| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.9 CrAdmitted-Finance | ₹2.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.9 Cr+₹6.0 L (2.06%)Admitted-Finance | ₹2.9 Cr+₹6.0 L (2.06%) | L2 | Admitted-Finance |
| 3 | L3₹3.0 Cr+₹8.0 L (2.75%)Admitted-Finance | ₹3.0 Cr+₹8.0 L (2.75%) | L3 | Admitted-Finance |
| 4 | L4₹3.6 Cr+₹70.7 L (24.5%)Admitted-Finance | ₹3.6 Cr+₹70.7 L (24.5%) | L4 | Admitted-Finance |
| 5 | L5₹3.6 Cr+₹70.9 L (24.6%)Admitted-Finance | ₹3.6 Cr+₹70.9 L (24.6%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | The Trikuta Engineer L3 | SRV TECHNO ENGINEERING PVT LTD L1 | TRIDENT ENGINEERS L4 | INDUSTRIAL ELECTRICALS L2 | M/s cee kay Traders L5 |
|---|---|---|---|---|---|---|---|---|
| 1.00SCOPE OF WORK FOR CREATION OF 100 KVA SUBSTATION | ||||||||
| 1.01 | Supply, Installation & commissioning of 11/0.433 KV, 100 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Aluminium Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation | 31 | No | 1,70,000 ₹52,70,000 | 1,85,000 ₹57,35,000 | 2,78,813.9 ₹86,43,230.9 | 1,58,000 ₹48,98,000 Lowest | 3,92,000 ₹1,21,52,000 |
| 1.02 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type | 31 | Set | 8,000 ₹2,48,000 Lowest | 20,000 ₹6,20,000 | 12,920.65 ₹4,00,540.15 | 9,000 ₹2,79,000 | 15,000 ₹4,65,000 |
| 1.03 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A | 31 | Set | 5,000 ₹1,55,000 | 15,000 ₹4,65,000 | 5,893.63 ₹1,82,702.47 | 4,500 ₹1,39,500 | 4,000 ₹1,24,000 Lowest |
| 1.04 | Supply Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA withpolymer housing, Stn. Type | 31 | Set | 7,000 ₹2,17,000 Lowest | 7,633 ₹2,36,623 | 34,001.7 ₹10,54,052.7 | 7,000 ₹2,17,000 Lowest | 9,000 ₹2,79,000 |
| 1.05 | Providing & Fixing of 120 mm² Single Phase Cable, 1.1 KV grade,PVC insulated Stranded conductor FRLS type(44 mtrs for each) | 1,364 | mtr | 215 ₹2,93,260 | 108 ₹1,47,312 | 200.01 ₹2,72,813.64 | 180 ₹2,45,520 | 100 ₹1,36,400 Lowest |
| 1.06 | Providing & Fixing of LT Distribution Box for 100 KVA DTR with MCCB for incomer & switch fuse unit for Out Going Ckts. | 31 | No | 25,000 ₹7,75,000 | 30,000 ₹9,30,000 | 35,061.75 ₹10,86,914.25 | 30,000 ₹9,30,000 | 18,000 ₹5,58,000 Lowest |
| 1.07 | Providing of Earthing of Sub-Station - Excavation of Earth Pit650mm and depth 3000mm , Installation of Earth Pipe of 40 mm of nominal bore & 4 mm wall thickness with length 2.5 Mtr long as per IS 1239, GI Strip for neutral Earthing of Size 25mm x3mm thickness for connection of Transformer Body, GO Set, LA Set as per IS 2629/85 GI nuts and bolts refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover(3per S/stn) | 93 | no | 2,500 ₹2,32,500 | 2,000 ₹1,86,000 Lowest | 8,000.4 ₹7,44,037.2 | 2,700 ₹2,51,100 | 2,500 ₹2,32,500 |
| 1.08 | Supply &Erection of 9 mtrs ST poles(ST-410 SP33) | 62 | No | 17,500 ₹10,85,000 | 23,000 ₹14,26,000 | 28,697.43 ₹17,79,240.66 | 18,000 ₹11,16,000 | 15,000 ₹9,30,000 Lowest |
| 1.09 | Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole | 62 | No | 1,200 ₹74,400 | 500 ₹31,000 Lowest | 2,400.12 ₹1,48,807.44 | 3,000 ₹1,86,000 | 2,500 ₹1,55,000 |
Tender Value
Refer Docs
EMD Value
₹7.5 L
Closing Date
12 Aug 2021, 4:00 pmClosed
Executive Engineer
Office of the Executive Engineer Electric Division Vijaypur JPDCL Jammu
Supply , Erection, Testing and Commissioning of Distribution Substations along with HT/LT lines for irrigation purposes under Saubhagya Excellency award with in the jurisdiction of Electric Division Vijaypur JPDCL Jammu
2021_PDD_131551_1
EDV/24 of 2021-22 dated 23.07.2021
Open Tender
Electrical Works
Turn-key
180 days
Samba District
Please refer Tender documents.
9 documents required · 9 mandatory
₹5,000
Executive Engineer Electric Division Vijaypur
₹7.5 L
Office of the Executive Engineer at Vijaypur
20 Jun 2022
23 Jul 2021
13 Aug 2021
23 Jul 2021
12 Aug 2021
23 Jul 2021
23 Jul 2021 - 12 Aug 2021
31 Jul 2021
Amount
SCOPE OF WORK FOR CREATION OF 100 KVA SUBSTATION
Supply, Installation & commissioning of 11/0.433 KV, 100 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Aluminium Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA withpolymer housing, Stn. Type
Providing & Fixing of 120 mm² Single Phase Cable, 1.1 KV grade,PVC insulated Stranded conductor FRLS type(44 mtrs for each)
Providing & Fixing of LT Distribution Box for 100 KVA DTR with MCCB for incomer & switch fuse unit for Out Going Ckts.
Providing of Earthing of Sub-Station - Excavation of Earth Pit650mm and depth 3000mm , Installation of Earth Pipe of 40 mm of nominal bore & 4 mm wall thickness with length 2.5 Mtr long as per IS 1239, GI Strip for neutral Earthing of Size 25mm x3mm thickness for connection of Transformer Body, GO Set, LA Set as per IS 2629/85 GI nuts and bolts refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover(3per S/stn)
Supply &Erection of 9 mtrs ST poles(ST-410 SP33)
Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Supply Installation, Testing & Commissioningof 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Supply Installation, Testing & Commissioningof 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & fixing of wedge connectors/PG clamps
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary galvinised Nut & Bolts & Washers etc.
Painting of Poles with two coats each of red Oxide & Aluminium Paint
SCOPE OF WORK FOR CREATION OF 63KVA SUBSTATION
Supply, Installation & commissioning of 11/0.433 KV, 63 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, "BIS Marked" (Aluminium Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Supply Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA withpolymer housing, Stn. Type
Providing & Fixing of70 mm² Single Phase Cable, 1.1 KV grade,PVC insulated Stranded conductor FRLS type(44 mtrs for each)
Providing & Fixing of LT Distribution Box for 100 KVA DTR with MCCB for incomer & switch fuse unit for Out Going Ckts.
Providing of Earthing of Sub-Station - Excavation of Earth Pit650mm and depth 3000mm , Installation of Earth Pipe of 40 mm of nominal bore & 4 mm wall thickness with length 2.5 Mtr long as per IS 1239, GI Strip for neutral Earthing of Size 25mm x3mm thickness for connection of Transformer Body, GO Set, LA Set as per IS 2629/85 GI nuts and bolts refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover(3per S/stn)
Supply &Erection of 9 mtrs ST poles(ST-410 SP33)
Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Supply Installation, Testing & Commissioningof 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Supply Installation, Testing & Commissioningof 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & fixing of wedge connectors/PG clamps
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary galvinised Nut & Bolts & Washers etc.
Painting of Poles with two coats each of red Oxide & Aluminium Paint
SCOPE OF WORK FOR LAYING OF HT LINE ON 9 MTR PCC POLES USING ACSR WEASEL
Supply, Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Supply Installation, Testing & Commissioningof 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Supply Installation, Testing & Commissioningof 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing of Stone Pad 300 mmx300mmx75mm
Providing and fixing of Aluminium Jointing sleeves
Providing and fixing of P G Clamps
RouteClearance and Branch Cutting
SCOPE OF WORK FOR LAYING OF LT LINE ON 8 MTR PCC POLES USING ACSR WEASEL ( 3 Phase 4 wire)
Supply, Transportation, Erection of 8 Mtr Long PCC Pole (WL-200 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Providing & Fixing of MS U-Clamp with Shakle Insulator (Polymer/Porcelain) alongwith Nut & Bolt of sorts
Supply, Laying & Stringing of ACSR Weasel Conductor through insulators including proper binding & twisting with soft Aluminium Wire
Providing & Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of LT Line Spacers
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing of Stone Pad 300 mmx300mmx75mm
Providing and fixing of Aluminium sleeves
RouteClearance and Branch Cutting
INDUSTRIAL ELECTRICALS
The Trikuta Engineer
TRIDENT ENGINEERS
M/s cee kay Traders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .