Ex. Engineer (Elect)/CSPZ
OFFICE OF THE EX. ENGINEER (ELECT)-I UNDER GROUND CAR PARKING ASAF ALI ROAD, DELHI-110002
Construction of 200 Bedded Balak Ram Hospital Ward Block at Timar Pur,Delhi. Sub-Head- Provision of cabling and LT panel expansion for Power supply to HVAC,Rising Main etc.
2023_NDMC_146535_1
37/MWEEE-I/2022-23/TC
Open Tender
Electrical Works
Item Rate
120 days
Balak Ram Hospital
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,180
₹1.1 L
13 Sept 2023
22 Feb 2023
2 Mar 2023
22 Feb 2023
2 Mar 2023
22 Feb 2023
Amount
7.6.2:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 35 sq. mm and upto 95 sq. mm
7.6.3:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 95 sq. mm and upto 185 sq. mm
7.6.4:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 185 sq. mm and upto 400 sq. mm
4.1.1:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4.1.2:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4.1.3:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
2.5.1:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4 + 12), Double door
2.10.4:Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.2.1:Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 16 KA, TPMCCB
OD3531/2022-2023:Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 (P-I) as required. 3½ X 50 sq. mm
OD3532/2022-2023:Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 (P-I) as required. 3½ X 70 sq. mm
OD3533/2022-2023:Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 (P-I) as required. 3½ X 150 sq. mm
OD3534/2022-2023:Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 (P-I) as required. 3½ X 240 sq. mm
OD3535/2022-2023:Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1 KV grade conforming to IS-7098 (P-I) as required. 3½ X 300 sq. mm
OD3536/2022-2023:VANTILATION FAN PANEL Fabrication, supplying, installation, Testing & Commissioning of wall mounted electrical panel of cubical construction, of suitable size with 250 Amp 4 Pole Aluminium Bus Bar insulated with heat shrinkable PVC sleeve, fabricated out of 2mm thick CRCA sheet for load bearing members & 1.6 mm thick CRCA sheet for non load bearing memebers, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection, having following switchgears and accessories mounting and internal wiring, earth terminals, numbering etc. Complete in all respect, suitable for operation on 415 v, 3phase, with neutral 50 HZ. AC supply. Incomer Feeder 250 Amp,35 KA,TPN MCCB - 1No Indicating Light - 3Nos Dig. Ammeter 0-300 A - 1No Dig. Voltmeter 0-500 V - 1No Control MCB - As required CT 250/5A -3Nos Outgoing Feeder 100 Amp,25 KA, TPN MCCB - 3 Nos
OD3537/2022-2023:MAIN LT PANEL Fabrication, supplying, installation, Testing & Commissioning of floor mounted electrical panel of cubical construction, of suitable size with 1600 Amp 4 Pole Aluminium Bus Bar insulated with heat shrinkable PVC sleeve, fabricated out of 2mm. thick CRCA sheet for load bearing members & 1.6 mm thick CRCA sheet for non load bearing memebers,compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley (Top Entry), inter-connection, having following switchgears and accessories mounting and internal wiring, earth terminals, numbering etc. Complete in all respect, suitable for operation on 415 v, 3phase, with neutral 50 HZ. AC supply. Incomer Feeder 1600 Amp TP ACB (MDO) -2Nos. Indicating Light - 6Nos Dig. Ammeter 0-2000 A -2No Dig. Voltmeter 0-500V -2No Control MCB - As required CT 2000/5A -6Nos BUS COUPLER 1600 Amp.TP ACB (MDO) - 1 No. Outgoing Feeder(with Ammeter of suitable rating) 1000 Amp,TP ACB (MDO) -2Nos 1250 Amp,TP ACB (MDO) -2Nos 630 Amp.40KA TP MCCB - 4 Nos.
OD3538/2022-2023:ESSENTIAL PANEL EXTENSION Fabrication, supplying, installation, Testing & Commissioning of floor mounted electrical panel of cubical construction, of suitable size with 800 Amp 4 Pole Aluminium Bus Bar insulated with heat shrinkable PVC sleeve, fabricated out of 2mm. thick CRCA sheet for load bearing members & 1.6 mm thick CRCA sheet for non load bearing memebers,compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley (Top Entry), inter-connection, having following switchgears and accessories mounting and internal wiring, earth terminals, numbering etc. Complete in all respect, suitable for operation on 415 v, 3phase, with neutral 50 HZ. AC supply.(Panel to be connected with existing panel with bus bar on top) Incomer Feeder - NIL Outgoing Feeder(with Ammeter of suitable rating) 630 Amp.40KA TP MCCB - 3 Nos.
zedelec switchgears LLP
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .