OFFICE OF THE EXECUTIVE ENGINEER EnM HP I HAIDERPUR WATER WORKS DELHI 110085
Renovation Servicing Dehydration of 1500 KVA Voltamp Make and 2000 KVA Crompton Greaves Make transformers at Khyala Booster Pumping Station
2020_DJB_195261_3
NIT 05
Open Tender
Miscellaneous Works
Item Rate
45 days
Haiderpur
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
₹11,000
16 Oct 2020
6 Oct 2020
13 Oct 2020
6 Oct 2020
13 Oct 2020
6 Oct 2020
Renovation/Repairing of transformer of 1500 KVA Voltamp Make at Khyala BPS. The job includes the following: A. 1500 KVA Transformer 11KV to 0.4 KV of Voltamp Make Dismantling of Transformer, removing all base nut/bolt & disconnecting of incoming HT cable connection as well as outgoing connection with bus duct
Dismantling of the complete transformer, removing the top cover, oil tank, silica gel breathers & cooling fins etc.
Cleaning of the core & coils with hot oil vacuum machine & removing the moisture from the coils & core. Cleaning the transformer tank, removing the sludges & silt. Heating the HT & LT windings with inductance heating, removing the moisture and improvement of the IR value of HT & LT winding
Replacement of top cover gasket & insulator gasket oil seal for stopping the leakage of oil
Tapping the HT connection lead with Kraft tape
Topping up of Transformer oil in Transformer
Dehydration of Transformer oil
Replacement of silica gel
Replacement of complete hardware items/nut bolt etc.
Checking & testing of the Transformer with HI POT testing, IR value, series testing, voltage ratio etc.
Assembling the complete Transformer & installation of the same and testing on load at site
B. 2000 KVA Transformer 11KV to .04 KV Dismantling of Transformer, removing all base nut/bolt & disconnecting of incoming HT cable connection as well as outgoing connection with bus duct
Dismantling of the complete transformer, removing the top cover, oil tank, silica gel breathers & cooling fins etc.
Cleaning of the core & coils with hot oil vacuum machine & removing the moisture from the coils & core. Cleaning the transformer tank, removing the sludges & silt. Heating the HT & LT windings with inductance heating, removing the moisture and improvement of the IR value of HT & LT winding
Replacement of top cover gasket & insulator gasket oil seal for stopping the leakage of oil
Tapping the HT connection lead with Kraft tape
Topping up of Transformer oil in Transformer
Dehydration of Transformer oil
Replacement of silica gel
Replacement of complete hardware items/nut bolt etc.
Checking & testing of the Transformer with HI POT testing, IR value, series testing, voltage ratio etc.
Assembling the complete Transformer & installation of the same and testing on load at site
A.S.ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .