| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹74.6 LAccepted-AOC | L1 | Accepted-AOC Being a lowest bid | |
| 2 | L2₹89.0 L+₹14.4 L (19.3%)Rejected-Finance | L2 | Rejected-Finance Not a lowest bidder | |
| 3 | L3₹1.2 Cr+₹44.9 L (60.2%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | L3 | Rejected-Finance Not a lowest bidder | |
| 4 | L4₹1.3 Cr+₹57.6 L (77.2%)Rejected-Finance MANEGAON CHAMPANAGAR KHAMARIA JABALPUR 482005 MP | JABALPUR | JABALPUR | MP | 482005 | L4 | Rejected-Finance Not a lowest bidder | |
| 5 | L5₹1.3 Cr+₹58.6 L (78.6%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | L5 | Rejected-Finance Not a lowest bidder |
Tender Value
₹93.7 L
EMD Value
₹1.7 L
Closing Date
10 Feb 2024, 6:00 pmClosed
CWE (AF) Gwalior
CWE (AF) Gwalior 474020
Provision of Retrofitting Emission control device in DG sets at AF Stn Gwalior
2023_MES_619457_2
85061
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF Stn Gwalior
As per tender documents
8 documents required · 8 mandatory
₹1,000
GE (AF) Tech Area Gwalior
₹1.7 L
Yes
14 Mar 2024
11 Jan 2024
12 Feb 2024
11 Jan 2024
10 Feb 2024
20 Jan 2024
Amount
Design, Supply, installation, testing & commissioning of Retrofit Emission Control device for each 125 kVA DG set conforming to the following specifications complete all as specified and as directed. (make : Kirloskar, Engine No.4h7906/1721502, Model No.4K1080TAG2), Installation date : 27.12.2018 i) The retrofit device shall confirm to the latest norms specified by CPCB. ii) The efficiency of the device to reduce particulate Matter shall be minimum 70%. iii) The device shall have the characterstic of high heat resistance, good thermal conductivity, low exhaust resistance, high filtration efficiency, strong pressure resistance, good cold start performance, low ignition temperatures and high conversion efficiency. iv) Working technology - ESP (Electrostatic Precipitator), Wet Scrubbing, Diesel Oxides Catalyst. (v) The RECD shall be of No manual cleaning, No choking, low maintenance, No filter replacement, No chemical or solvent usage. (vi) Durability period fitted on the DG set engines shall be 4000 running hours or 06 Years whichever is earlier.(A certificate in this regard shall be obtained from the OEM) (vii) The RECD shall be of class I, which is intended to control particulate matter emissions only and which does not increase the direct NO2 emissions. (viii) RECD shall be equipped with a monitoring device that detects incorrect operation or removal of the RECD and that triggers an audible and/or visual alarm to the operator. For reagent based particulate reduction RECD the monitoring device may interrupt the input of any reagent or additive, if necessary. The warning system can be based for example on the continuous measurement of the engine exhaust back-pressure as an example.
Item no. 1.00 contd... (ix) RECD shall not lead to an increase of the DG set’s noise emissions. RECD is intended only to be fitted in addition to the original equipment manufacturers’ standard production silencer system on a DG set. (x) Carbon Monoxide, Hydrocarbon reduction efficiency (Min) 70% for all DG sets. (xi) The RECD shall be accompanied by the following information :- (a) The manufacturer’s name or trademark. (b) The make and identifying part number of the RECD as recorded in the information document issued in accordance with the model set out. (c) The RECD family including year of manufacture, for which the RECD is approved, including, where applicable, a marking to identify if the RECD is suitable for fitting to an engine & family that is equipped with an on-board diagnostic (OBD) system. (d) The instruction manual for the retrofit installation; (e) The end-user service manual including maintenance instructions. (f) The contractor shall carryout pollution test as mentioned above before installation of RECD and after installation of RECD to compare the results.
Item no. 1.00 contd... Certification :- (A) Device should be ‘Type Approved’ as per the System and Procedure of Central Pollution Control Board for Emission Compliance Testing of Retro-fit Emission Control Devices (RECD). For Diesel Power Generating Set Engines, Dated 01/02/2022, wide Pollution Control Series PCLS/12/2021-22. Adhering to this, RECD to be ‘Type Tested’ for an equivalent kVA family as per the System and Procedure from any one of the four Central Pollution Control Board, Govt of India, recognized/approved test agencies/laboratories as given below: (a) Automotive Research Association of India (ARAI, Pune) (b) International Centre for Automotive Testing (ICAT, Manesar) (c) Indian Institute of Petroleum (IIP, Dehradun) (d) Vehicle Research Development Establishment (VRDE, Ahmednagar) Note: 1. Necessary foundation for fixing of RECD as recommended by the OEM is deemed to be included in the quoted rate. 2. The Contractor has to get approved the Make, Technology and Drawings by the GE before commencement of the work. 3. The contractor has to submit the documents all as specified in the PS. 4. Necessary pipes, fittings and fixtures for the installation of RECD is deemed to be included in the quoted rate.
Item no. 1.00 contd... General Technical Requirements (GTR) / Commissioning :- a) Retrofit emission Control device shall be complete with safety precautions to ensure no damage should be done to the DG set operations under any circumstances. The Emission Control retrofit device should be closely coupled with the DG exhaust to ensure 100% of the exhaust passes through the Emission Control retrofit device. b) Anti-Vibration mountings shall be provided for complete Emission Control retrofit device in case of flexible coupling with the diesel generator exhaust. c) Emission Control retrofit device should have protection against under voltage, over voltage, under frequency, over frequency, low battery voltage, over current, earth-fault, short circuit, phase sequence change, etc. d) The Emission Control retrofit device shall be with corrosion resistive and HR paint. e) The Contractor shall provide the trial run (Testing) of retrofit Emission Control device alongwith trial run with the available electrical load at site. The trial run shall be for TWO hours. The electrical loading shall not be more than the rated capacity of the DG set. f) Exhaust piping, extra civil work, distribution board as per the OEM recommendations is deemed to be included in the quoted rate.
All as per Item No 1.00 here-in-before but of Cummins make (a) Engine No.84373685 & Model No.6BTAA5-9-G13, Installation date-30.10.2017
All as per Item No 1.00 here-in-before but of Cummins make (a) Engine No.84388653 & Model No.6BTAA3-9-G13, Installation date-04.06.2018
All as per Item No 1.00 here-in-before but of Cummins make (a) Engine No.84402515 & Model No.6BTAA3-9-G3, Installation date-04.06.2018,
All as per Item No 1.00 here-in-before but 320 kVA capacity of Kirloskar make (a) Engine No.6KL12TASR1 & Model No.KI6.5001/0600102, Installation date-20.10.2011,
All as per Item No 1.00 here-in-before but 320 kVA capacity of Sterling make (a) Engine No.TAD1351GE-2013487101 & Model No.SGV320, Installation date-24.03.2015,
All as per Item No 1.00 here-in-before but 160 kVA capacity of Cummins make (a) Engine No.P84344T60 & Model No.F63205/0600084, Installation date-04.04.2018,
All as per Item No 1.00 here-in-before but 380 kVA capacity of Cummins make (a) Engine No.25316618 & Model No.NTA-14-G3, Installation date-27.07.2007,
All as per Item No 1.00 here-in-before but 250 kVA capacity of Cummins make (a) Engine No.84508429 & Model No.6CTAA-83-GA, Installation date-30.10.2017,
All as per Item No 1.00 here-in-before but 200 kVA capacity of Greaves Cotton make (a) Engine No.338062203501 & Model No.GP1011-PH11:200kVA+6GIIT+STAM+W/OCP, Installation date-11.08.2022,
All as per Item No 1.00 here-in-before but 200 kVA capacity of Kirloskar make (a) Engine No.F6862512220051 & Model No.65L1500DAG, Installation date-13.05.2022,
All as per Item No 1.00 here-in-before but 400 kVA capacity of Kirloskar make (a) Engine No.KU8-5001/07000-33 & Model No.KG400WS349, Installation date-27.07.2010,
All as per Item No 1.00 here-in-before but 500 kVA capacity of Cummins make (a) Engine No.25346416 & Model No.KTA-19-99, Installation date-24.03.2010,
All as per Item No 1.00 here-in-before but 500 kVA capacity of Kirloskar make (a) Engine No.133M10J114581 & Model No.DV1002/1000180, Installation date-27.11.2011,
N K BUILDERS
Vijaypower Generators Limited
ASHOKA ASSOCIATES
POONAM ELECTRIC INDUSTRY
M/s Kohli Builders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .