| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.8 LAccepted-AOC | L1 | Accepted-AOC Found lowest and reasonable | |
| 2 | L2₹51.7 L+₹1.3 L (2.52%)Rejected-Finance | L2 | Rejected-Finance In order but L2 | |
| 3 | L3₹67.6 L+₹17.1 L (33.9%)Rejected-Finance | L3 | Rejected-Finance In order but L3 | |
| 4 | L4₹89.0 L+₹38.5 L (76.3%)Rejected-Finance | L4 | Rejected-Finance In order but L4 | |
| 5 | Rejected-Technical 14 INDUSTRIAL AREA TILAK NAGAR NEW DELHI BEHIND SUBASH NAGAR METRO STATION WEST DELHI DELHI 110018 | WEST DELHI | DELHI | 110018 | - | Rejected-Technical Being un-enlisted contractor not uploaded requisite documents as per NIT nor hard copy received in this office. |
Tender Value
Refer Docs
EMD Value
₹98,000
Closing Date
3 Apr 2023, 6:00 pmClosed
GE(U) E/M Meerut
Roorkee road Meerut Cantt
REPAIR/ MAINT OF LT PANEL, LT SWITCH GEARS AND ALLIED WORKS IN SOUTH AREA AND BHAGAT LINE AREA UNDER AGE E/M ELECT SUPPLY AT GE (U) E/M MEERUT CANTT
2023_MES_583405_1
8485/E8
Open Tender
Electrical and Maintenance Works
Works
180 days
Meerut
Please refer Tender documents.
11 documents required · 11 mandatory
₹500
GE(U) E/M Meerut
₹98,000
Yes
18 Apr 2023
28 Feb 2023
5 Apr 2023
28 Feb 2023
3 Apr 2023
14 Mar 2023
Amount
Excavation in trenches in soft/loose soil n. exc. 1.5 meter wide and n. exc. 1.5 meter depth and getting out, including trimming the sides and forming bottom surface to required levels for fixing pole/ stay assembly and laying cables etc, complete all as specified and directed.
Returning, filling in trenches including spreading, levelling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed.
Removing of excavated material (soil) to a distance n. exc. 50 Mtr and dispositing where directed at a level n. exc. 1.50 Mtr above the starting point complete as directed.
M & L Sand cushioning in trenches to UG cables (8cm deep before laying of cable and 15 cm deep over the cable) complete all as specified and directed. Note :- Punned thickness only will be considered for payment.
M & L Bricks for protection cover to under ground cable (with old size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other complete all as specified and directed.
Supply & Laying jointing, testing and commissioning in replacement of LT XLPE, PVC insulated, PVC sheathed armoured LT 1100 volt grades heavy duty with aluminium stranded conductor through pipes, induct, on poles, in trenches etc including taking out of cable complete of following sizes
240 Sqmm, 3.5 core.
185 Sqmm, 3.5 core.
150 Sqmm, 3.5 core.
Supply & fixing or laying galvanised steel tubing medium grade (ISI marked) for protection of under ground cable on poles/ walls under road crossing etc of following sizes including dismantling and taking down existing pipe.
80mm bore
150mm bore
M&L for auguring of hole suitable for passing 40mm to 100mm bore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road including HDPE pipe 150mm dia suitable for 0.4 MPA working pressure complete all as specified.
M&L for taking down of old existing rusted LT panel board/feedr pillar by removing connected cables etc from site complete all as specified and directed by Engr-in-Charge.
Supplying, installing, commissioing and testing of LT switch gear panel board of size 1650mmx2200mmx600mm (min) , IP-54 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) , having busbar chamber for and including 1008 Amps insulated Aluminium bus bars , 4 pole , cubical type, factory made out of 3.15mm thick CRCA sheet structure mounted on Platform (as per Sketch), rigid mild steel angle iron frame of 50mmx50mmx5mm with 750mm long extended legs grouting in PCC platform and plateform bottom area bounded with single brick work & filled with sand from which cables enter into panel bottom, duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front and back openable doors with proper locking arrangements for dust and vermin proof with two earthigs of 600x600x6mm thick GI Plate by using 32x6mm strip, 10 watt LED light with holder in panel upper side with ,complete including suitable size cable allay, lugs , cable glands and making connections , wiring with suitable size SC PVC insulated copper conductor cable and proper copper conductor wiring for Neutral CT with every outgoing MCCB , l65mm size lock with keys comprising of the followings and specified hereafter:- (NOTE:- (i) Panel board shall be manufactured from CPRI approved firm and of apporved make & LT Panel board shall be as per IS/ICE 61439-part I&II Type Test certificates. Contractor shall submit all Certificates before executing the job. (ii) Contractor shall got the apporaval of make and drawings of panel from GE before execution.
FP EDO ACB With MP Based O/C, S/C & E/F Protection LSIG Release 6.0E ,4 pole,800Amps 415V, 50 kA, 50 Hz , Model NW08H14PEDO6.0E,Icu 50ka Frame -1, -01 No.(incoming) , Make: Siemens,scheinder,ABB
CT for Metering Cl-1.0 Resin Cast, 800/5A,15VA - 03 No. And for CT Shorting Link - 03 No
SP Control MCB C-Curve 6A,10KA - 03 No & Neutral Link - 01 No
Phase Indication lamp-R/Y/B 230 VAC with holder panel mounting type complete all as specified. -01 Set of three
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 400Amps, 415V, 36 kA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 400 Amps,Model - LV540630 , -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 320Amps, 415V, 36 KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 400 Amps,Model - LV540630, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 160Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 100 Amps,Model - LV516610, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 100Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 100 Amps,Model - LV510619, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 63 Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 63 Amps,Model - LV510619, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
Drawings of LT panel shall be got approved from GE before placing order for procuring.
Supplying, installing, commissioing and testing of LT switchgear panel board of size 1650mmx2275mmx800mm (min) , IP-54 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) , having busbar chamber for and including 1280 Amps insulated Aluminium bus bars or (100x10 and 100x6mm) main busbar, 4 pole , cubical type, factory made out of 3.15mm thick CRCA sheet structure mounted on Platform (as per Sketch), rigid mild steel angle iron frame of 50mmx50mmx5mm with 750mm long extended legs grouting in PCC platform And plateform bottom area bounded with single brick work & filled with sand from which cables enter into panel bottom, duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front and back openable doors with proper locking arrangements for dust and vermin proof with two earthigs of 600x600x6mm thick GI Plate by using 32x6mm strip, 10 watt LED light with holder in panel upper side with ,complete including suitable size cable allay, lugs , cable glands and making connections , wiring with suitable size SC PVC insulated copper conductor cable and proper copper conductor wiring for Neutral CT with every outgoing MCCB, l65mm size lock with keys comprising of the followings and specified hereafter:- (NOTE:- (i) Panel board shall be manufactured from CPRI approved firm and of apporved make & LT Panel board shall be as per IS/ICE 61439-part I&II Type Test certificates. Contractor shall submit all Certificates before executing the job. (ii) Contractor shall got the apporaval of make and drawings of panel from GE before execution.
(B) Outgoing :- (i) FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 400Amps, 415V, 36 kA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 400 Amps,Model - LV540630 of scheinder, -01Nos. (ii) FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 320Amps, 415V, 36 KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 400 Amps, Model - LV540630 of scheinder, -01Nos. (iii) FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 250Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 250 Amps,Model - LV525630 of scheinder, -01Nos. (iv) FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 200Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 200 Amps,Model - LV525630 of scheinder, -01Nos. (v) FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 63 Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 63 Amps,Model - LV510619 of scheinder, -01Nos. Make of All MCCB:- Siemens,scheinder,ABB
Supplying, installing, commissioing and testing of LT switchgear panel board of size 1600mmx2000mmx600mm (min) , IP-54 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) , having busbar chamber for and including 640 Amps insulated Aluminium bus bars , 4 pole , cubical type, factory made out of 3.15mm thick CRCA sheet structure mounted on Platform (as per Sketch), rigid mild steel angle iron frame of 50mmx50mmx5mm with 750mm long extended legs grouting in PCC platform And plateform bottom area bounded with single brick work & filled with sand from which cables enter into panel bottom, duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front and back openable doors with proper locking arrangements for dust and vermin proof with two earthigs of 600x600x6mm thick GI plate by using 32x6mm strip, 10 watt LED light with holder in panel upper side with, complete including suitable size cable allay, lugs, cable glands and making connections, wiring with suitable size SC PVC insulated copper conductor cable and proper copper conductor wiring for Neutral CT with every outgoing MCCB, l65mm size lock with keys comprising of the followings and specified hereafter:- (NOTE:- (i) Panel board shall be manufactured from CPRI approved firm and of apporved make & LT Panel board shall be as per IS/ICE 61439-part I&II Type Test certificates. Contractor shall submit all Certificates before executing the job. (ii) Contractor shall got the apporaval of make and drawings of panel from GE before execution.
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 400Amps, 415V, 36 kA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 400 Amps,Model - LV540630 , -01Nos.(outgoing) Make: Siemens,scheinder,ABB
CT for Metering Cl-1.0 Resin Cast, 400/5A,15VA - 03 No. And for CT Shorting Link - 03 No
SP Control MCB C-Curve 6A,10KA - 03 No & Neutral Link - 01 No
Phase Indication lamp-R/Y/B 230 VAC with holder panel mounting type complete all as specified. -01 Set of three
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 250Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 250 Amps,Model - LV525630, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 160Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 100 Amps,Model - LV516610, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 100Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 100 Amps,Model - LV510619, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
FP MCCB with built-in LSIG Electronic trip unit ETS 6, 4 pole, 63 Amps, 415V, 25KA (Ics=100%Icu), 50 Hz with Microprocessor based with Neutral CT 63 Amps,Model - LV510619, -01Nos.(outgoing) Make: Siemens,scheinder,ABB
Taking down of old/unserviceable MCCB by removing connected cables etc from LT Panel board/feeder pillar complete including supply and fix MCCB, 4 pole, 50 Hz, 36/25 KA rupturing capacity (Microprocessor based) all as specified and directed by Engr-in-Charge for following capacity Make of MCCB : Siemens,scheinder,ABB, Legrand
FP MCCB 630A,36KA with built-in LSIG Electronic trip unit ETS 6
FP MCCB 400A,36KA with built-in LSIG Electronic trip unit ETS 6
FP MCCB 250A,25KA with built-in LSIG Electronic trip unit ETS 6
FP MCCB 200A,25KA with built-in LSIG Electronic trip unit ETS 6
FP MCCB 160A,16KA with built-in LSIG Electronic trip unit ETS 6
FP MCCB 100A,16KA with built-in LSIG Electronic trip unit ETS 6
FP MCCB 63A,16KA with built-in LSIG Electronic trip unit ETS 6
S&F LED type indicator ( R,Y,B) complete assembly with holder suitable for 220V, 50 Hz,including taking down of existing complete all as specified.
Supply & Fixing in replacement of aluminium thimble size 25 Sqmm to 50 Sqmm complete all as specified.
Supply & Fixing in replacement of aluminium thimble size 70 Sqmm to 120 Sqmm complete all as specified.
Supply & Fixing in replacement of aluminium thimble size 150 Sqmm to 185 Sqmm complete all as specified.
Supply & Fixing in replacement of aluminium thimble size 240 Sqmm to 400 Sqmm complete all as specified.
Cutting of wornout / burnt aluminium cable terminal lugs from the HT/LT cable, crimping of new aluminium cable core and fixing with transformer, Panel MCCB terminal stud including cutting/ dressing of cable,disconnecting under ground cable from over head conductor , cutting down wornout portion under ground cables of any type and size for repairs including taking out under ground cable loop from ground and making connections of restoration of electric supply complete all as specified. Note:- Excavation, earth work , taking out cable protection covers, and sand cushion and relaying the same shall be deemed included in the unit rate quoted by Contractor
Supplying and fixing STRAIGHT THROUGH cable jointing Kit in repair for 1100 V grade XLPE cable for complete with jointing material (heat shrink type) and accessories suitable for 70 sqmm to 150 sqmm 3.5 core XLPE armoured aluminium conductor cable and testing aftre jointing complete all as specified and directed.
Supplying and fixing STRAIGHT THROUGH cable jointing Kit in repair for 1100 V grade XLPE cable for complete with jointing material (heat shrink type) and accessories suitable for 185 sqmm to 240 sqmm 3.5 core XLPE armoured aluminium conductor cable and testing aftre jointing complete all as specified and directed.
S&F Side pole mounting bracket in repair suitable for 8 LED flood lights made of MC-75 with three arms (Note: bracket upper and middle arm should be Minimum 1.2 RM In length and lower arm shouid be minimum 0.8 RM in length) fixed with proper clamps,Nut bolt and washers with two coats of synthetic enamelled paint over one coat of red oxide Zinc chrome primer, complete all as specified.
S&F LED Flood light 250 watt 230 V AC outdoor type made up of die cast aluminium body with thermal management in multiple optics and equipped with IP 66 protection, with impact and corrosion resistant and must have 4 KV internal and 10 KV external surge protection complete with driver and LED, including taking down of old fitting complete all as specified and directed. Make:- Crompton, Philips, Eveready
Supply, laying & testing in repair PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 4 sq mm ,4 core, 1100 Volts grade
Ramesh Traders Govt Contractors & General OrderSuppliers
Microsys Controls India
janta tradrers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .