| Sl No | Description | Qty | Unit | SAHEL DHAWA L2 | Bharat Sales Corporation L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of self supported Indoor type totally enclosed panel board of size not less than 9m X 1.2m X 0.9m or suitable size recommeded by OEM, compartmental design, dust and vermin proof, suitable for 3 phase, 4 wire 415 volt, made out of 2mm thick CRCA sheet with built upon rigid frame work, cubical type with angle iron of size 50X50X6mm, duly powder coated, IP 54 as per IS 13947 protection, complete with air circuit breaker, aluminium bus bar 2400 Amp, fault rating 50KA/Sec, having front and rear hinged door with neoprene rubber gasket including danger notice plate, earthing termination points including continous earthing strip alongwith panel, bottom detachable gland plate with holes for incoming and outgoing cables and control circuit diagram with colour code complete with following accessories:- | 1 | Set of Panel | 78,90,000 ₹78,90,000 | 65,02,297.09 ₹65,02,297.09 Lowest |
| 1.01(a) Incoming : Air Circuit Breaker,1600A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard , inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminum Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation, having extended terminal and rotary with breaker ON, OFF, Trip indication, Digital Ampere Meter, Digital Volt meter, selector swithces including suitable CT complete all as specified and directed - 02 Nos. (Make : Hager/Schneider/Seimens) | |||||
| 1.02(b) Buscoupler : Air Circuit Breaker,1600A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard , inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminum Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation complete all as specified and directed - 01 No. (Make : Hager/Schneider/Seimens) | |||||
| 1.03(c) Outgoing : Air Circuit Breaker, 630A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard, inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminium Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation complete all as specified and directed - 12 Nos. (Make : Hager/Schneider/Seimens) | |||||
| 1.04(d) ACB panel Bay : Each ACB panel bay shall be equipped with following and cost of the same shall be deemed to be included in quoted rate:- (i) Multifunction Meter: Each bay will display current/voltage/KW/KVA/KVAR/Pf/Hz. (ii) Local/remote switch : Panel needs to be equipped with local/remote with wiring of remote upto terminal block. (iii) Indication : Green (ON) & Red (OFF) indication on each ACB panel console. (iv) Extended cable bus bar: Suitable capacity of aluminium busbars as per I/C & O/G ACB capacity from breaker to O/G cables end termination for accommodate all cables. (v) Suitable copper control cable wiring with proper routed and ducted to each panels. | |||||
| 1.05Note : (i) ACB panel has two nos. for incoming, One no. for Bus-coupler & Twelve nos. for outgoing with a proper cable termination chamber. (ii) Incomer ACB panels shall be electrically interlocking system with suitable adapter. (iii) Panel manufacturer shall got approval of general arrangement drawing and size of panel, etc before panel manufacturing. (iv) Existing foundation shall be modified and alteration as per new ACB manufacturer's requirement are deemed to be included with cost of panel. (v) Contractor has to ensure the electric supply will not be hampered when replacement of panel takes place and make suitable arrangements like temporary cables, bus bar, lugs, etc. has to be provided without extra cost | |||||
| 2.00 | Supply and fixing of APFC panel without reactor 350 kVAr, rated voltage 415 V AC, 3 phase, 50 Hz, delta connection, having super heavy duty cylindrical capacitors as per suitable capacity, size of panel 1175 X 800 X 540mm minimum complete all as specified and directed. (Make : Schneider/Seimens/Havells) | 2 | Each | 9,90,000 ₹19,80,000 | 7,30,000 ₹14,60,000 Lowest |
| 3.00 | Supply and fixing of APFC panel without reactor 200 kVAr, rated voltage 415 V AC, 3 phase, 50 Hz, delta connection, having super heavy duty cylindrical capacitors as per suitable capacity, size of panel 1175 X 800 X 540mm minimum complete all as specified and directed. (Make : Schneider/Seimens/Havells) | 1 | Each | 5,70,000 ₹5,70,000 | 4,30,000 ₹4,30,000 Lowest |
| 4.00 | Disconnecting & taking out unserviceable LT panel/APFC panel from site including connected LT UG cables from ACBs/MCCBs and earthing connections complete material all as specified and directed. | 18 | Each Job | 2,000 ₹36,000 | 1,000 ₹18,000 Lowest |
| 5.00 | M&L in replacement of Earthing complete with GI earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25m deep below ground level with top edge of the plate not less than 1.5m below normal ground level connected to GI earth strip 32x6 mm dia up to 7.5 meter from earth pit, protected by GI pipe light grade 40mm dia, 20 mm medium grade for watering with funnel , common salt, charcoal dust and connected to panel board by means of bolts and nuts washers made out of GI all as shown in Electrical plate No 5 of SSR part I including necessary earth work and excavation in any type of soil, PCC 1:2:4 type B1 chamber with 40mm thick RCC 1:2:4 type mix cover slab with 6mm dia MS bars at 100mm dia both ways with MS hook 6mm dia MS bars etc complete all as specified and directed | 4 | Each Set | 7,900 ₹31,600 | 5,000 ₹20,000 Lowest |
Tender Value
₹1.2 Cr
EMD Value
₹2.0 L
Closing Date
17 Jun 2026, 6:00 pmClosed
Shri. Shirish Sharma IDSE SE SAG
CWE AF KALAIKUNDA
SPECIAL REPAIR/REPLACEMENT OF LT PANELS WITH ACBS/MCCBS AND APFC PANELS AND ALLIED WORKS AT MAIN POWER HOUSE AND TECH AREA SUB STN AND PROVN OF PIPELINE AND WATER TAP FOR MAINTENANCE OF EARTHING INFRASTRUCTURE AT VARIOUS PLACESAT AF STATION KALAIKUND
2026_MES_766678_1
8732/KKD/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
CWE AF KALAIKUNDA
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE AF KALAIKUNDA
₹2.0 L
Yes
30 Jul 2026
20 May 2026
18 Jun 2026
20 May 2026
17 Jun 2026
10 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of self supported Indoor type totally enclosed panel board of size not less than 9m X 1.2m X 0.9m or suitable size recommeded by OEM, compartmental design, dust and vermin proof, suitable for 3 phase, 4 wire 415 volt, made out of 2mm thick CRCA sheet with built upon rigid frame work, cubical type with angle iron of size 50X50X6mm, duly powder coated, IP 54 as per IS 13947 protection, complete with air circuit breaker, aluminium bus bar 2400 Amp, fault rating 50KA/Sec, having front and rear hinged door with neoprene rubber gasket including danger notice plate, earthing termination points including continous earthing strip alongwith panel, bottom detachable gland plate with holes for incoming and outgoing cables and control circuit diagram with colour code complete with following accessories:- | 1 | Set of Panel | - | - |
| 1.01 | (a) Incoming : Air Circuit Breaker,1600A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard , inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminum Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation, having extended terminal and rotary with breaker ON, OFF, Trip indication, Digital Ampere Meter, Digital Volt meter, selector swithces including suitable CT complete all as specified and directed - 02 Nos. (Make : Hager/Schneider/Seimens) | - | - | - | - |
| 1.02 | (b) Buscoupler : Air Circuit Breaker,1600A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard , inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminum Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation complete all as specified and directed - 01 No. (Make : Hager/Schneider/Seimens) | - | - | - | - |
| 1.03 | (c) Outgoing : Air Circuit Breaker, 630A 4P 50KA EDO LSIG Realease, 50 Deg Celcious (ambient temperature) without deration, Short Circuit Breaking Capacity (Icu=Ics=Icw) of 50kA for 1 sec ,100% Neutral , with inbuilt ZSI / Pre Trip Alarm as standard, inbuilt Copper Terminal Adaptor with flexibility of orientation from horizontal to vertical at site upto 4000A With sufficient overlap area for aluminium Bus bar termination, positive interlocking feature while rack in / rack out for correct racking positioning and Position acknowledgement for each position while racking operation complete all as specified and directed - 12 Nos. (Make : Hager/Schneider/Seimens) | - | - | - | - |
| 1.04 | (d) ACB panel Bay : Each ACB panel bay shall be equipped with following and cost of the same shall be deemed to be included in quoted rate:- (i) Multifunction Meter: Each bay will display current/voltage/KW/KVA/KVAR/Pf/Hz. (ii) Local/remote switch : Panel needs to be equipped with local/remote with wiring of remote upto terminal block. (iii) Indication : Green (ON) & Red (OFF) indication on each ACB panel console. (iv) Extended cable bus bar: Suitable capacity of aluminium busbars as per I/C & O/G ACB capacity from breaker to O/G cables end termination for accommodate all cables. (v) Suitable copper control cable wiring with proper routed and ducted to each panels. | - | - | - | - |
| 2 | Supply and fixing of APFC panel without reactor 350 kVAr, rated voltage 415 V AC, 3 phase, 50 Hz, delta connection, having super heavy duty cylindrical capacitors as per suitable capacity, size of panel 1175 X 800 X 540mm minimum complete all as specified and directed. (Make : Schneider/Seimens/Havells) | 2 | Each | - | - |
| 3 | Supply and fixing of APFC panel without reactor 200 kVAr, rated voltage 415 V AC, 3 phase, 50 Hz, delta connection, having super heavy duty cylindrical capacitors as per suitable capacity, size of panel 1175 X 800 X 540mm minimum complete all as specified and directed. (Make : Schneider/Seimens/Havells) | 1 | Each | - | - |
| 4 | Disconnecting & taking out unserviceable LT panel/APFC panel from site including connected LT UG cables from ACBs/MCCBs and earthing connections complete material all as specified and directed. | 18 | Each Job | - | - |
| 5 | M&L in replacement of Earthing complete with GI earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25m deep below ground level with top edge of the plate not less than 1.5m below normal ground level connected to GI earth strip 32x6 mm dia up to 7.5 meter from earth pit, protected by GI pipe light grade 40mm dia, 20 mm medium grade for watering with funnel , common salt, charcoal dust and connected to panel board by means of bolts and nuts washers made out of GI all as shown in Electrical plate No 5 of SSR part I including necessary earth work and excavation in any type of soil, PCC 1:2:4 type B1 chamber with 40mm thick RCC 1:2:4 type mix cover slab with 6mm dia MS bars at 100mm dia both ways with MS hook 6mm dia MS bars etc complete all as specified and directed | 4 | Each Set | - | - |
| 6 | Supply and fixing Aluminium strip 25 X 3.15mm with saddles and fixing screws etc. for continous earthing of panels complete all as specified and directed | 150 | RM | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
TENDER8732.pdf
Tender Documents • 0.92 MB
BOQ_858637.xls
BOQ • 2.29 MB
8732amend.pdf
PDF • 3.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .