Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.8 LAccepted-AOC TAILOR MARKET MAIN BAZAAR MANDI ADAMPUR 125052 | HISAR | HARYANA | 125052 | L1 | Accepted-AOC L1 | |
| 2 | L2₹99.4 L+₹1.1 L (1.09%)Rejected-Finance 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L2 | Rejected-Finance L2 | |
| 3 | Rejected-Technical DSS 194 POCKET A SEC 14 125001 | HISAR | HARYANA | 125001 | - | Rejected-Technical Not Eligible | |
| 4 | Rejected-Technical 2ND FLOOR PLOT NO 338 UDHYOG VIHAR PHASE IV GURUGRAM 122015 HARYANA | GURUGRAM | HARYANA | 122015 | - | Rejected-Technical Not Eligible |
Tender Value
₹95.1 L
EMD Value
₹1.9 L
Closing Date
26 May 2025, 5:00 pmClosed
PRAMESH Kumar
ED - Hisar
Pdg. Fire Alarm and PA System in Mini Sectt. Hisar
2025_HRY_447072_1
202578381F07 051F 48EC 9468 2D9968009387666BAR
Open Tender
Electrical Works
Works
60 days
Hisar
2 documents required · 2 mandatory
₹5,000
₹1.9 L
Yes
4 Jul 2025
15 May 2025
27 May 2025
15 May 2025
26 May 2025
15 May 2025
Amount
[23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. [Through Rate]
SITC of Wiring for Fire Alarm system with the following sizes 2 x 1.5 sq.mm of FRLS insulated copper conductor Double core 1100 volts grade cables in existing surface/recessed M.S. conduit etc. as complete as required. Make Finolex/Grandly/Polycab/PLAZA.(Rates are excluding GST)..
SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having Detector nos 879. of required loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 2 Serial Ports. The panel shall have a built in power supply, battery charger maintenance free battery capable of running for a minimum 24 hours operation complete as required. The panel should also have IP30 or better protection. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. Make: Morley ZX5SE,Bosch Avenar 2000, Siemens Cereberus EN. (Rates are excluding GST).
SITC of addressable multisensor smoke detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements: Drift Compensation feature and Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values.Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Make: Morley HM/PTSE/I plus MI/B501AP/IV ,Bosch FAP-425-OT plus MS400B,Siemens OH720 plus DB721 (Rates are excluding GST).
SITC of addressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector). (Make: Morley HM/RHSE/I plus MI/B501AP/IV, Bosch FAH-425-T plus MS400B, Siemens HI720 plus DB 721). (Rates are excluding GST).
SITC of Analog Addressable type Active Repeater Fire Alarm Panel with Backlit LCD display, having controlls for reset, mute, accept, silence alarms and self test conforming to BS5839 standards with all labour and materials required to complete the job in all respect up to the entire satisfaction fo engineer-in-charge of work. Make : (Morley ZX R-A, Bosch FMR, Siemens FT201). ( Rates are of GST excluded).
SITC of Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliat to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make : Morley HM/MCP/Glass, Bosch FMC-210- DM-G-R, Siemens FDM22.(Rates are excluding GST).
SITC of Addressable Loop powered sounder with strobe/flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer - in Charge of work. Make: Morley WSO-PR-N05,Bosch FNM-420, Siemens FDS224R (Rates are excluding GST).
SITC of Co2 type Fire Extinguisher 4.5Kgs. Capacity, made from brand new seamless cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Squeeze Grip type valve with initial Charge as per IS: 15683:2006 specification, bearing ISI Mark (Make:Safex / Savemax/Ceasefire) (Rates are excluding GST).
SITC of minimum 1000 Mtr. Range Siren generator provided at the roof of the building with separate power suppl, relay etc.. Make: National/Kheraj (Rates are excluding GST).
SITC of ABC Stored Pressure type Fire Extinguisher 6kg. Capacity (5 year warranty) bearing ISI Mark for fire fighting ABC class of fire extinguisher will be manufactured strictly as per BIS IS:683:2006 bearing ISI Mark EN3 615 approved powder(Make:Safex / Savemax/Ceasefire) (Rates are excluding GST).
SITC of Intelligent Analog Addressable type Response Indicator with all labour and material required to complete the job in all respect Makes: Bosch/ Siemens /Honeywell Moreley. (Rates are excluding GST).
SITC of Glow Type Exit Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class - I material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour and material required to complete the job in all respect up to entire satisfaction of Engineer-in-Charge of work. Make Pearl/Giolite/OMEX.
SITC of 3 Meter Rubber pipe with EPDM Quality with squzeer grip nozzle for Jet length I.S.I Mark Make Safex / SAVEMAX / CEASEFIRE . (Rates are excluding GST).
SITC of Mechnical foam Type Fire Extinguisher 50 Leter capacity with OUTSIDE CYLINDER, CO2 CYLINDER 1 KG CAPACITY for Above AFFF foam compound for the extinguisher, 3000 mls capacity combine. Make Safex / SAVEMAX / CEASEFIRE . ( Rates are excluding GST).
SITC of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be considered separately for payment). Makes: Bosch/ Siemens /Honeywell Moreley. (Rates are excluding GST).
SITC of Electrical Cabinet Suppression system Contains FK -5-1-12 fire Suppression Fluid (10lbs/4.54 kgs)ECS Cylinder bracket (1) EOL Adapter w/ pressure gauge(1) , EOL plug (1) , Rubber grommets (4) , Plastic loop clamps (25) , pressure Switch point 5 bar /singal generator UL listed , UL listed Head detection tube (red color )10 mtr, T- Connector -6 UL listed, EOL Adapter w/ guage UL listed, , End of line Plug UL listed complete in all respect upto the satisfaction of engineer - in charge f the work .(Make:Safex / Savemax/Ceasefire) (Rates are excluding GST).
SITC of Wall mounted 22 U enclosure of dimension 600W X9UX500D with front sheet steel glass door , top and bottom cover with cable entry provision, integrated side walls , 1 pair of 19` angles with wall mounting provision, captive hardware(pack of 20) complete in all respect(Make: COMRACK/Netrack/ Dynamic ) (Rates are excluding GST).
SITC of battery backup for controllers ( 3 KVA UPS on line with 1 hours backup ) Make Elnova, Microtek, Eaton. (Exclusive GST)
SITC of 9 U rack with cable manager, fan tray, power distribution kit complete in all respect. Make: HCL/Cormack/Wallrack/Netrack. (Rates are excluding GST).
SITC of Horn Loudspeaker made with ABS, watered dust protected to IP 65,Sound pressure level at 15W/1W - 115/103 dB (SPL), Effective frequency range 500 Hz to 5 kHz, Rated power 15W to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work MakeHenrich/Honeywell/Bosch (Rates are excluding GST).
SITC of Class D amplifier 500 watts Frequency response: 60 Hz to 15 khz ( plus 1/3db), Inputs :XLR and phone jack , Input 1, Input 2-4, Impendence :20kO, Sensitivity : 1 V balanced , S/N ): )85 dB complete in all respect MakeHenrich/Honeywell/Bosch. rate are excluding of GST
SITC of Wall Mount/Ceiling Speaker with operation 15 Watts to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work MakeHenrich/Honeywell/Bosch. (Rates are excluding GST).
SITC of 5 Kg ceiling mounted fire extinguisher clean agent HFC 134A zero ODP, stored pressure type, pressure guage gross weight 7.7 Kg empty weight 2.7 Kg, can height 267 MM diameter 230 MM Discharge time less than Bsec, Auto discharge mechinism on temperture rise applicable on class A,B,C aqnd electrically started fire can construction valve construction forging and mechinig internal coating of can expoxy powder coating sheet metal thickness 1.60 Mm (Make - Cease fire/ Savemax/ SAFEX).(Rates are excluding GST).
Insat Techno Services (BID ID -1265372)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .