Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.9 LAccepted-AOC | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹19.5 L+₹63,303.80 (3.36%)Rejected-Finance 37 PUNJABI COLONY NEAR RAILWAY CROOSING ARYA SAMAJ ROAD MATHURA U P | MATHURA | MATHURA | UTTAR PRADESH | 281001 | L2 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 3 | L3₹19.9 L+₹1.1 L (5.67%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST TENDERER |
Tender Value
₹22.5 L
EMD Value
₹45,000
Closing Date
7 Jan 2020, 6:00 pmClosed
GE (EAST) MATHURA
Garrison Engineer East Military Engineer Services Mathura Cantt Mathura 281001
SPL PROVN OF STANDBY SUPPLY ELECTRIC CONNECTION AND PROVN OF 50 X SECURITY LIGHTS AROUND HELIPAD BOUNDARY AREA UNDER GE EAST MATHURA
2019_MES_305229_1
8200-1097/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (EAST) MATHURA
SPL PROVN OF STANDBY SUPPLY ELECTRIC CONNECTION AND PROVN OF 50 X SECURITY LIGHTS AROUND HELIPAD BOUNDARY AREA UNDER GE EAST MATHURA
7 documents required · 7 mandatory
₹500
GE (EAST) MATHURA
₹45,000
7 Feb 2020
9 Dec 2019
8 Jan 2020
9 Dec 2019
7 Jan 2020
26 Dec 2019
9 Dec 2019 - 31 Dec 2019
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/loose soil complete.
Surface excavation n.exc 30 cm deep and averaging 15 cm deep and getting out in hard/dense of soil.
Returning filling with earth obtained from excavation including spreading watering and consolidation in layers not exceeding 25 cms thick complete.
Removing surplus soil to a distance not exceeding 50 m and depositing at a level not exceeding 1.5 m above the starting point complete.
M&L for sand cushioning to under ground cable in trenches in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engr in charge. Note:- Measurement shall be taken after gentling puning of sand.
M&L for hardcore of broken stone or boulders of guage n.exc 63 cm, deposited, spread and leveled in layers n.exc 15 cm thickness, watered and rammed to true surface.
Supply and Laying Unreinforced precast concrete cable cover class LV type 1, size 250mmx150mmx40mm complete as directed.
M&L for 50mm bore steel tubes light grade galvanised with all fittings fixed to walls/ floors/ poles/ road crossing etc sizes complete.
M&L for 40mm bore steel tubes light grade galvanised with all fittings fixed to walls/ floors/ poles/ road crossing etc of following sizes complete:- 40 mm bore
Supply, laying, jointing and testing of XLPE insulated, sheathed, armoured, heavy duty LT 1100 volts grade cable with aluminium conductor laid in trenches / pipes, fixed to poles / walls, fixing with suitable saddle/clamps complete all as directed.
35 sqmm 3.5 core.
50 Sqmm 3.5 core
120 Sqmm 3.5 core
150 Sqmm 3.5 core
M&L for Cable route indicator showing "LT Cable" and route/joint of cable with arrow made of PCC M-15 grade (Nominal Mix) using 20mm graded stone aggregate duly rendered with plaster 10mm thick of size 40x50x20cm, fixed and erected on PCC platform of size 40x40x10cm grouted in ground, duly painted on both side with LT cable route complete all as directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cmX60cmX6.0mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not than 1.5mtr below normal ground level connected to GI earth strip of size 32x6mm dia by means of bolts, nuts, check nuts and washers of galvanised iron complete earth pit of PCC M-10(Nominal mix) using 20mm graded stone aggregate, 50mm thick earth pit cover of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape, PGI funnel, wire mesh and 20mm bore GI water pipe medium grade and 40mm bore medium grade GI pipe for protection of earth strip from plate to main switch board, common salt, charcoal dust including testing on completion complete all as specified and as directed all as shown in electrical plate No. 3 including testing on completion and making good the disturbed surfaces of wall floors etc without claiming extra cost all as directed by Engr-in-Charge. (Note: GI strip beyond 5.0Mtr length from earth electrode shall be measured and paid separately).
Supply & install steel tubular swaged poles type 410 SP 31(9.0 meters long) complete with CI base plate and finial taper plug bolts nuts and screws . Painting with aluminium paint one under coat one finishing coat cover a coat of red oxide primer and making alternate colour bands of black & yellow colours in 30cms widths upto a heihgt of 1.5 mtr from pole coping with synthetic enamelled paint complete. Note: Earth work and PCC shall be measured saperately under respective item.
M & L PCC M-5 graded (Nominal Mix) using 40mm graded stone aggregate as in lean concrete of foundation.
M & L PCC M-7.5 grade (Nominal Mix) using 40 mm graded stone aggregate as in lean concrete for foundation filling and mass concrete all as specified and directed.
M & L PCC M-10 grade (Nominal Mix) using 40 mm graded stone aggregate as in foundation filling and mass concrete all as specified and directed.
M & L PCC M-15 graded (Nominal Mix) using 20mm graded stone aggregated as in foundation filling and mass concrete & coping of pole all as specified and directed.
M&L for 150mm thick M-15 graded (Nominal Mix) using 20mm graded stone aggregate as in floors and pavings finished even and smooth without using extra cement
Forming contraction (Dummy) joints 65mm deep x 10mm wide filled with sealing compound grade 'A'.
S&F Rolled section as in main and cross beams, hip and jack rafters, purlins where connected to common rafters and running rails and guides for sliding doors, fixed with angle cleats or other connecting plates.
S&F joints, channels, angle or tee section fixed independently, without connecting plates etc.
Mild steel bolts dia of neck n.exc 12mm, purpose made with hexagonal or square heads at one end and screwed the other or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, n.exc 30 cm long.
M&L 0.63mm thick, galvanized, corrugated mild steel sheeting with two corrugation slide lap, (class-8) fixed with 'L' hooks or cranked bolts in lieu of screws, in roof coverings walls etc completre all as specified and directed.
S&F Flat iron as in wind ties for roof including securing bolts, necessary drilling, bolting or riveting etc and similar work, complete all as specified and directed.
M&L for applying two coats of synthetic enamelled paint over a coat of red oxide on steel surfaces over 10 cm width or girth over new steel surfaces etc complete all as specified and directed.
M&L for PCC M-15 grade (Nominal Mix) using 20mm graded crushed stone aggregates as in copings, bed plates kerbs, water throughs and the like including weathering, slightly rounded or chamfered angels and throating as directed.
S& F LED street light fitting 70 Watt pressure die cast aluminium housing and heat resistance with toughend glass cover and instensity of light not less than 7000 lumens with inbuilt seach production device including fixing on poll or any other location all as directed at site new genration energy saving & environmental friendly long life versatile pressure die cast aluminium IP66 roadway luminaiie with with high power LED as light source. Make:- C&S Cat part nu LTESS70WLED/LS
S&F street light bracket made of GI pipe medium grade bend in shape of 50 mm dia, 1.2 m long and clamped with 2 pairs of 30 x 5 mm flat iron clamps, nuts/bolts/washers & painted with 2 coats of aluminium paint over a red oxide primer on clamps complete all as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core
Supply & replacement PVC insulated and sheathed flat twin core solid aluminium conductor cable 1100 volts grade of size 4.0 sqmm complete all as directed.
Supplying, installing, testing and commissioning out door type cubical feeder pillar box suitable for 3 phase, 4 wire, 415 volts, 50 Hz and CPRI approved for 35 MVA rupturing capacity at 415 volts, factory made in an approved factory having seven tank treatment process for powder coating with thickness not less than 60 microns provided with suitable gasket to make it dust / vermin proof & general construction confirming to IS:8623 / 93 mounted on suitable PCC M-15 grade (Nominal Mix) using 20 mm graded stone aggregate foundation comprising of the following complete all as specified and directed. comprising of following (i) MCCB TPN 415 volts 63 Amp. 10 KA --01 Nos (For incoming going). (ii) MCB TPN 32 Amp 10 KA ----02 Nos ( For outgoing) (iii) Copper bus bar 200 Amp for three phase and 100 Amp neutral (iv) Grouting of panel 60cm above GL, embedded in PCC M-15 grade (Nominal Mix) using 20 mm graded stone aggregate up to 30 cm all as directed.
shyam construction
RAJ CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .