Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.0 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹20.9 L+₹1.1 L (5.41%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹21.6 L+₹1.8 L (9.22%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹24.4 L+₹4.6 L (23.4%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | L5₹24.5 L+₹4.7 L (23.5%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
4 Jul 2023, 6:00 pmClosed
Major S K Yadav
GE(S) BATHINDA BATHINDA MIL STN
GE(S) BTD TOKEN NO 14 OF 2023-24 REPAIR REPLACEMENT OF INTERNAL UNSERVICEABLE POINT/ REWIRING FITTING FIXTURES DBS SUB MAIN WIRING SWITCHES AND CONNECTED ACCESSORIES WORK IN JADUNATH ENCLAVE AND ABDUL HAMID ENCLAVE UNDER AGE EM IV UNDER GARRISON EN
2023_MES_601379_1
GE(S)/BTD/TOKEN NO 14 OF 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GES(S)Bathinda
Class D
category a(i)
11 documents required · 11 mandatory
₹500
GE(S)Bathinda
₹70,000
Yes
12 Jul 2023
6 Jun 2023
7 Jul 2023
6 Jun 2023
4 Jul 2023
20 Jun 2023
Amount
Taking down carefully existing copper/Aluminum point wiring (light,fan, socket or power) complete including fixture and fittings such as switches, bellpushes, ceiling roses, pendents, regulators, sockets, light fitting, callbells etc removiing materials to store for keeping in safe custody or for taking credit(credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc. to match existing, etc, complete all as specified and as directed.
Dismentaling & taking down of existing unsv light fittings/fixtures for replacement etc. complete all as specified and as directed.
Dismentaling & taking down of existing unsv call bell for replacement etc. complete all as specified and as directed.
Dismentaling & taking down of existing unsv batten/angle holder for replacement etc, complete all as specified and as directed.
M & L for Point wiring with multi-stranded copper conductor, single core, PVC insulated and unsheathed cable, including PVC insulated unsheathed multistranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, GI terminal boxes, modular frame & cover plate (suitable for modular switch/sockets) comprising the following: -
One light point controlled by one switch or one fan point controlled by one switch & fan regulator etc. with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit complete all as specified and as directed.
One Socket outlet three pin, 6 Amp, on the same board, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, complete all as specified and as directed.
One Socket outlet three pin, 6 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit complete all as specified and as directed.
One Bell/Buzzer point controlled by one push button with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit complete all as specified & as directed.
One light point controlled by two two way switch. with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit complete all as specified and as directed.
One socket outlet three pin, 5/15 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit complete all as specified and as directed.
Note for serial item No 5.00 to 5.06: 1. Switch(es) & socket(s) shall be measured & paid for separately under respective item of BOQ 2. GI boxes shall be fixed flush in position with cement mortar (1:4) complete all as directed.
S&F Switch modular type single pole, one way, 6 Amp, one module, etc. complete all as specified and as directed.
S&F Switch modular type single pole one way, 16 Amp, one module, complete all as specified and as directed.
S&F Switch modular type single pole, two way, 6 Amp, one module, etc, complete all as specified and as directed.
S&F Bell push switch modular type single pole one way, 6 Amp, one module, etc. complete all as specified and as directed.
S&F Socket outlet modular type, multipurpose, 2/3 pin, single pole one way, 6 Amp, two module, etc, complete all as specified and as directed.
S&F Socket outlet modular type multipurpose 2/3 pin single pole one way 6/16 Amp, two module, etc, complete all as specified as directed.
S&F Fan regulator, modular type, 5 step, high speed, two module etc. complete all as specified and as directed.
S&F Ceiling rose, 3 terminal PVC/polycarbonate, suitable for 230 V, AC, 50 Hz supply.etc, complete all as specified and directed.
S&F call bell ding dong type AC 230 V etc, complete all as specified and as directed.
S&F wall mounted extruded Aluminium/polycarbonate integrated LED batten fixture with tube 1.2 m, 20watt, 1.2 m 6500K, efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor and integrated inbuilt driver complete complete including making connection complete all as specified and as directed.
S&F wall mounted extruded Aluminium/polycarbonate integrated LED batten fixture with tube 1.2 m, 25watt, 1.2 m 6500K, efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, PC diffusor and integrated inbuilt driver complete complete including making connection complete all as specified and as directed.
S&F decorative wall light fixture made of polycarbonate suitable for retrofit 9W LED lamp(base B-22) complete with PC diffusor & including one 9W LED lamp(base B-22), 6500K, not less than 90 lumen/watt efficacy including making connection complete all as specified and as directed.
S&F round shape 6 watt 220V AC surface type with high efficiency PMMA diffusor soft glare free light complete with drivers, holders, LED lamps suitable for roof ceiling including making connection complete all as specified and as directed.
S&F Lamp holder PVC/polycarbonate type with back plate, etc. complete all as specified and as directed.
S&F LED 7W lamp(base B-22) 6500K, not less than 90 lumen/watt efficacy complete all as specified and as directed.
S&F in replacement sub main two single core PVC copper conductor unsheathed wire multi stranded 6 sqmm along with earth wire 6.0 sqmm copper conductor single core wire connected by common earth in existing surface/recessed PVC/steel conduit and including complete all as specified and as directed. (Note :- two lengths of 6.0 sqmm cable and one length of 6.0 sqmm earth cable will be measured as one running length)
S&F in replacement sheet metal encloser double door 12 way SPN 240V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and as directed.
Supply, installing, test and commissioning (in replacement ) of indoor type LT panel wall mounted, having dimensions not less than 1.4mx0.8mx0.2m with double door made out of 2 mm thick CRCA sheet metal weather proof, with thimble and cable entry boxes with cable glands, having 07 Nos compartments for fixing of meters having acrylic cover. Panel should covered from all sides with front and back lockable door and hinges complete with copper bus bar of capacity 200 Amps with heat shrinkable PVC sleeve, with an angle iron Base Frame grouted in wall complete including painting with Paint shade of Epoxy based Powder Paint RAL 7032 & DMC insulators and consisting of the following :- (a) Incoming MCCB, 63 Amps, 4pole, 415volts 16KA - 01No (b) Outgoing MCB, 32 Amps, SPN , 230 volts 10KA B Curve- 06 No (Outgoing one for each DU) (c) Outgoing MCB, 10 Amps, SPN , 230 volts 10KA B Curve- 01 No (Outgoing one for each DU) (d) Internal Power & control wiring with suitable PVC insulated FR single core multistranded copper wire cable. (e) Indicating lamp set RYB ,type -01 Set. Note:- 1. Meters as dismentaled during panel replacement to be deposited in E/M store and shall be refixed into the meter boxes after installation. 2. Drawing of meter box panel must be approved by Engr-In Charge before placing order.
S&F in replacement single pole and neutral enclosure 240V with a two pin and earth plug and socket complete with one double pole MCB 20Amp complete all as specified and as directed.
S&F in repair MCB 6-32 Amp 240V SP 10 KA ‘B’ series etc. complete all as specified and as directed.
S&F in repair RCCB EARTH LEAKAGE PROTECTION 230V 25A AC type Double pole 30mA ISI marked complete all as specified and as directed.
S&F in repair MCCB 415V, FP 63A 16kA etc, complete all as specified and as directed.
M & L for earthing with galvanized steel plate electrode 600 x 600 mm x 6 mm size directly burried in ground vertically to earth pit not less than 2.25 meter deep below normal ground level with top edge of the earth plate not less than 1.5 m below normal ground level surrounded with coal dust and common salt filling in alternative layers of 15 cm thick each connected to and including GI earth wire 4 mm dia by means of nuts, bolts, check nuts & washers etc connecting to earthing test point, main switch board and including 15 mm dia GI pipe light grade for protection of earth lead from earth plate to distribution board and 20 mm dia GI pipe medium grade connected with funnel having wire mess for watering purpose including necessary excavation and earth work, PCC (1:2:4) type B-1 (using stone aggregates) for earthing pit, 10mm thick cast iron cover with angle iron frame all as specified and shown in electrical plate No 3 of SSR Part-I and testing on completion including replacement of old unserviceable. Note:- It is mandatory to paint a sqaure shape notice board of yellow color with legible black color letters of earthing mentioned details as below; Cost incurred deemed to be inlcuded in quoted rate:- (i) CA No. (ii) Date of installation after initial testing & Value of earth resistance in Ohm (iii) Date of last testing (iv) Value of earth resistance in Ohm in last test
M&L for painting staircase meter box including removing old paint, cleaning with scrapers of preparation of pld painted surface, complete with filler and making smooth surface, priming with red oxide primer and painting with two coat of synthetic enamel paint with approved color complete all as specified and as directed.
S&F in repair Switch piano, flush type single pole, one way 5 Amp complete all as specified and as directed.
S&F in repair Switch piano, flush type single pole, two way 5 Amp complete all as specified and as directed
S&F in repair Switch piano, flush type single pole, one way 15 Amp complete all as specified and as directed.
S&F in repair Bell push 5/6 Amps 230 V AC etc. complete all as specified and as directed.
S&F in repair Socket outlet 3 pin, 5A, flush type etc. complete all as specified and as directed.
S&F in repair Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flush type universal, etc. complete all as specified and as directed.
S&F in repair Socket outlet 2 in 1, 3 pin, 5 and 15 Amp flush type, etc. complete all as specified and as directed.
S&F in repair Stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. complete all as specified and as directed.
S&F in repair rigid non-metallic PVC conduit external dia 20mm in size inclusive of all tees, bends, elbows, reducers, junction boxes, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Complete all as specified and as directed.
S&F in repair Hylam sheet cover 3mm thick of size 5"x5" complete with machine screw/ washer with provision of slots for switches, sockets, fan regulators (including refixing of all switches, sockets, fan regulators dismentaled from existing sheets) etc, complete all as specified and as directed.
S&F in repair Hylam sheet cover 3mm thick of size 8"x5" complete with machine screw/ washer with provision of slots for switches, sockets, fan regulators (including refixing of all switches, sockets, fan regulators dismentaled from existing sheets), etc. complete all as specified and as directed.
S&F in repair Hylam sheet cover 3mm thick of size 13"x8" complete with machine screw/ washer with provision of slots for switches, sockets, fan regulators (including refixing of all switches, sockets, fan regulators dismentaled from existing sheets), etc. complete all as specified and as directed.
S&F in replacement GI terminal box of size not less than 79mmx99mm with minimum depth 50mm & thickness not less than 18 gauge complete with earth dolly including making good the disturb surfaces CM (1:3) to match the existing, etc. complete all as specified and as directed.
S&F in replacement GI terminal box of size not less than 79mmx207mm with minimum depth 50mm & thickness not less than 18 gauge complete with earth dolly including making good the disturb surfaces CM (1:3) to match the existing, etc. complete all as specified and as directed.
S&F in replacement GI terminal box of size not less than 132mmx207mm with minimum depth 50mm & thickness not less than 18 gauge complete with earth dolly including making good the disturb surfaces CM (1:3) to match the existing complete all as specified
M&L in replacement for earthing circuit wiring (green color) with multi-stranded copper conductor, single core, FRLS, PVC insulated and unsheathed cable of size 1.5 sqmm, run through existing conduit connected to existing terminal/socket point outlet/ MCBs etc complete all as specified and as directed. Note:- One run of cable in existing concealed conduit/surface drawn with suitable saddling shall be measured as one Running metre(RM) and shall deemed to be included in the quoted rate.
M&L in replacement for earthing circuit wiring (green color) with multi-stranded copper conductor, single core, FRLS, PVC insulated and unsheathed cable of size 2.5 sqmm, run through existing conduit connected to existing terminal/socket point outlet/ MCBs etc complete all specified and directed Note:- One run of cable in existing concealed conduit/surface drawn with suitable saddling shall be measured as one Running metre(RM) and shall deemed to be included in the quoted rate.
M&L in replacement for earthing circuit wiring (green color) with multi-stranded copper conductor, single core, FRLS, PVC insulated and unsheathed cable of size 4.0 sqmm, run through existing conduit connected to existing terminal/socket point outlet/ MCBs etc complete all specified and directed Note:- One run of cable in existing concealed conduit/surface drawn with suitable saddling shall be measured as one Running metre(RM) and shall deemed to be included in the quoted rate.
M&L in replacement for earthing circuit wiring (green color) with multi-stranded copper conductor, single core, FRLS, PVC insulated and unsheathed cable of size 6.0 sqmm, run through existing conduit connected to existing terminal/socket point outlet/ MCBs etc complete all specified and directed. Note:- One run of cable in existing concealed conduit/surface drawn with suitable saddling shall be measured as one Running metre(RM) and shall deemed to be included in the quoted rate.
Dismentaling & taking down of existing single phase energy meter and carried out testing and calibration for accuracy requirements and tempering issue as per standards. in NABL accredited laboratory and submit the report; refixing the calibrated energy meter at same specified location, etc. complete all as specified and as directed.
Dismentaling & taking down of existing three phase energy meter and carried out testing and calibration for accuracy requirements and tempering issue as per standards. in NABL accredited laboratory and submit the report; refixing the calibrated energy meter at same specified location.
S&F LED light fitting 9/10W bulkhead luminaires incluing LED light, driver, holder connecting up with three core flexible copper conductor cable of suitable size, etc. complete all as specified and as directed.
Supplying, laying, jointing & testing, underground XLPE insulated screen PVC bedded, GI steel strip or wire armoured heavy duty LT electric cable with aluminium conductor, 1100 volts grade, cross sectional area 16 sqmm 4core complete all as specified and as directed.
Disconnecting carefully DG set complete from existing LT panels, earthing installations & mounting plateform, lifting the DG set with hydralic machine & transporing carefully the same to place (not more than 4Km distant) as directed by Engineer-in-charge/GE and installing the same on mounting plateform including making necessary electric connection with existing LT panels / changeovers and existing earthing installation complete all as specified and as directed.
Note:- Net contract sum shall be calculated after deduction of Sch of credit.
M/s VISHAL ELECTRIC STORE
NASIB ENGINEERS AND CONSTRUCTION
KARTIK BUILDERS
M/S SODHI ASSOCIATES
SHARDA ENTERPRIES
M/s GURFATEH BUILDERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .