departmental officers. (The wash hand basin and specials should be got approved by the Executive Engineer before use on works).
Supplying and fixing in position Indian make bevelled edge mirror of approved quality and brand PVC / Fibre Glass framed 600 x 450 x 5.5mm thick mirror, shelf type with hard board backing of approved colour fixed with brass screws, rawl plug, etc., complete complying with standard specification. (The mirror should be got approved by the Executive Engineer before use on woks).
Over head Shower: Supplying & Fixing in postion of CP Shower Rose with CP Stop cock arrangements of size 15mm inlet 100mm outlet to the pipe line with necessary cutting, threading and jointing using shellac Etc.,Complete complying with standard specification and as directed by departmental officer. ( The CP Shower rose should be got approved by the Executive engineer before use on Works
Supplying & fixing of Angle valve stopcock with connecting hose and wall flange. (Make: Parryware or equivalent)
Supplying and fixing approved best quality brass CP towel rail 600mm long and 20mm dia with brackets of same materials including cost of teak wood plugs and CP screws, etc.,complete complying with standard specifications. (The tower rail should be got approved by Executive Engineer before use on works).
Supply & fixing C.P soap tray of approved quality (Parryware or equivalent) including cost and conveyance complying with standard specification.
Supplying & fixing of Long body Bibcock with brackets including fixing over Wall tile dado complete.(Make: Parryware or equivalent)
PART - B SOIL AND WASTE PIPES Supplying and fixing in position best quality PVC soil / waste pipes of various dia having 6 kg / sq.cm. pressure BIS mark and providing leak proof joints using PVC adhesives including fixing to the wall with special PVC / MS clamp, teak wood plugs, brass screws, etc., and making connection to all sanitary fittings, dismantling masonry / RCC works wherever found necessary and making the good dismantled portion to the original condition,including testing for any leakages,etc.,complete complying with standard specifications.(The PVC pipes should be got approved by the Executive Engineer before use on works). The rate for earth work excavation will be measured and paid separately in the cases where the pipe lines are proposed to laid below Stilt level.
40mm dia
50mm dia
75mm dia
110mm dia
Supplying and fixing in position cost iron Nahini / Floor trap with Stainless steel grating / PVC nahini / Floor Trap with PVC Grating type of size 100 x 75 / 75 x 50 mm with best quality gratings of approved brand fixed over a bed of brick jelly lime concrete 1;2;5 (One lime two sand and five aggregate ) brick jelly 40mm and finishing with cm 1;3(One cement and three sand) including dismantling masonary wherever found necessary and making good to the original condition and giving connections to the cast iron pipe etc, complete complying with standard specififcation and as directed by the departmental Officers.
RAIN WATER PIPE:- Supply and fixing in position best quality PVC IS 4985 - CLASS-II - 4 Kg/Sqcm -Rain water pipes of various size having ISI mark and providing leak proof joints with such as Bend, Tee Junction, door etc.,of approved qualityincluding fixing to the wall with special PVC /MS clamps, etc., and making connection to all sanitary fittings, wherever necessary and making chipping good to the original condition, complying with standard specification etc.,complete.
110mm dia
Supplying and fixing in position of the following dia PVC rain water gratings for rain water pipes ,of approved quality and variety of various size confirming to ISS and including necessary cutting and fixing and giving connection to PVC pipes etc., complete complying with standard specification and as directed by the Departmental Officer.
100mm dia
Supplying and fixing in position of the following dia PVC specials such as PVC vent Cowl etc.,of approved quality and variety of various size confirming to ISS amend providing leak proof joint etc., including necessary cutting and fixing and giving connection to PVC pipes etc., complete complying with standard specification and as directed by the Departmental Officer.
110mm dia
PART-C EXTERNAL DRAINAGE Supplying and fixing in position best quality PVC soil / waste pipes of various dia having 6 kg / sq.cm. pressure BIS mark and providing leak proof joints using PVC adhesives including fixing to the wall with special PVC / MS clamp, teak wood plugs, brass screws, etc., and making connection to all sanitary fittings, dismantling masonry / RCC works wherever found necessary and making the good dismantled portion to the original condition, including testing for any leakages, etc., complete complying with standard specifications. (The PVC pipes should be got approved by the Executive Engineer before use on works). The rate for earth work excavation will be measured and paid separately in the cases where the pipe lines are proposed to laid below ground level
75mm dia
110mm dia
160mm dia
GULLY TRAP:- Supplying and fixing in position 150 x 100mm "P" or "S" stoneware gully trap 'A' grade with CI double gratings of size 150 x 150mm and 230 x 230mm at bottom and top respectively with necessary earth work excavation laid over a bed of brick jelly cement concrete 1:3:6 (One cement, Three sand and Six broken brick jelly) 150mm thick using 40mm size broken brick jelly including necessary brick work and plastering including dismantling masonry wherever necessary and re-doing the damaged portions to the original conditions using cement concrete 1:3:6 using 20mm stone jelly for fixing the gully trap and giving connections to stoneware sewer line etc., complete complying with standard specifications. [Earth work excavation, brick work, plastering shall be measured and paid separately]. The stoneware gully trap should be got approved by the Executive Engineer before use on works.
Construction of INSPECTION CHAMBER following clear sizes including earth work excavation, CC 1:5:10 of 10 cm thick and brick work in Cement Mortar 1:5 [One cement and Five sand] using best quality of second class Table Mould Bricks of size 9" x 43/8" x 23/4" with Plastering with Cement Mortar 1:3 [One Cement and Three Plastering Sand] 12 mm thick to inner and outer sides and wearing coat 1:3:6 [One Cement, Three crushed stone sand and Six Aggregate] 15 cm thick and covered with precast slab 5 cm thick etc., complete complying as directed by the departmental officers as per standard specification.
INTER CONCEALED WORK:- Providing, supplying & laying of Chlorinated Poly Vinyl Chloride (CPVC-SDR-11) Pipes conforming to IS 15778 having thermal stability with brass and CPVC fittings like Elbow, Brass Tee, Brass Elbow, Offsets, Tee with clamps @1.00 meters spacing, with jointing of pipes with one step CPVC solvent cement with including cutting of chase including testing of the joints complete and making good the walls etc. Rate is inclusive of all material labour, transportation, tools & tackles taxes, etc all complete as per as per specifications, Exposed work including chase cutting, bracket fixing)complete complying with standard specification and as directed by the Departmental Officer.
20mm dia
25mm dia
32mm dia
PART F.EXTERNAL PLUMBING WORKS Providing, supplying & laying of Unplasticized Polyvinyl Chloride (UPVC-SDR-11) Pipes conforming to IS 15778 having thermal stability cold water with brass and UPVC fittings like Elbow,Brass Tee, Brass Elbow,Offsets,Tee with clamps @1.00 meters spacing, with jointing of pipes with one step UPVC solvent cement with including cutting of chase including testing of the joints complete and making good the walls etc.Rate is inclusive of all material labour, transportation,tools & tackles all complete as per as per specifications,Concealed work including chase cutting) complete complying with standard specification and as directed by the Departmental Officer.
32mm dia
40mm dia
50mm dia
Providing, supplying & laying of Gunmetal type NRV - pressure rating less tahn 16 Kg/Sqcm and IS778 with 2 Nos of MTA with jointing material like shellac, thread including testing of the joints complete and making good the walls etc. Rate is inclusive of all material labour, transportation, tools & tackles taxes, levies VAT etc all complete as per as per specifications, complete complying with standard specification and as directed by the Departmental Officer
32mm dia
40mm dia
50mm dia
Supplying and erection of horizontal shaft centrifugal mono block power pump set of single phase 2.00 H.P of best approved quality and make with ISI mark on suitable pedastal with foundation bolt and nut including labour supplying and fixing of starter and main switch suitable for 2.00 H.P pumpset on suitable angle iron frame work with necessary labour including panel board, supply and run off 4 of 10 Sq,mm, in P V C pipe with 14 SWG TC wire including fixing of suction pipe and foot valve up to a maximum depth of 7m and delivery pipes upto the exterior wall of pump room etc., complete and operating the pumps on trial run for 3 days. (The make and quality of pump set to be got approved by the Executive Engineer before use on works.)
BOREWELL:- Drilling of bore wells in alluvial soil or sedimentary strata of clay and sand or sand stone, shale, pebbles, boulders etc., by first taking a pilot bore of 150 mm dia and then enlarging to the required dia by direct or reverse rotary mud circulation method including charges for all T&P, cost of fuel, labour charges, bentonite mud and water required for drilling at the site shown by the departmental officers including construction of mud pit etc., complete.
Upto 60 m Depth ending below ground level
From 60 m to 90 m Depth ending below ground level
Reaming 150mm dia Pilot bore to 300mm dia bore as directed by the departmental officers upto required depth
Upto 60 m Depth ending below ground level
From 60 m to 90 m Depth ending below ground level
Supplying, and fixing the following size of PVC pipes of approved quality and variety conforming to pressure IS 4985. The rate is inclusive of cost of pipe, all taxes, conveyance charges of materials and all other labour charges for fixing the PVC pipe as directed by the departmental officers etc., complete complying with standard specifications. The PVC pipe should be got approved by the departmental officers before use on work and Labour Charges for insering PVC casing pipe assembly (with slots and without slots) in the drilled holes including jointing the pipes with PVC couplers with PVC adhesive etc., complete and supplying and packing annular space with pebbles of size and quality as approved by the Departmental Officers.
150mm dia PVC Casing Pipe (With or without Slot)
Charges for developing Borewell with air compressor of 600 CFM capacity (Min 8 Hours) including transportation and labour and fuel charges for the compressor as directed by the departmental officers and conducting yeild test by 'V' notch methods, excluding cost of bore charges and conveyance charges for handling boring
Supply, errection and giving necessary water supply and electrical connections of new type 2 HP submersible pumpset confiming to IS-14220 with ISI mark suitable for 150mm borewell, complete complying with standard specification including suitable 3-phase panel board with DOL with two level guard starter and accessories and Labour charges for the erection of submersible pump set in bore well including fixing and jointing the submersible cable ( but excluding cost of 2.50sqmm - 3core copper cable)with proper clamps upto othe starter to the required depth, valves section clamps, pressure gauges upto the exterior wall of the panel board consisting of JPICN switch starter, voltammeter, ammeter, 3 pilot (indicating) lamps, capacitor, single phasing preventor, water level guard and laying and jointing the cables and twin earthing as per I.E. rules etc. complete and testing pump sets on trial run for 3 days etc., complete complying with standard specifications. with Three phase panel board
Suppling and fixing PVC bore well end cap of size 165/168mm dia etc., complete complying with standard specifications as directed by departmental officers
Supply of 4.00 Sq.mm / PVC insulated and sheathed, 3 core flat type copper cable for submersible motor complete complying with standard specifications as directed by departmental officers
Supply and fixing the Nylon Rope to connect the Submersible motor in borewell etc., complete complying with standard specifications as directed by departmental officers
ELECTRICAL WORK:-WIRING Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (5 points / Coil) Higher End )
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End
Wiring with 2 x1.5 sq.mm. PVC insulated single core unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with PVC accessories with suitable Module GI switch box in flush with wall with 1 No 6A one way module switch and 1 No 6A 3/2 pin module socket with module front plate with continuous Earth wire connection of 1.5 sq.mm copper wire and making good of the concealed portion with painting of suitable colour for concEaled PVC pipe Plug point ( 8 points / Coil) Higher End
LIGTHT FIXTURES Supply and fixing of 4' 20W LED fitting with LED on wall or ceiling with PVC unshEathed copper lEads from terminals to the fitting (Higher end)
Supply and fixing of 4' 20W LED fitting with LED on conduit pipe suspension from the ceiling with PVC unshEathed copper lEads from terminals to the fitting (Higher end)
Supply and fixing of Water tight BulkhEad fitting with Guard suitable with 9W/7W LED Bulb
supply and fixing of 24W LED 2x2 square type surface/ Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unshEathed copper lEads from terminals to the fitting.
Supply and fixing of 12V 6W Indoor LED strip (for cove lighting)of 5 mtr. Length with LED driver 12V 60W with necessary connector with connection complete.
supply and fixing of 18W LED square type Surfcace/Recessed fitting with LED (Higher end) on false Ceiling with suitable hanging support from ceiling with PVC unshEathed copper lEads from terminals to the fitting
Supply and fixing of LED food lamp concEaled in wall with connection Complete
Supply and fixing of 20W LED Mirror light fitting on wall or ceiling with PVC unshEathed copper lEads from terminals to the fitting (Higher end)
Supply and fixing of 60W LED High Bay fitting on ceiling with suitable clamp with connection complete
supply and fixing of 48W LED street light fitting with LED (Higher end) with 32mm dia. GI pipe (class B) with 1 No32 mm GI bend complete on the existing post/ on wall with PVC unshEathed copper lEads with MS clamps and with painting .
FANS Supply and fixing of 1200mm (48") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 600 mm fan down rod on exisitng fan clamp
Supply and fixing of 1400mm (56") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 600 mm fan down rod on exisitng fan clamp
Supply and fixing of 300mm (12") sweep (Heavy duty) AC exhaust fan complete without provision of hole in the wall
Supply and fixing of louvers shutters arrangements for 300mm (12") sweep (light duty) AC exhaust fan
Supply and fixing of 250mm sweep modular AC exhaust fan complete without provision of hole in the wall
supply and fixing of 450mm wall mounting fan with suitable clamp on wall with connection
Supply and fixing of 375mm (15") sweep (HEavy duty) AC exhaust fan complete without provision of hole in the wall
Supply and fixing of louvers shutters arrangements for 375mm (15") sweep (light duty) AC exhaust fan
Supply and fixing of 1No.6A two module 5 pin socket , 1 No. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 2Nos6A two module 5 pin socket , 2 Nos 6A one module switch with module cover plate (plastic) on suitable module concEaled Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 3Nos6A two module 5 pin socket , 3 Nos 6A one module switch with module cover plate (plastic) on suitable module concEaled Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 1 No6/16A two module socket , 1 No 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 1 no.6/16A two module socket , 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 1 No6/16A two module socket with module cover plate (plastic) on suitable module concEaled Box (GI ) in flush with wall with connections.(for Geycers) Higher End
Supply and fixing of 1 No 16A one module switch with module cover plate (plastic) on suitable module concEaled Box (GI ) in flush with wall with connections. (for Geycers)Higher End
Supply and fixing of 1500W automatic electric water hEater of 25 litres capacity suitable for 230V 50 c/s AC supply on suitable MS clamps with 3 core flex wire but without plumbing connection
Supply and fixing of 20 Amps 3 modular Key card switch -Electronic with suitable GI concEaled box and front plate in flush with wall with connection
supply and fixing of 2 nos.9A 2Ploe contactor, 1 no. timet switch, 2 nos.6A 2P MCB housed in suitable polycarbonate control box with necessary wiring etc. on wall with connection (Based on room key tag function )
Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unshEathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous Earth wire connection of 2.5 sq.mm copper wire and making good of the concEaled portion
Supply and Run of 2 of 2.5 sq.mm. PVC insulated SC unshEathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with continuous Earth wire connection of 2.5 sq.mm copper wire with painting of suitable colour
Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe concEaled in wall and ceiling with continuous Earth wire connection of 4 sq.mm copper wire and making good of the concealed portion with suitable colour
Supply and run of 2 of 4 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous Earth wire connection of 4 sq.mm copper wire with painting of suitable colour
Supply and run of 4 of 4sq.mm. PVC insulated SC unshEathed FRLS copper conductor of 100V grade in suitable PVC rigid pipe concEaled in wall and ceiling with continuous Earth wire connection of 4sq.mm coppe rwire and making good of the concEaled portion with suitable colour
Supply and run of 4 of 6 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous Earth wire connection of 6 sq.mm copper wire with painting of suitable colour
Supply and run of 4 of 6sq.mm. PVC insulated SC unshEathed FRLS copper conductor of 100V grade in suitable PVC rigid pipe concEaled in wall and ceiling with continuous Earth wire connection of 6sq.mm coppe rwire and making good of the concEaled portion with suitable colour
Supply and Run of 4 of 10 sq.mm. PVC insulated SC unshEathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe concEaled in wall and ceiling with continuous Earth wire connection of 10 sq.mm copper wire and making good of the concEaled position.(SD 358)
Supply and Run of 4 of 10 sq.mm. PVC insulated SC unshEathed FRLS copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with continuous Earth wire connection of 10 sq.mm copper wire and painting of suitable colour
Supply and Run of 25mm PVC rigid pipe concealed in wall and ceiling and making good of the concEaled position.(for future LAN and TV Line
Supply and Run of 25mm PVC rigid pipe on wall and ceiling and painting of suitable colour (for future LAN and TV Line
Supply and Run of 20mm PVC rigid pipe concealed in wall and ceiling and making good of the concEaled position.(for future LAN and TV Line
Supply and Run of 20mm PVC rigid pipe on wall and ceiling and painting of suitable colour (for future LAN and TV Line
Supply and run of GI Hot Dip/Powder coated 16SWG Cable tray with 300mm width and 50mm height with suitable anchor fastener rod of suitable length from the ceiling with accessories such as bend, Tee etc.
Supply and fixing of 16A DP MCB with sheet steel enclosure in flush wall with Earth connection (Higher end)
Supply and fixing of 100A 4P MCB with sheet steel enclosure housed in sitable IP66 SMC box with AI frame support with earth connection (Higher end) (for 14HP outdoor AC unit)
Supply and fixing of 32A DP MCB with sheet steel enclosure in flush wall with Earth connection (Higher end)
Supply and fixing of 32A 4P MCB with sheet steel enclosure in flush wall with Earth connection (Higher end)
Supply and fixing of 125A 4P MCB with sheet steel enclosure housed in suitable SMC box with AI support with Earth connection (Higher end)( for AC outdoor unit)
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 No 25A 30 mA DP RCCB/ELCB switch as incoming and 6 Nos. 6A to 32A SP MCB as outgoing in flush with wall with Earth connection only. Higher End (Higher end)
Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 No 25A DP RCCB /ELCB switch as incoming and 10 Nos 6A to 32A SP MCB as outgoing in flush with wall with Earth connection only. Higher End
Supply and fixing of 7 segment 6 way TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one No 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one No 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 4 ways in Each segment) and seperate provision for MCB / Isolators ( totally 12 Nos) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. with the following on wall with Earth connection only. (Data A 27) i.63A TPN MCB - 1 No ii. 40A RCBO 100 mA - 3 Nos iii. 16A DP MCB - 9 Nos
Supply and fixing of 7 segment 4 way TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one no. 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one no. 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 4 ways in each segment) and seperate provision for MCB / Isolators ( totally 12 nos.) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. with the following on wall with earth connection only. i.63A TPN MCB - 1 no. ii. 40A DP RCBO - 3 nos. iii.20A DP MCB -6 nos.
Supply and fixing of 7 segment 6 way TPN MCB sheet steel distribution board (Higher end) with metal / acrylic door cover flush type /surface type fitted with busbars and neutral links with single / three phase MCB outgoings and seperate 4 way provision for accomodating one No 4 pole incoming MCB / Isolator and another seperate 4 way provision for accomodating one No 4 pole ELCB / RCD (totally 8 ways in one segment) (3x 4 ways in Each segment) and seperate provision for MCB / Isolators ( totally 12 Nos) for sub incomers in 3 segments with lable holder and provison for taking up cable for size not less than 35 sq.mm. with the following on wall with Earth connection only. i.63A TPN MCB - 1 No ii. 40A DP MCB - 3 Nos iii. 32A DP MCB - 9 Nos
Supply and fixing of 4 way Vertical Triple pole and neutral MCCB sheet steel enclosure distribution board ( with MCCB incomer) with double door (metal door) with 1 no. 100A 4P MCCB switch as incoming and 2 no.32A TP MCB and 6 nos.6to 32A SP MCB as outgoing with suitable cable end box on suitable angle iron frame with earth connection only. Higher End
Supply and fixing of 4 way Vertical Triple pole and neutral MCCB sheet steel enclosure distribution board ( with MCCB incomer) with double door (metal door) with 1 no. 100A 4P MCCB switch as incoming and 2 no.63A TP MCB and 6 nos.6to 32A SP MCB as outgoing with suitable cable end box on suitable angle iron frame with earth connection only. Higher End
Supply and fixing of 8 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 63A 4P MCB as incoming and 3 nos. 32A 3P MCB, 15 nos. 6A to 32A SP MCB as outgoing on wall with earth connection only. Higher End
Supply , Erection Testing and commissioning of 415V/50 HZ 100A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 100A TPN switch disconnector fuse units interior only with HRC fuses double break -1 no.Outgoing 63A TPN switch disconnector fuse units interior only with HRC fuses double break -3nos. (for pump motors)
Supply , Erection Testing and commissioning of 415V/50 HZ 125A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 125A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 63A TPN switch sheet steel double break with HRC fuses -4nos.
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 200A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 100A TPN switch sheet steel double break with HRC fuses -4nos.
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 200A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 125A TPN switch sheet steel double break with HRC fuses -1no 63A TPN switch sheet steel double break with HRC fuses -4nos
Supply , Erection Testing and commissioning of 415V/50 HZ 250A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 250A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 125A TPN switch sheet steel double break with HRC fuses -4nos.
Supply , Erection Testing and commissioning of 415V/50 HZ 315A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 315A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 200A TPN switch sheet steel double break with HRC fuses -3nos.
Supply , Erection Testing and commissioning of 415V/50 HZ 400A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 1 no. Digital function meter, 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 400A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 250A TPN switch sheet steel double break with HRC fuses -3nos. 200A TPN switch sheet steel double break with HRC fuses -1no.
Supply , Erection Testing and commissioning of 415V/50 HZ 100A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete.(Pump Panel) Incoming 315A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 200A TPN switch sheet steel double break with HRC fuses -3nos.Outgoing 63A TPN switch disconnector fuse units interior only with HRC fuses double break -2 nos. 32A TPN switch disconnector fuse units interior only with HRC fuses double break -2 nos. (For External lights)
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases 1 no. Digital multifunction meter on a separate Chamber and with the following switches complete as per Electricity regulation authority 2023 norms. Incoming 315A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 200A TPN switch sheet steel double break with HRC fuses -3nos. Outgoing ( Data -A 37 )00A TPN switch disconnector fuse interior only with HRC fuses double break -2nos. 63A TPN switch disconnector fuse interior only with HRC fuses double break -6nos.(For Lighting Panel)
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 200A TPN switch disconnector fuse interior only with HRC fuses double break -1no. Outgoing 63A TPN switch disconnector fuse interior only with HRC fuses double break -6nos. (For Geycer Panel)
Supply , Erection Testing and commissioning of 415V/50 HZ 250A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 250A TPN switch disconnector fuse interior only with HRC fuses double break -1no. Outgoing 100A TPN switch disconnector fuse interior only with HRC fuses double break -7nos. (For AC Panel)
Supply , Erection Testing and commissioning of 415V/50 HZ 400A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete.Incoming 400A TPN switch disconnector fuse interior only with HRC fuses double break -1no. Outgoing 200A TPN switch disconnector fuse interior only with HRC fuses double break -3nos. 125A TPN switch disconnector fuse interior only with HRC fuses double break -2nos. (For Main Lighting Panel)
Supply , Erection Testing and commissioning of 415V/50 HZ 400A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 400A TPN switch disconnector fuse interior only with HRC fuses double break -1no. Outgoing 250A TPN switch disconnector fuse interior only with HRC fuses double break -2nos. 200A TPN switch disconnector fuse interior only with HRC fuses double break -4nos. (For Main Power Panel)
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete.Incoming 200A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 100A TPN switch disconnector fuse interior only with HRC fuses double brEak -1 no. 63A TPN switch disconnector fuse interior only with HRC fuses double brEak -8Nos
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 200A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 100A TPN switch disconnector fuse interior only with HRC fuses double brEak -1 no.63A TPN switch disconnector fuse interior only with HRC fuses double brEak -4Nos
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete.Incoming 200A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 63A TPN switch disconnector fuse interior only with HRC fuses double brEak -8Nos
Supply , Erection Testing and commissioning of 415V/50 HZ 200A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete.Incoming 200A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 63A TPN switch disconnector fuse interior only with HRC fuses double brEak -4Nos
Supply , Erection Testing and commissioning of 415V/50 HZ 250A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/4 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 250A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 125A TPN switch disconnector fuse interior only with HRC fuses double brEak -6 nos.
Supply , Erection Testing and commissioning of 415V/50 HZ 315A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 315A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 200A TPN switch disconnector fuse interior only with HRC fuses double brEak -4Nos 100A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No.
Supply , Erection Testing and commissioning of 415V/50 HZ 315A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for Earth buses , 3 Nos LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 315A TPN switch disconnector fuse interior only with HRC fuses double brEak -1No Outgoing 125A TPN switch disconnector fuse interior only with HRC fuses double brEak -8 Nos.
Supply , Erection Testing and commissioning of 415V/50 HZ 400A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 1 no. Digital function meter, 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases on a separate Chamber and with the following switches complete. Incoming 400A TPN switch sheet steel double break with HRC fuses -1 no. Outgoing 315A TPN switch sheet steel double break with HRC fuses -2nos 250A TPN switch sheet steel double break with HRC fuses -1n 200A TPN switch sheet steel double break with HRC fuses -4nos
LTCT METER Supply ,Erection ,Testing and commissioning of Three compartment LTCT meter box made up of 16 SWG CRCA sheet steel ( Length 1200mm x Height 1200mm x width 600mm) with door and lock & key arrangements on suitable angle iron frame support for floor / wall mounting support with supply and fixing of the following interior mounting arrangements with busbar chamber, meter chamber and Terminal box chamber confirming to IE rules. i.The busbar chamber will consist of 4 nos. 2” x 1/4” tinned copper flat for phase and neutral busbar on epoxy mounted bus insulated at proper and sufficient spacing between the bus bar as per IE Rules. ii. 3 nos. 200/5A CT coil mounted in Three phase busbar. iii. Interconnection between CT coil to 4 way terminal box and 4 way terminal box to Meter box by 4 sq.mm PVC cu.wire The LTCT meter box should be powder coat paint of approval colour , approved by site officer. Automatic Transfer switch
APFC PANEL Supply and erection of 50 KVAR 415/440Volts 50Hz 3 Ph automatic power factor correction panel, 5 stage, (at 0.95 lag), made up of powder coated, 16 SWG CRCA sheet steel enclosure with 1 1/2" x 1 1 1/2" x 1/2" AI Frame work with RCC concreting foundation and bolted to masonry pedestal with Delta Connected capacitors (BCH/EPCOS) MOO Type operating in multiple stage with 3 current and Voltage Transducers (CVT) at the phases simultaneously to activate the desired power factor switching time between steps 120 seconds, switching off time in case of fault 3 seconds with a LCD display to show the following Parameters. a. Vr – R phase Line Voltage b. Vy – Y phase Line Voltage c. Vb – B phase Line Voltage d. Ir – R phase Line currente. Iy – Y phase line current . Ib – B phase Line Current g. KW – Present Kilo Watts h. RKVA – Present KVAR Demand i. KVA – Present KVA j. PF – Present Power Factor k. Number of Capacitor bank ON/OFF l. Provision to indicate the imbalanced load m.Provision to indicate the change in phase Sequence n. The APFC Panel Should also have built in protection for current imbalance. For high Voltage/Low Voltage cut off, single phase Preventer, provision for inductor coil to cater the in-rush currents, line surges, Current Limiters, Current Sensor, etc., with connection complete and as per the relevant IE Rules. Eight Stages of Automatic Power Factor control panel with necessary connection. Make. (Matrix /L&T /or equivalent
Supply and erection of 100 KVAR 415/440Volts 50Hz 3 Ph automatic power factor correction panel, 8 stage, (at 0.95 lag), made up of powder coated, 16 SWG CRCA sheet steel enclosure with 1 1/2" x 1 1 1/2" x 1/2" AI Frame work with RCC concreting foundation and bolted to masonry pedestal with Delta Connected capacitors (BCH/EPCOS) MOO Type operating in multiple stage with 3 current and Voltage Transducers (CVT) at the phases simultaneously to activate the desired power factor switching time between steps 120 seconds, switching off time in case of fault 3 seconds with a LCD display to show the following Parameters. a. Vr – R phase Line Voltage b. Vy – Y phase Line Voltage c. Vb – B phase Line Voltage d. Ir – R phase Line current e. Iy – Y phase line current f. Ib – B phase Line Current g. KW – Present Kilo Watts h. RKVA – Present KVAR Demand i. KVA – Present KVA j. PF – Present Power Factor k. Number of Capacitor bank ON/OFF l. Provision to indicate the imbalanced load m.Provision to indicate the change in phase Sequence n. The APFC Panel Should also have built in protection for current imbalance. For high Voltage/Low Voltage cut off, single phase Preventer, provision for inductor coil to cater the in-rush currents, line surges, Current Limiters, Current Sensor, etc., with connection complete and as per the relevant IE Rules. Eight Stages of Automatic Power Factor control panel with necessary connection. Make. (Matrix /L&T /or equivalent Automatic Transfer switch
Supply and clamping of 4C x 10 sq.mm PVC armoured LTUG copper cable on post or on wall with clamps )for outdoor AC units
Supply and fixing of brass cable gland suitable for 4C x 10 sq.mm PVC armoured LTUGcopper cable with Earth connection
Supply and providing cable end termination of 4Cx 10 sq.mm. PVC LTUG copper armoured cable with necessarycopper cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 25 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the Earth to make good
Supply and clamping of 3.5C x 25 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 25 sq.mm PVC armoured LTUG aluminium cable with Earth connection
Supply and providing cable end termination of 3-1/2 x 25 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 50 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the earth to make good
Supply and clamping of 3.5C x 50 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 50 sq.mm PVC armoured LTUG aluminium cable with earth connection
Supply and providing cable end termination of 3-1/2 x 50 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 70 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the earth to make good
Supply and clamping of 3.5C x 70 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 70 sq.mm PVC armoured LTUG aluminium cable with earth connection
Supply and providing cable end termination of 3-1/2 x70 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 95 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the Earth to make good
Supply and clamping of 3.5C x 95 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 95 sq.mm PVC armoured LTUG aluminium cable with Earth connection
Supply and providing cable end termination of 3-1/2 x95 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 120 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the Earth to make good
Supply and clamping of 3.5C x 120 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 120 sq.mm PVC armoured LTUG aluminium cable with Earth connection
Supply and providing cable end termination of 3-1/2 x 120 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 150 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the Earth to make good
Supply and clamping of 3.5C x 150 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 150 sq.mm PVC armoured LTUG aluminium cable with Earth connection
Supply and providing cable end termination of 3-1/2 x 150 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 240 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the Earth to make good
Supply and clamping of 3.5C x 240 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and clamping of 3.5C x 240 sq.mm PVC armoured LTUG aluminium cable in suitable GI pipe on post or on wall with clamps cost of 65mm dia GI pipe
Supply and fixing of brass cable gland suitable for 3.5C x 240 sq.mm PVC armoured LTUG aluminium cable with Earth connection
Supply and providing cable end termination of 3-1/2 x 240 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 3.5C x 185 sq.mm PVC armoured LTUG aluminium cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the earth to make good
Supply and clamping of 3.5C x 185 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and fixing of brass cable gland suitable for 3.5C x 185 sq.mm PVC armoured LTUG aluminium cable with earth connection
Supply and providing cable end termination of 3-1/2 x 185 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and laying of 120mm/103.50mm size HDPE pipe in a trench to be excavated at a depth of 0.75m and refilling the earth to make good [for future cable laying]
Design, engineering, supply, erection, testing, commissioning and handling over of the 20 persons capacity (1360 kg) passenger lift, gEarless with machine room as per the following technical specification:
31) Lift license: Preparation of drawings, lift contractor should do payment of charges to CEIG and insurance policies if any and obtaining CEIG safety certificate as per lift act.32) Floor announciator with music: To be provided in the car. 33) Special fEatures: (a) Battery Operated Emergency Light and Alarm Bell (b) Call Register Signal And Vf Door Operator (c) Automatic Rescue Device. (d) Stainless Steel Button with S.S. Cover. (e) Dot Matrix Led D & P Indicators in Car & Landings - Orange Colour. (f) Floor Annunciator with Music. (g) Firemans Switch (h) False Ceiling in Car. (i) Fire Rating of Landing Doors-One Hour (j) Infra Red Door Screen (k) Overload warning Indicator (l) Laminated Mirror At REar Side. (m) Scaffolding (n) Two way Intercom with press & spEak in Cop (o) Provision for EBABX (p) Free Service for One YEar (q) Pit Ladder (r) Ss Handrail (s) Lift License (t) Minor Builders Work (u) Provision for Cctv Camera - Ip (Cat6 Flat Travelling Cable) 34) Over speed governor, phase failure and phase reversal relay, alarm bell, T Guide brackets for car and counter weight, rubber padding under winding unit, motor of adequate capacity, electro magnetic brake with compression spring etc. 35) Guarantee: Gurantee for the materials and lift firm should offer workmanship of equipments complete for a period of not less than one yEar. (SOR) (M-2363 - less cost of 1.00 lakh for one floor) 250 KVA DG SET
Supply, Erection, Testing, Commissioning and Handing over of 1No 250 KVA Diesel Generator set of 0.8 P.F. Three Phase 415/420 Volts, 50 C/S, 1500 RPM CPCB IV+ Norms and BIS specification Approved capacity compressing of Engine BHP/ suitable BHP of water cooled clock wise rotating feed pump with 200KW/250KVA operating capacity brush less alternator close coupled underneath fuel tank standard, safeties, LLOP with stop solenoid, battery with lead, Electric start and vibration fitting & accessories and AMF control panel as detailed below including transporting of unloading changes. (A). ENGINE Water cooled diesel engine suitable for Generator application with a shaft output suitable at 1500 RPM under NTP conditions. The Engine shall comprise the following standard fitting flexible coupling, fly wheel air cleaner ,fan blower, radiator, water pump, fuel pump, fuel filter lubricating oil filter etc.,(B) 12/24 Volt Electronic starting Equipment Complete with starter motor, dynamo, standard batteries with cable, flexible exhaust piping of 50 cms length( C ) ENGINE INSTRUMENT PANEL / MOUNTED Starting push button/ staring key, lubricating oil temperature gauge, lubricating oil pressure gauge, water temperature gauge, safety control for low lubricating oil pressure, safety control for high water temperature, safety control for over speed, hour meter (mechanical) and RPM indicator, battery charging ammeter. The engine should be capable of providing 10% over load for one hour for every 11 hours continuous at full load. (D). Alternator 250 KVA/100 KW capacity of brush less alternator AC, Three phase 50 c/s, 415/420V,0.8PF, 1500 RPM under NTP conditions conforming to IS 13364 (Part – II) 1992 to be means of coupling
Note: 1. The control panel should be complete with necessary fuses, cables, labels, other accessories with neutral isolation arrangements. 2 . The engine should trip for the following a. Low lubricating Oil pressure b. High water temperature (F). FUEL TANK : Fuel tank of 400 liters capacity and with inlet and outlet connections level indicator with scale etc., (G).BASE FRAME : The Base frame should be fabricated MS channel frame of rigidly welded construction for mounting of generator set. The engine and alternator should be coupled by suitably designed diaphragm type flexible coupling with guard and mounted on the base frame with proper alignment. The supply of generator set includes loading.(H). ACOUSTIC ENCLOSURE The Acoustic enclosure be free standing floor mounting type with modular construction with the provision to assemble and dismantle easily and designed to suit all weather conditions. Erection of Acoustic enclosure suitable for 250 KVA Diesel generator complete with all accessories as above with required concreting and suitable supports etc., (i) Supply of manuals for operation & maintenance of DG set with warranty card etc.,125 KVA DG SET
Supply, Erection, Testing, Commissioning and Handing over of 1No 125 KVA Diesel Generator set of 0.8 P.F. Three Phase 415/420 Volts, 50 C/S, 1500 RPM CPCB IV+ Norms and BIS specification Approved capacity compressing of Engine BHP/ suitable BHP of water cooled clock wise rotating feed pump with 100KW/125KVA operating capacity brush less alternator close coupled undernEath fuel tank standard, safeties, LLOP with stop solenoid, battery with lEad, Electric start and vibration fitting & accessories and AMF control panel as detailed below including transporting of unloading changes.(A). ENGINE Water cooled diesel engine suitable for Generator application with a shaft output suitable at 1500 RPM under NTP conditions. The Engine shall comprise the following standard fitting flexible coupling, fly wheel air clEaner ,fan blower, radiator, water pump, fuel pump, fuel filter lubricating oil filter etc.,(B) 12/24 Volt Electronic starting Equipment Complete with starter motor, dynamo, standard batteries with cable, flexible exhaust piping of 50 cms length ( C ) ENGINE INSTRUMENT PANEL / MOUNTED Starting push button/ staring key, lubricating oil temperature gauge, lubricating oil pressure gauge, water temperature gauge, safety control for low lubricating oil pressure, safety control for high water temperature, safety control for over speed, hour meter (mechanical) and RPM indicator, battery charging ammeter. The engine should be capable of providing 10% over load for one hour for every 11 hours continuous at full load.(D). Alternator 125 KVA/100 KW capacity of brush less alternator AC, Three phase 50 c/s, 415/420V,0.8PF, 1500 RPM under NTP conditions conforming to IS 13364 (Part – II) 1992 to be mEans of coupling (E). AMF Control Panel : The AMF control panel (Cubicle) should be fabricated with vermin proof and dust proof best quality sheet steel and floor mounted with removable rEar panels and hinged front doors with enamel painted and incorporating the following with suitable provision for connecting incoming and outgoing lEads having been made on the control panel.
(G).BASE FRAME : The Base frame should be fabricated MS channel frame of rigidly welded construction for mounting of generator set. The engine and alternator should be coupled by suitably designed diaphragm type flexible coupling with guard and mounted on the base frame with proper alignment. The supply of generator set includes loading.(H). ACOUSTIC ENCLOSURE The Acoustic enclosure be free standing floor mounting type with modular construction with the provision to assemble and dismantle Easily and designed to suit all weather conditions. Erection of Acoustic enclosure suitable for 125 KVA Diesel generator complete with all accessories as above with required concreting and suitable supports etc., (i) Supply of manuals for operation & maintenance of DG set with warranty card etc.,
Construction of RCC foundation of size suitable for 125 KVA DG set with cement concert 1:2:4 with sand cushion all around the foundation for the erection of 125 KVA DG set with proper alignment as per site Engineer instruction
Supply and Run of 12 core 2.5 sqmm armoured copper control cable FRLS in suitable PVC rigid pipe on wall/Ground/ ceiling with connection (For AMF to 125KVA Genset)
Supply and installation of exhaust piping of sufficient length with suitable MS pipes so as to extend outside the generator room with necessary thermal insulation, (M-2085)
Charges for filling of diesel for test and initial run of Generator
Earthing as per the ISI specification with an Earth electrode of 2.10 metre Class 'B' GI pipe of dia not less than40mm with copper Earth plate of size 125mm x 50mm x 6mm with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry (SD 221)
Supply and Run of 1 of No8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for Earth Connection (SD 372)
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps/supports on wall/floor/ground for Earth connection. (SD 76)
Cable Tray Supply and installation of sheet steel 2.5mm /2mm thick consisting 2 nos. side rail s with runs at every 250mm interval and complete with associated accessories such as coupler plates , Tees , long bend, elbows etc.Hot Dip Galvanized 65 microns tthick cable tray of size 150mm width and 50mm Height and 10mm threated GI rod supports upto 450mm with cable tray and they supports should be at 1.5m interval and grouting the supports in wall/ ceiling / floor as per the requirment External Electrification
Supply and erection of hot dip GI Double arm octagonal poles of 7 Mt length and necessary GI pipe bent and luminaire with MCB control and cable entry exit (complete including all civil work for foundation etc) with supply and fixing of 2 Nos 150W LED Street light as per specification with RCC civil foundation and U bolts & Nuts
Supply and Laying of 4C x 10 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the Earth to make good.
Supply and clamping of 4C x 10 sq.mm PVC armoured LTUG aluminium cable on post or on wall with clamps
Supply and clamping of 4C x 10 sq.mm PVC armoured LTUG aluminium cable in suitable on post or on wall with clamps (SD 198+ cost of GI pipe )
Supply and fixing of brass cable gland suitable for 4C x 10 sq.mm PVC armoured LTUG aluminium cable with Earth connection
Supply and providing cable end termination of 4C x 10 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
Supply and fixing of 3ftx4ftx1.5ft Outdoor street light fabricated box with fixing 63A Main switch, Analog Timer, 4P 100A Contactor and fixing of Three phase Vertical type 8 way 63A distribution board with Industrial Protection cover Code IP54 Protection , with 63A 4 pole MCB as incoming and 3 Nos 32A TP MCB and 9 Nos 6-32A SPMCB as Outgoing on Wall with Earth connection only. The MCB DB and MCB’s should be with ISI mark. The Indoor box arrangement should be erected on suitable MS channel arrangement. Copper flat used as Earth bus and it should be fixed at side of the lower portion with suitable number of Earth bolts. The box should be painted with powder coated enamel paint and necessary Earth connection.
Design, Supply, erection, Testing, Commissioning and handing over of 12 metre Mini Mast Structure (Bajaj / Philips / Crompton make or equivalent) with required number of continuously tapered hot dip galvansied steel polygonal side sections with telescopic strip joints to a total of 12 meters capable of sustaining the maximum wind pressure at the erection site with single flange base mast section with vertically movEable hot dip galvanised lantern carriage and accessories such as electrical junction box brackets for providing 6 Nos of 150W LED flood light luminaries with control gEar box complete hEad frame assembly, pulley drive stainless steel wire rope single / double drum self-lubricating winch arrangements suitable for raising and lowering the luminaries carraige ring flexible multi core power cable and necessary high tensile hot dipped galvanized foundation, bolt & nuts along with washers and templates including supply and fixing the following accessories in the Mast design and casting of suitable foundation with 1:2:4 mix RCC concrEate with 30cm projection above the ground level with 1 Mt width x 1Mt length x 2 Mts depth with necessary galvanised foundation bolts nuts and washers and dump plates enclosing the bolts nuts for high mast cosidering the safe soil bEaring capacity at site-1 Set b) High powered power tool with complete with hand held control panel and motor with push button type remote control switch suitable for 3 phase 415 V /50 HZ for raising and lowering of the lantern carriage complete to operate all fittings mounted in the base to couple with winch-1 Set c) Feeder pillar box comprising of 0.90m x 0.45m x1.20m floor angle iron frame with 63 A power contactor starter for the 3 Phase motor-1Set d) Neon aviation obstruction light (Bajaj/equivalent) - 1No e)2Nos of special GI Earth electode with copper plate 300 x300x3mm and copper flat (1"x1 1/4")inter connection as per ISS complete with Earth connections-1Set f) Hot dip galvanised lighting arrester- 1 No
Air conditioning EquipmentVARIABLE REFRIGERANT FLOW SYSTEM Supply of VARIABLE REFRIGERANT FLOW SYSTEM of below mentioned capacities comprising of DC INVERTER & Scroll Compressor and complete with the following
OUTDOOR UNITS 22 HP
Supply and Installation of 18G Copper Piping finished with polyshield coating with Necessary fittings, Y Joints and headers. (This includes the pressure testing and Refrigerant Gas charging ) between indoor & outdoor units as per specifications . All piping inside the room shall be properly supported with hanger and all external piping
Supply and Installation of 18G Copper Piping finished with polyshield coating with Necessary fittings, Y Joints and hEaders. (This includes the pressure testing and Refrigerant Gas charging ) between indoor & outdoor units as per specifications . All piping inside the room shall be properly supported with hanger and all external piping
1 1/8 Copper Pipe (18 G)
7/8 Copper Pipe (18 G)
3/4 Copper Pipe (18 G)
5/8 Copper Pipe (18 G)
1/2 Copper Pipe (18 G)
3/8 Copper Pipe (18 G)
Supply and Laying of the 5/8 and 3/8 Soft Copper pipe for Indoor to Main Copper Pipe
The copper pipe to be insulated with 19mm thick for suction 13mm thick for liquid (Quotation)
Supply and installation of PVC drain piping with Suitable Sleeve and white tape (Quotation)
Supply, laying of Control wiring between indoor units and outdoor units with PVC Conduits (Quote)
Supply and filling of R-410A Refrigerant gas
Nittrogen Pressure Testing, Vaccumsing & commissioning of the entier VRF Outdoor Units
Labour work charges for Lifting VRF outdoor units to the specific locations with Load Man Support with Suitable Equipment (Quotation)
Equipment VARIABLE REFRIGERANT FLOW SYSTEM Supply of VARIABLE REFRIGERANT FLOW SYSTEM of below mentioned capacities comprising of DC INVERTER Indoor Units and complete with the following
INDOOR UNITS 2.02 TR Hi Wall Split Unit
Supply and fixing of Refnet joint
Installation of VRF Outdoor Units
Installation of Indoor units
Nittrogen Pressure Testing, Vaccumsing & commissioning of the Indoor Unit
Renewal by Supply and fixing of 50mm thick anti vibrating rubber pads
Supply,Fabrication and fixing of Masonry Concrete Pedestal suitable for Mounting the VRF Outdoor Units with the Size of 3Meter x 1.5Meterx 0.3 meter
Core cutting for Copper pipe lying between Indoor to outdoor with Drain pipe 4 x 4 Inch Size (Quotation) HT Supply arrangments
TNEB HT Cable Supply and laying of 11KV 3 core 300 sq.mm XLPE HT UG cable in a trench to be excavated at 1.0 Mtr. and covering the cables completely with RCC. Truff and refilling the earth to make good. (EB HT Point to RMG)
Supply and providing cable end termination suitable for 11KV 3 core 240 sq.mm XLPE HTUG cable with necessary outdoor type heat / cold shrinkable joint kit and accessories (Make : Ray Chem. / M Seal) (For RMG - 1 No, EB HT Point-1 No)
RMG Unit Supply, Erection, testing and commissioning of 11KV 25 KA 630Amps 3 Panel HT INDOOR RING MAIN GEAR Switch board suitable for indoor installation comprising two incomer panels with Air Break/ load Breaks switches and one outgoing panel with Vacuum Circuit Breaker complete as per specification with Mechanical inter lock between incomers 1. Supply and Erection of draw out type 11KV 25 KA 630 Amps Horizontal draw out./Horizontal Isolation VACCUM CIRCUIT BREAKER fitted with motor ( 230 V AC) operated spring charged Mechanism, with ON and Off mechanical indicator Anti pumping Device, 110V DC shunt trip and closing coils ( DC source of supply to be derived from a power pack suitable for three Tripping and two closing operations incorporated on Incoming panel only) Mechanical Operation counter, 4 No + NC spare Aux contact with contact multiplication contractor for customer use. Automatic safety shitter, Mechanical close/Trip Knob, Mechanical ON/OFF Indication, operating Handle, 230V AC to 110V DC power pack operating handle 2. Supply and Erection of 11KV 630 Amps 25 KA HT Air Break/Load Break switch with mechanically inter locked each switch, front operated spring assisted manual closing mechanism 2NO + 2NC Aux. contact
8. Phase Indication Lamps R,Y,B(Incomings 3Nos) 9. Control Wiring 10. 800Amps Copper Bus bar PVC Sleeved and required panel copper earthing. 11. Control switch TNC (Incoming-1 No, Outgoing -1No) 12.Trip Circuit healthy Push Button(Incoming-1 No, Outgoing -1No) 13. Common for Switch gear, MCB's for AC DC Control, Heater ON/OFF Switch with space Heater and thermostat Single phase switch socket, cubicle illumination lamp, Disconnecting type terminal Block.etc., 14. MS Sheet enclosure for Indoor Installations Powder.
Supply,Erection,Testing and commissioning of 11KV/433/800KVA oil cooled distribution transformer complete with first fill of Oil , all components and accessories as per technical specification - IS 1180 – I including minor civiworks
Supply and laying of 11KV 3 core 185 sq.mm XLPE HT UG cable in a trench to be excavated at 1.0 Mtr. and covering the cables completely with RCC. Truff and refilling the earth to make good. (RMG to HT TP, HT TP to 800KVA T/F)
Supply and providing cable end termination suitable for 11KV 3 core 185 sq.mm XLPE HTUG cable with necessary Indoor type heat / cold shrinkable joint kit and accessories (Make : Ray Chem. / M Seal) (RMG- 1no, HT TP - 2 nos, 800KVA T/F - 1 No)
Supply, erection ,testing and commissioning of 1600A capacity vermin dust proof cubical of 14SWG line quality MS sheet steel enclosures for accommodating the 1600A TPN Aluminium busbar and rising main of 3” x 1/2” Aluminium busbar 3 phases 2runs and neutral 1 run earth bus bar Aluminium of 1” x 1/4” and with provision for accommodating incomer ACB, Transformer and adaptor boxes including copper inter connect to the stretch of HT Room
Supply and fixing of flexible Aluminium termination to connect bus duct to transformer and to connect bus duct to MV panel (Quotation)
MV PANEL Design ,Supply, erection, Testing and commissioning of 1600A draw out type floor mounted MV cubical panel board with bus bar chamber dust and vermin proof and Accommodating the following d sine with microprocessor based 1 Nos 1600A ACB as incomer units with the following items of work complete to staisfy the latest IE rules and CEIg guidelines. supply and fixing of suitable busbar chamber made up f 16SWG mS sheet steel (1.6mm) with 4Nos. 2runs 3" x 1/2" Aluminium bus bar for 3 phases and neutral (1 x 75mm x 12mm) and 2Nos of earthing bus of size 1" x 1/4 Aluminium bus (25mm x 3mm) in suitable bus bar insulator (Epoxy insulator) with maximum creep age distance an supportd on MS base channel frame work of size 4' x 2" x 1/4" - 1 set . Incoming: 1) supply and Fixing of 1 No. 1600A basic rating 4 pole 433V LT ACB confirming to IS 13947 - 2 IEC 60947 - 2 with suitable capacity and breaking capacity of 50 KA AC with all accessories for standard horizontal manual draw out type ACB equipped with auxillary contacts and all accessories for closing and opening operation ith Micro processor based SR 18 G relay, Over Current trip device adjustable to LTD,STd and release for overcurrent protection Uv release with time delay,EF release short Circuit protection,Mains CTs for 3 phases protection safty acccessories as per CEIg ,IE rules inforce with hinter connection and terminations as required in specification . Outgoing : 1) Supply and Fixing of 800A 4P, 50 KA Microprocessor based EDB ACB -2 Nos. 2) Supply and Fixing of 400A SDF with HRC fuses - 4 Nos 3)Supply and Fixing of 250A SDF with HRC fuses - 3 Nos
Inter connecting the all LT ACB's and MCCb's to bus bar with suitable insulated tinned Aluminium flats and painting/PVC sleeve colour coding ofphases and neutral indication .double earth connection o the SDF's and ACb's to earth bus usinf suitable tinned Aluminium flats by 2 runs of 1" x 1/4" suply and Fixing of led lamp arrangements with toggle switch to th control to each phases and with rigid connection in suitable seperate compartments withg in the cubical by CEIg rules with ,2 sets of supply and fluhmounting L&T or equivalent make - Model ER300N. supply and Fixing of danger board with siemens grey powder caoting with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc., erection of panel board complete with suitable fountation bolts and nuts including suitable M.channel,concreting,testiung and commissioning (L&T/ C&S/ SIEMENS/ABB)
Supply ,fixing and of 1 No.400A ATS in suitable Sheet steel enclosure on suitable AI frame work with necessary interconnection copper flat with earth Connection.
NON -ESSENTIAL PANEL Supply and fixing of 800A capacity dust and proof cubical panel board of CRCA 16 SWG sheet for outer body and stiffness and doors switches supports respectively and with supply and fixing of the following cubical mounting switches with centre bus bar chamber and vertical covers, and cable chamber on both side of the buss bar chamber at the extreme ends on both side and confirming in Electricity regulation 2023 norms.
Supply , Erection Testing and commissioning of 415V/50 HZ 400A Cubicle Panel board with centre switches Chamber the bus bar chamber and cable chamber on extreme end with 16 SWG thick CRCA sheet with 1”x 1/2 ” copper flats for 3 phases and neutral with 6mm hylem sheet separation of 3 phases and neutral and with synthetic moulded insulators bus supports at equal intervals as per IS specification and 2 runs of 1”x 1/8” copper flat on either side of the panel board for earth buses , 3 nos. LED pilot lamps set withfuse base, top & 10A HRC Fuse link for 3 phases with Digital Multifunction meter on a separate Chamber and with the following switches complete as per Electricity regulation authority 2023 norms. Incoming 400A TPN switch disconnector fuse interior only with HRC fuses double break -1 no Outgoing .200A TPN switch disconnector fuse interior only with HRC fuses double break -5 nos.100A TPN switch disconnector fuse interior only with HRC fuses double break -2 nos.
Earthing Materials Supply and Laying of copper - the following sizes including bolt Nuts Washers,etc.,
Supply and Laying of 50 x 6 mm Copper Flat
Supply and Laying of 25 x 3 mm Copper Flat
Supply and Laying of 8 Gauge Copper Wire in pvc pipe with suitable clamp.
Supply and installation of 17.2mm dia 2 mtr. Low carbon steel earth electrode bonded with 250 microns copper with GI clampto be installed in a suitable bore and filled with 50 lbs of cabon bond environment friently back filling compound . An RCC troughed of size 300 x 300 mm should be with RCC cover for protecting the electrode
Earthing as per the ISI specification with an earth electrode of 2.10 metre Class 'B' GI pipe of dia not less than 40mm with copper earth plate of size 125mm x 50mm x 6mm with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry
Towards safety accessories, measuring instruments and tools. Safety Accessories for 11 KV-substation First Aid Box-3 Nos, 4 Fire Bucket with stand -8 Set. Rubber Mat 1m X 2m - 24 Nos. Fire Extinguisher-DCP- 5 Kg’s - 8 Nos. Hand Gloves in glass frame- 2 Nos. (2 pair) First Aid Chart Tamil and English - 8 Nos. Earth Discharge Rod-1 No Danger Stricker -50Nos.
Preparation of Electrical schematic diagram, site plans, physical layout 5 copies and payment of CEIG fees submission of completion report, rectification report, obtaining drawing approval, safety certification etc., complete including lamination copy fixed at HT sub station.
CCTV arrangments Supply and installation of 4MP IP Bullet /Dome camera with key fEatures of not less than 2.8/4/6mm fixed lens, resolution 2560 x 1920 @15 fps , 25-30 mts length range
Supply and installation of 4MP IP Bullet /Dome camera with key features of not less than 2.8/4/6mm fixed lens, resolution 2560 x 1920 @15 fps , 25-30 mts length range
Supply and Installation of 32 channel Network Video recorder with 2 sata , (2 Nos Hard disc) recording minimum 720P resolution in full HD , Hard disc support 4TB, USB, HDMI should be available with all accessories
Supply and Installation of 4TB built in Hard Disc drive
supply and installation of 43 inches LED monitor with full HD with following fEatures. Resolution 1920 x 1080, HDMI , audio in, built in spEaker , 24/7 operation.
supply and installation of 43 inches LED monitor with full HD with following features. Resolution 1920 x 1080, HDMI , audio in, built in speaker , 24/7 operation.
Supply and run of CAT 6 cable in existing concEaled PVC pipe including termination work.
Supply and installation of 8 Port PoE switch for CCTV IP camera
Supply and installation of 24 Port PoE switch for CCTV IP camera (Higher end)
Charges for Testing and commissioning (34 camera x Rs.500 per camera) LAN Arrangement
Supply and installation of RJ 45 i/o socket with module box and phase plate. Combo D-RJ45 CAT6E Lan I/O Network Keystone Jack, Gang Box, Single Port Face PlateType: 1x Keystone Jack + 1x Gang Box + 1x Single Socket Face Plate Suitable for : CAT6 / CAT6E (Higer end)
Supply and installation of 8 port 10/100/1000 Mbps fully managed layer -2 switch with 1G uplink,24 x 10/100/1000 BASE-T ports Fanless design for silent operation Innovative Green energy saving features Complete web interface for comprehensive switch management. (Higher end)
Supply and installation of 24 port 10/100/1000 Mbps fully managed layer -2 switch with 1G uplink,24 x 10/100/1000 BASE-T ports Fanless design for silent operation Innovative Green energy saving fEatures Complete web interface for comprehensive switch management. (Higher end)
Supply and installation of 24 port patch panel -fully loaded. 6 patch panels are six port RJ45 modules applied and suitable for 22-26 AWG stranded and solid wire, compatible with both 110 & Krone punch down tools. patch panels have improved Cable Management with optional Cable Management bar terminating 4 pairs UTP cable. (Higher end)
Supply and installation of 4U wall rack with power sockets, cable manager with 0.6 KVA UPS all accessories. (Higher end)
Supply and installation of 6U wall rack with power sockets, cable manager with 0.6 KVPS all accessories. (Higher end)
Supply and installation of 4U wall rack with power sockets, cable manager with 0.6 KVA UPS all accessories. (Higher end)
Supply and installation of 6U wall rack with power sockets, cable manager with 0.6 KVA UPS all accessories. (Higher end)
Supply and installation of 1 Mt patch cord. (Higher end)
Supply and laying of CAT 6 cable in exisitng PVC pipe. (Higher end)
Supply and laying of RG11 TV cable in exisitng PVC pipe. (Higher end)
Supply and Installation of Caller ID Telephone with SpEaker
Sub Total
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.36 MB
bookled1.pdf
Tender Documents • 1.22 MB
bookled2.pdf
Tender Documents • 1.36 MB
IDUMBANKUDILdrawing.pdf
Additional Documents • 0.96 MB
KADAMBANILLAMdrawing.pdf
Additional Documents • 0.82 MB
KANDANILLAMdrawing.pdf
Additional Documents • 0.62 MB
BOQ_774930.xls
BOQ • 0.61 MB
Download all tender documents and submit your bid