Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.1 LAccepted-AOC H NO 959 SECTOR 3 ROHTAK | L1 | Accepted-AOC L1 | |
| 2 | L2₹20.6 L+₹3.6 L (21.0%)Rejected-AOC N A | NA | NA | 121004 | L2 | Rejected-AOC L2 |
Tender Value
₹18.6 L
EMD Value
₹37,280
Closing Date
6 May 2024, 3:00 pmClosed
JAGDISH SINGH DAHIYA
ENGG.CELL, MDU, ROHTAK
Construction of 1st and 2nd floor over the existing Sports Hostel for Boys participation for increasing the capacity, MDU Rohtak..(Electrical Work)
2024_HRY_368165_1
2024268CEB79 CB4C 4125 AC65 2F07F714CD5D817MDU
Open Tender
Electrical Works
Works
90 days
Rohtak
Construction of 1st and 2nd floor over the existing Sports Hostel for Boys participation for increasing the capacity, MDU Rohtak..(Electrical Work)
2 documents required · 2 mandatory
₹1,000
₹37,280
Yes
20 Nov 2024
13 Mar 2024
7 May 2024
13 Mar 2024
6 May 2024
13 Mar 2024
Amount
[20.72]Supplying, errection, testing of Exhaust fan (as per IS code 374) having a capacity of 45 cubic metre per minute complete with suitable G.I sheet ducting in structure confirming to latest IS specifications complete in all respect to satisfaction of Engineer-in-charge.
[23.11]Making suitable hole in the wall suitable for exhaust fan up to 450 mm sweep including finishing the same and fixing of Stainless steel wire mesh 2 mm thick having about 50 meshes per inch at exhaust side complete as required
[23.13]Supply, erection and fixing of 12 mm thick ply wood board having a circular /rectangular hole etc as required including the cost of making hole, nuts and bolts, painting and other petty material with all labour etc. complete in all respect up to the entire satisfaction of Engineer-in-charge of the work.
[23.20]Fixing of LED Tube light/ 2*2 ft square panel fitting directly on wall /ceiling or false ceiling including making connections etc as required
[23.22.1.10]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.10. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 125 to 160 amp, 25 KA
[23.22.1.11]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.11. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. 4 pole MCCB 200 to 250 amp, 25 KA
[23.22.2.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 2.2. MCCB Enclosure made of Sheet Steel suitable for mounting MCCB of following ratings MCCB up to 250 A FP
[23.22.4.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.7. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. TPN DB Horizontal type Double Door 8 way ( 8 incoming 3phase*8 outgoing)
[23.22.5.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.1. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole
[23.22.5.8]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.8. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs FOUR POLE
[23.22.6.6]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 6.6. Supply and erection double pole/Four pole Residual (RCCB/ELCB) on 240/415V, 5Hz. AC supply installed in existing sheet steel enclosures including making necessary connections and bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. FP RCCB 30ma sensitivity , 63 A
[23.3.1.2]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 1.2. Wiring for Light/Fan/call bell point in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe. Group B
[23.3.2.2]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 2.2. Wiring for Twin control light point with 2 nos , 2-ways, 5 amp. switch in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick PVC conduit pipe. Group B
[23.3.4.2]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 4.2. Wiring in PVC conduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin socket and 1 no 5/6 Amp switch required MS Box etc complete as required Group B
[23.3.5.2]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 5.2. Wiring in PVC conduit system for 3-pin 15amp. Plug point by using 2 no 4 sqmm FRLS copper wire and 1 no 4 Sqmm FRLS copper wire for earthling , including providing 1 no 15/16 Amp 3/6 pin socket and 1 no 15/16 Amp switch required MS Box etc complete as required Group B
[23.3.6.2]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.2. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 2.50 Sqmm(1.1.80mm)
[23.3.6.6]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.6. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 2 run of Size 1.50 Sqmm(1/1.40mm)
[23.5.6.5]COPPER WIRING IN EXISTING PVC/MS CONDUIT PIPE SURFACE/RECESSED FOR ELECTRICAL POINTS 6.5. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in existing MS/PVC Conduit etc as required. 1 run of Size 10 Sqmm(1/3.50 mm)
[23.7.6.1]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.1. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 20 mm dia.
[23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia.
[23.7.6.3]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.3. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 32 mm dia.
[23.8.4]FITTING AND ACCESSORIES 4. Supply and erection of 10.5 cm dia M.S.Fan box including 8 mm dia 30 cm long M.S. Road made into suitable suspension hook and erected in R.C.C. slab for the erection of fan complete with all labour and material required to complete the job.
[23.9]Erection of exhaust fan in existing opening ,complete with necessary earthling of fan including carriage from PWD store to the site of work.
[24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required.
[24.1.13]EARTHING AND LIGHTENING ARRESTOR 13. Providing and fixing 4.00 mm dia G1. Wire on surface or in recess for loop earthing as required.
[24.1.15]EARTHING AND LIGHTENING ARRESTOR 15. Erection only of lightning conductor GI. tape including supply of suitable GI. staples of same size.
[24.1.16]EARTHING AND LIGHTENING ARRESTOR 16. Supply and erection of 25mm dia 1.5 metre long lightning GI. tube rod tapered into a point at the top with 16cm x 16cm x 3mm thick G.I. base plate and necessary nuts and bolts with washers.
[24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required.
[24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required.
[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
[24.1.6]EARTHING AND LIGHTENING ARRESTOR 6. Supplying and laying 25mm x 3mm G.I. strip at 0.5 metre below ground as strip earth electrode including soldering etc. as required.
[24.1.7]EARTHING AND LIGHTENING ARRESTOR 7. Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required.
[24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material.
[24.10.1]CIVIL ITEMS (USED COMMONLY IN ELECTRICAL WORKS) 1. Digging & refilling of trench 30 cm wide below ground level for erection of pipe/cable (up depth of 1 Metre. underground cable excluding the cost of cable/pipe complete in all respect.
[24.10.6]CIVIL ITEMS (USED COMMONLY IN ELECTRICAL WORKS) 6. Digging of pucca road in required width for laying of cable / pipe complete in all respect up to the entire satisfaction of Engineer-in charge
[24.2.2.3]LT CABLE 2.3. Laying of underground cable 0.75 metre below ground level covered with sand and bricks including excavation and refilling of trenches.:- 50 Sq mm to 150 sqmm 2 to 4 Core
[24.2.4.3]LT CABLE 4.3. Laying of underground cable in pipe /existing open/closed trench etc as required:- 50 Sq mm to 150 sqmm 2 to 4 Core
[24.2.5.3]LT CABLE 5.3. Laying and fixing of cable on surface/ cable tray etc as required:- 50 Sq mm to 150 sqmm 2 to 4 Core
[24.2.6.5]LT CABLE 6.5. Supply and erection of copper lugs including crimping etc. entire satisfaction of Engineer-in- Charge of the work. 10 sqmm
[24.2.8.11]LT CABLE 8.11. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 150 sqmm
[24.2.8.7]LT CABLE 8.7. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 50 sqmm
[24.5.2.7]MISCELLANEOUS ITEMS 2.7. S/E mark double walled corrugated (DWC) HDPE, pipe 10 Kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 180/150 mm outer dia/ inner dia
Supply of 18/20 Watt LED PVC batten set Life- 50000 running Hours, 100 lumens/watt complete as per entire satisfaction of the Engineer-in-charge. (Make- Philips, Havells, Bajaj)
Dismantling of old main switches of different rating i.e 63 amp to 800 amp. From panel board in nitch including removal of all connections.
Dismantling of old angle iron board from existing nitch including removal of all connections and nut bolts.
supply of 50sq mm 4 core PVC flexible un armoured copper cable LT as per entire satisfaction of the Engineer-in-charge of work.(make- havells, polycab, RR Kabel/KEI/Anchor)
Supply and fixing of cable 3 core 1.5 Sqmm PVC Copper Cable complete in all respect as per entire satisfaction of Engineer in Charge. Make: Havells, Polycab, Anchor
Supply and installation of 200 watt LED flood light with IP66 multiple LED with lens optics and epoxy powder coated dia-cast aluminium housing for effective thermal management. Total system lumen of 200 watt LED should be 20000 or above in cool day light (5600K to 6500) power factor)0.95, effocacy)140 LM/W with 10 KVA SPD inbuilt and driver should be potted connections. Make- Philips, Havells, Wipro
supply of 150sq mm 3.5 core XLPE armoured Aluminum cable as per entire satisfaction of the Engineer-in-charge of work. (Make -havells, polycab,KEI.)
Supply and erection of MS Stand including fastening , drilling and required petty material complete as per entire satisfaction of the Engineer-in-charge.
Supply and erection of energy efficient 48` 1200MM 26/28 watt BLDC Ceiling fan 230 Volts, 50Hz,Rated speed 350 RPM,air delivery 220 cum/min minimum, THD less than 10% complete in all respects as per directions of Engineer-in-charge Make-Havells/Orient/Bajaj/Crompton.
M/S SURYANSH POWER
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .