Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.3 LAccepted-AOC | L1 | Accepted-AOC Lowest amount quoted | |
| 2 | L2₹34.6 L+₹2.9 L (9.14%)Rejected-Finance PLOT NO 81 SHANTAJI COLONY JANKI NAGAR JABALPUR MP PIN 482002 | JABALPUR | MADHYA PRADESH | 482002 | L2 | Rejected-Finance Second lowest amount quoted | |
| 3 | L3₹41.4 L+₹9.7 L (30.5%)Rejected-Finance HO SR NO 73 TAPKIR MALA CHOWK TAPKIR NAGAR KALEWADI PIMPRI PUNE 411017 | PUNE | MAHARASHTRA | 411017 | L3 | Rejected-Finance Highest amount quoted | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-The firm is suspended since EMD amount on account of revocation of tender has not deposited by the contractor. |
Tender Value
Refer Docs
EMD Value
₹75,400
Closing Date
16 Mar 2022, 6:00 pmClosed
Shri Dhiraj Kumar, IDSE, EE
Garrison Engineer (East), Near COD Estate, Ranjhi, Jabalpur (MP)-482011
As per BOQ
2022_MES_506022_2
8400/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer (East) Jabalpur
D b (i)
7 documents required · 7 mandatory
₹500
Garrison Engineer (East) Jabalpur
₹75,400
Yes
5 May 2022
23 Feb 2022
18 Mar 2022
23 Feb 2022
16 Mar 2022
2 Mar 2022
23 Feb 2022 - 25 Feb 2022
Amount
Supply & lay XLPE insulated armored and PVC sheathed heavy duty electric cable with aluminum conductor 1100 Volt grade laid in tranches passing through pipes /ducts including testing complete of following cross sectional area and size Make of cable , NOTE-Rate is inclusive of cable lugs & cable gland.
2 Core,10 Sq. mm cross sectional area
2 Core,16 Sq. mm cross sectional area
4 Core,10 Sq. mm cross sectional area
4 Core,16 Sq. mm cross sectional area
4 Core, 25 Sq. mm cross sectional area
3.5 Core, 35 Sq. mm cross sectional area
3.5 Core, 50 Sq. mm cross sectional area
3.5 Core, 70 Sq. mm cross sectional area
3.5 Core, 95 Sq. mm cross sectional area
3.5 Core, 120 Sq. mm cross sectional area
(l) 3.5 Core, 240 Sq. mm cross sectional area
Supply, Installation, test and Commissioning CPRI APPROVED factory fabricated, out door type, LT FEEDER PILLAR BOX of size not less then 0 .9 m width X 1.2 m heigth X 0.6 m depth,made out of 3.15 mm thick CRCA Sheet with projected Globe roof for rain water protection Dust and Vermin Proof , Double door with both side opening including Neoprene Rubber Gasket, suitable for 440 Volt 3 Phase 4 Wire System, including Danger Plate, Earthing Strip Point and Ventilation Louvers at Rear Side, Bottom detachable Gland Plate complete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and embedded with 50X50X6mm Mild Steel Angle Iron Frame and 750 mm above the Normal Ground Level complete with internal connection with suitable size of cable, cable lugs and cable glands PCC Foundation in Cement Concrete 1:3:6 (20 mm Graded Stone Aggregate) and Testing after Installation including complete all as specified and comprising of the following :–
(a) Aluminum bus bar 400 Amps - 01 Set.
(b) MCCB 250 A 35 KA,4 POLE ,thermal magnetic relese, Ics=100% Icu -1 no ( incomming)
(c) MCCB 125 A 25 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu - 3 nos (O/G)
(d) MCCB63 A 25 KA,3 POLE ,thermal magnetic relese, Ics=100% Icu & L&T/Legrand /schneider- 2 nos (O/G)
(g) LED TYPE indicator lamp 1 set (set of three for R,Y,B)
Earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth 32 x 6mm GI strip by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt,Earthing lead 32x6 up to 7.5m, 20mm dia medium grade GI watering pipe, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-1991 (part-I) NOTE-: GI earth strip beyond 7.5 m & GI protection pipe shall be measured and paid for separately under relevant item of schedule .
M & L for dismantling of LT overhead ACSR conductor of any size from its position by necessary disconnecting of conductor and removing complete all as directed by Engr-in-Charge.
M & L for dismantling of earthing wire of any size from LT overhead poles of any size etc and removing from site of work complete all as directed by Engr-in-Charge.
Dismantling of U/S insulator of any size and type complete from its position and removing all as directed by Engr-in-Charge.
Dismantling of U/S stay assembly carefully including stay wire necessary excavation and earth work in any type of soil, demolition of PCC of any type and removing from site all as directed.
M & L for dismantling of existing cross arms, angles, CI clamps, nuts etc from OH line and removing complete from LT pole of distribution span complete all as specified and directed.
Dismantling of LT steel Tubular poles and srtting aside for re-use complete all as specified and directed Note : ((i) The Contractor would be responsible from removing the existing steel tubular poles and depositing with the MES yard. (ii) Incase erection of poles, Excavation refilling, removal and PCC will be measure and Paid seperately.
Taking down street light Fittings any size and re-fixing again of LT pole complete all as specified and directed. NOTE :- Afterdismantling of ACSR/AAC, Earthing wires, cross Arms, channel, brackets, clamps, insulators etc complete and again re-fixing of street light fittings any & size and rate is deemed in included in unit rate quoted by the contractor.
M & L for PCC 1:3:8 type D2 using 40 mm graded stone aggregate as in filling & mass concrete complete all as specified and directed.
M & L for PCC 1:3:8 type B2 using 20 mm graded stone aggregate as in coping of pole ect including work & finishing the surface even & smooth with out using extra cement complete all as specified and directed.
Material and labour for boring hole under the road/path/pavment/hard standing with the help of trenchless technology using ultra sound technique and necessary machine include HDPE pipe of 110 mm dia suitable for 0.4 mpa working pressure not less than one metre below ground level complete all as specified & directe buy Engr-in-charge at site. NOTE:- The cost of HDPE pipe shall be deemed to be include in quoted rate.
S & F for GI Pipe light grade for cable protection passing under road/floor or for fixing to poles all as complete all as specified and directed the following :-
100 mm Dai
80 mm Dai
50 mm Dai
Supply instll commissining and testingof CPRI Approved floor mounted outdoor cubicl type LT Feeder Pillar Box of uitabl size abricated out of 3.15 mm thick CRCA Sheet and angle iron 50X50X6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrngement on front and back with locking arrangement cable entry and exist from bottom with cble glands and gaskets, Copper bus bar 750 Amps rating fixed on porcelain insulator with inernal wiiring with suitable size of Copper strips to be used for incoming and outgoing connection of all switchs/MCCB"s & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 500 Amps, 4 Pole, 45 KA with front operated locking device - 01 Nos
(b) OUTGOING
(i) Thermal magnetic MCCB 250 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
(ii) Thermal magnetic MCCB 225 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
(iii) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 26 KA, Qty-02 Nos
(iv) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
(v) Thermal magnetic MCCB 50 Amps, 4 Pole, 415 V, 26 KA, Qty-01 Nos
(vi) Thermal magnetic MCCB 32 Amps, 2 Pole, Qty-01 Nos
(vii) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
(x) Indicator Lamp - R-Y -B (Set of three)
(xi) Frequency meter 40-55 Hz - 01 Nos
Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 300 Amps, 4 Pole, 45 KA with front operated locking device - 01 Nos
(b) OUTGOING
(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 16 KA Qty - 01 Nos
(ii) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 16 KA Qty - 05 Nos
(iii) Thermal magnetic MCCB 32 Amps, 2 Pole, Qty-01 Nos
(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
(vii) Indicator Lamp - R-Y -B (Set of three)
(viii) Frequency meter 40-55 Hz - 01 Nos
Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 500 Amps, 4 Pole, 35 KA with front operated locking device - 01 Nos
(b) OUTGOING
(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 25KA, Qty - 04 Nos
(ii) Thermal magnetic MCCB 250 Amps, 4 Pole, 415 V, 25 KA, Qty - 01 Nos
(iii) Thermal magnetic MCB 32 Amps, 2 Pole, Qty-03 Nos
(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
(vii) Indicator Lamp - R-Y -B (Set of three)
(viii) Frequency meter 40-55 Hz - 01 Nos
Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 300 Amps, 4 Pole, 45 KA with front operated locking device - 01 Nos
(b) OUTGOING
(i) Thermal magnetic MCCB 100 Amps, 4 Pole, 415 V, 16 KA, Qty - 01 Nos
(ii) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 16 KA, Qty - 05 Nos
(iii) Thermal magnetic MCCB 32 Amps, 2 Pole, Qty-01 Nos
(iv) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
(vii) Indicator Lamp - R-Y -B (Set of three)
(viii) Frequency meter 40-55 Hz - 01 Nos
Supply & install commissioning and testing CPRI Approved floor mounted outdoor cubical type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA sheet and angle iron 50 x 50 x 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, copper bus bar 450 Amps rating fixed on percelain insulator with internal wiring with suitable size of a copper strips to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar, Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surfce externally & internally over a coat of red oxide primer paint incl, necessary PCC (1:3:6) type C2 as in fjoundation all as directed, comprising of the following :-
(a) INCOMING
(i) Thermal magnetic and microprocessor release MCCB 150 Amps, 4 Pole, 25 KA with front operated locking device - 01 Nos
(b) OUTGOING
(i) Thermal magnetic MCCB 63 Amps, 4 Pole, 415 V, 16 KA, Qty - 02 Nos
(ii) Thermal magnetic MCCB 32 Amps, 4 Pole, Qty-01 Nos (IV) Thermal magnetic MCCB 25 Amps, 4 Pole, 16 KA Qty-01 Nos (V) Thermal magnetic MCB 32 Amps, 2 Pole, Qty-03 Nos
(iii) Timer Switches single phase 20A rating with contrator fitted - Qty 01 Nos
(vi) Indicator Lamp - R-Y -B (Set of three)
(vii) Frequency meter 40-55 Hz - 01 Nos
S&F Junction box for street lights of size 155 x210 x92 mm, 2 mm thick totally enclosed, with rubber gasket, water tight junction IP 66 protection single leaf shutter in front having proper locking arrangements and stud terminal (provision for socket bolting)-05 Nos suitable for 240 volts, 50 HZ, 2 wire internal wiring system including MCB SP 6 Amps-01 No and mounted on secutity light pole with suitable bracket nuts, bolts complete all as specified and directed.
Taking down old unserviceable street light fitting any type & size and S&F LED street light lumanaries of size 45 CW high performance street light luminaire with single die ceramic base high power LED light source, IP 66 protection complete with driver, lamp bracket with impect and corrosion resistant including thermal management arrangement with pre-wired and necessary mounting junction box including provision of 4 sq mm three core copper conductor cable multi stranded from fitting to junction box including GI pipr medium grade of 40 mm dai bracket 1.5 mtr long bend to required shape with suitable clamps made out of flate iron of size 40x6 mm- 2 sets, bolts& nuts, washers etc complete all as specified and directed. Make: PHILIPS cat part No BRP 052 LED 045 CW SLMR FG S1 GR /HAVELLS/BAJAJ.
Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth wire 4.00 mm dia by means of bolts, nuts, check nuts and washers complete up to and including test point made out of 40 x 6 mm alum flat including earthing pit, charcoal common salt, Earthing lead 4.00 mm dia up to 7.5 m, 20 mm dia medium grade GI watering pipe, G.I. protection pipe 15 mm dia up to 7.5 m long, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2009 (Part-I).
Excavation in trenches for laying of cables, poles and stay not exceeding 1.5 mtr wide and not exceeding 1.50 mtr deep and getting out.in soft/loose soil
Returning & filling in, including spreading and leveling, watering and well ramming in layers n.exc. 25cm all as specified and directed by Engr-in-Charge.
Removing excavated materials not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point.
Unwashed Sand cushioning to under ground cable provided with a layer of 8 cm deep before laying and 15 cm covering above the top edge of cable after laying complete all as specified. Note : maesurement shall be done after puning down of sand.
Supplying and laying Brick covering with width equal to length of bricks as mechanical protection to cable with well burnt sub class `B` bricks laid dry and flat complete all as specified and as directed.
Supplying & laying unreinforced precast cement concrete cable covers, Class LV, Type-1 flat, size 250mm x 150mm x 40mm in trenches for cable protection, embossed with "LT 1100 Volts electric" on the top surface complete all as specified and as directed by the Engineer-in-Charge.
S & F MCCB DB vertical type made of sheet steel, powder painted with Nutral bus Bar 200A, neutral link IP-43-IK09 protection grade, 415 Volts TPN with 4 way Double door including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and directed.
MCCB TPN 100 Amps, 415Volts, 25KA, 4 POLE
MCCB TPN 63 Amps, 415Volts, 25KA, 4 POLE
MCB SP 63 Amps 'C' series, breaking capacity 10 KA of rating
MCB SP 40 Amps 'C' series, breaking capacity 10 KA of rating
MCB SP 6-32 Amps 'C' series, breaking capacity 10 KA of rating
Supply & fix Microprocessor based Single phase electronic temper proof energy meter of rating 06 to 30 Amp with optical communication port, conforming to IS: 13779.including woodn board on which meter to be installed properly all as spesified and directed by Engr-in-Charge.
S & F MCB DB made of sheet steel, powder painted with Nutral bus Bar 200A, neutral link earth bar and Din rail, 230 volts SPN with 8 way Double door IP-43 IK09 protection grade including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and directed.
S&F Service cable of aluminum conductor of size 10 sq mm, 2 core with PVC sheathered weather proof of ISI mark and suspended with No 8 SWG GI wire up to distance 135 mtr from pole to service bracket & than to meter passing through 40 mm GI pipe service bracket .
S&F Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 4 Sqmm, earth continuity conductor of size 2.5 Sqmm to be drawn through in and including PVC conduit on walls/roof/floors all as directed by Engineer in Charge. Notes:- (i) Two wires of 4 sqmm and one wire of 2.5 sqmm shall be measured as one unit.
S&F Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 6 Sqmm, earth continuity conductor of size 4 Sqmm to be drawn through in and including PVC conduit fixed on walls/roof/floors all as directed by Engineer in Charge.Notes:- (i)Two wires of 6 sqmm and one wire of 4 sqmm shall be measured as one unit.
S&F cable route indicator/marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregate) of size 900mm x 300mm x 100mm thick with "DANGER/LT 433 VOLTS CABLE /MES OR DANGER/MES" embossing on canble route Indiator/Marker including painting as per approed colour and buried in ground 45 cms including necessary earth work (as required/ordered at site) complete all as specified and as directed.
Schedule of credit amount of Rs. 39,030.00 to be deducted during AOC
shri krishna traders
Goodluck Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .