Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 CrAccepted-AOC VPO MAJARI TEHSIL SHRI NAINA DEVI DISTT BILASPUR HP | ₹3.5 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹3.6 Cr+₹3.5 L (0.99%)Accepted-AOC 0 MATADIN KAKRAHI KAKRAHI BHARTHANA ETAWA ETAWAH UTTAR PRADESH 206242 | ETAWAH | UTTAR PRADESH | 206242 | ₹3.6 Cr+₹3.5 L (0.99%) | L2 | Accepted-AOC L2 |
| 3 | L3₹3.8 Cr+₹30.1 L (8.54%)Accepted-AOC | ₹3.8 Cr+₹30.1 L (8.54%) | L3 | Accepted-AOC L3 |
| 4 | L4₹3.9 Cr+₹34.0 L (9.65%)Accepted-AOC HIMACHAL PRADESH HP | HAMIRPUR | HIMACHAL PRADESH | 174304 | ₹3.9 Cr+₹34.0 L (9.65%) | L4 | Accepted-AOC L4 |
| 5 | L5₹4.0 Cr+₹49.3 L (14.0%)Accepted-AOC | ₹4.0 Cr+₹49.3 L (14.0%) | L5 | Accepted-AOC L5 |
Tender Value
₹3.9 Cr
EMD Value
₹4.2 L
Closing Date
28 May 2020, 11:00 amClosed
Executive Engineer
Jal Shakti Division Hamirpur
Providing and laying jointing and testing of Rising main construction of anchor Block for rising main and supply and errection of pumping machinery Booster and 1st stage
2020_HPIPH_37148_1
IPH-HMR-CB-Misc.Agr/2019-20/
Open Tender
Civil Works
Item Rate
180 days
Hamirpur Distt.
Providing and laying jointing and testing of Rising main construction of anchor Block for rising main and supply and errection of pumping machinery Booster and 1st stage
9 documents required · 9 mandatory
₹2,500
EE Hamirpur
₹4.2 L
Yes
13 Aug 2020
14 May 2020
28 May 2020
14 May 2020
28 May 2020
14 May 2020
14 May 2020 - 28 May 2020
Amount
Excavation in foundations and trenches (for pipes and pits) upto all depths etc. in all kinds of soil such as pick work, jumper work and saturated soil including bailing or pumping out of water, blasting in soft/hard rock or chiseling or wedging out of same where blasting is prohibited in all leads and lifts including trimming and dressing of sides, leveling of beds to correct grade including shoring strutting, planking timbering and dewatering wherever required, stacking usable and unusable material/soil separately and after laying jointing and testing of pipes, returning the usable soil in 15 cm layer by ramming and watering and then disposing of all surplus excavated soil/unusable material as directed within all leads and lifts including restoration of unmetaled surfaces to its original condition and including cost of diversion of traffic, night signal boards, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects within all leads and lifts as per the direction of Engineer-in-charge.
Providing laying and jointing and testing in trenches of GMSERW Plain ended pipes including cost of bends of all degrees conforming to IS 3183-2007 of following steel grade as per dimension rates and test pressure mentioned below in random lenth 5 to 7 Mtrs with 95% butt welded and 5% flanged joints by considering minimum three layer to make the joints leak proof and to the enitire satisfaction of the Engineer-in-charge. The laying of pipe should be confirmed to IS 5822-1994 (earth work in trenches and butt welding to be measured and paid for separtely) The pipe shall be zinc coated on innter to outer face as per IS:4736-1986 with upto date ammendments.
Rising main:- I GMSERW Pipe 150 mm dia of Grade L-210 or A With W.T. 4.80 mm (RD 0-190) =190 RMT
Rising main -II GMSERW Pipe 150 mm dia of Grade L-210 or A With W.T. 4.80 mm (RD 190/0-4500) = 4500 RMT
Rising main -III GMSERW Pipe 100 mm dia of Grade L-210 or A With W.T. 4.80 mm (RD 4500/0-3450) = 3450 RMT
Rising main -IV GMSERW Pipe 125 mm dia of Grade L-210 or A With W.T. 4.80 mm (RD 0/500-500) = 500 RMT
Rising main -V GMSERW Pipe 80 mm dia of Grade L-210 or A With W.T. 4.80 mm (RD 0/0-1500) = 1500 RMT
Rising main -VI GMSERW Pipe 125 mm dia of Grade L-210 or A With W.T. 4.80 mm (RD 0/0-1500) = 1500 RMT
Providing, Laying jointing and testing in trenches (to level or grade) of GMS pipes 95% butt welded and 5% flanged jointng including cost of bends of below mentioned diametre conforming to IS 1239-2001 (Latest upto date amendments) of grade and wall thickness as specified, suitable to withstand required hydraulic test pressure including fixing of required number of MS nuts and bolts as per IS 1369-1967 and compressed asbestos fibre jointing gaskets sheet not less than 3.00 mm in thickness as per IS 2712-1998. complete in all respects to the entire satisfation of Engineer-in-Charge. The laying of pipes shall conform to IS 5822-1994 as well as CPHEEO manual and will include all operations such as jointing including flushing, cleaning and hydrauliic testing complete in all respects to the entire satisfation of Enginner in Charge including entire carrirage of materials in all leads and lifts. ((Earth work in trenches , jointing i.e. flanged and butt welded will be measured and paid for separately.)
Rising main:- IV RD 500 to 1800 Rmt GMS tube 125mm dia (Heavy Class)
Rising main:- V RD 1500 to 2400 Rmt GMS tube 80mm dia (Heavy Class)
Rising main:- VI RD 1500 to 2700 Rmt GMS tube 125mm dia (Heavy Class)
Providing and welding MS flanges @ 5% of total joint conforming to following tables as per IS 6392-1971 (Last with upto date amendments) with plan end G.I/MSERW pipe in three (One inner and two outer) number of layers on both faces to make the joint leak proof (The cost of providing and laying of GI pipes to be measured and paid for separately). The welding of flanges should conform to IS 816-1969 with electrodes as per IS: 814-1991 and required number of nuts and bolts conforming to IS 1364. including cost of gasket sheet nuts & bolts. The thickness of gasket sheet not less then 3.00 mm conforming to IS 2712-1998. The work shall be done tothe entire satisfaction of engineer in charge within all leads and lifts
M.S. flange 150mm dia Table-28
M.S. flange 150mm dia Table-17
M.S. flange 150mm dia Table-5
M.S. flange 100mm dia Table-28
M.S. flange 100mm dia Table-17
M.S. flange 100mm dia Table-5
M.S. flange 125mm dia Table-28
M.S. flange 125mm dia Table-17
M.S. flange 125mm dia Table-5
M.S. flange 80mm dia Table-17
M.S. flange 80mm dia Table-5
Providing Circumferencial Butt welded joints by electrical welding of following dia GMSERW pipe, welded in requsite number of weld runs so as to achieve the minimum effective throat thickness of weld conforming to IS 816-1969 specifications, by using welding electrodes of 2.5mm to 6.30mm of Advani Oerlikon (Adore) CITOJETE/ESAB make conforming to IS 814-1991, at site of work complete in all respects, including manual/machanical handling of pipes in all leads and lifts with die penetrtion test to the entire satisfaction of Engineer in charge.
GMSERW Pipe 150 mm dia With W.T. 4.80 mm (RD 0/0 tpo 190 & 0-4500)=4690 Rmt.
GMSERW Pipe 100 mm dia With W.T. 4.80 mm (RD 0-3450)
GMSERW Pipe 125 mm dia With W.T. 4.80 mm (RD 0-1800)(RD- 0/0 to 2700 Rmt )=4500Rmt.
GMSERW Pipe 80 mm dia With W.T. 4.80 mm (RD 0-2400)
Providing doubble flange cast steel Reflux valve of Leader/Kirloskar make and 125 mm dia to 200mm for rising main with standing the nominal sheet pressure as per BIS 1868-API/ class-600 with upto date ammendments.
150mm dia ASA-300
150mm dia ASA-150
125mm dia ASA-300
125mm dia ASA-150
100mm dia ASA-300
100mm dia ASA-150
80mm dia ASA-300
Providing and fixing of screwed type cast steel Air valve of leader make and 25mm dia with upto date ammendments.BIS 1452-90,PN-10 with stand a steel pressure 11.22kg/cm2.
Providing and laying cement concrete 1:4:8(1cement:4sand:8 graded stone aggregate 40mm nominal size and curing complete excluding the cost of form work in foundation and plinth in all leads and lifts.
Providing form work with steel plated 3.15mm thick welded with angle iron in frame 30x30x5mm, so as to give a fair finish including centring,shuttering,strutting and propping etc. with wooden battens and ballies height of propping and centering below supporting floor to ceiling not exceeding 4 meters and removal of the same for insitu-reinforced concrete and plain.
Vertical surfaces such as walls(any thickness) partitions and the like including attached pilasters, buttresses, plinth and string courses and the like complete in all respect as per direction and to the entire satisfaction of the Engineer-in-charge.
Providing and laying cement concrete 1:2:4(1cement:2sand:4 graded stone aggregate 20mm nominal size)and curing complete excluding the cost of form work in foundation and plinth within all leads and lifts.
Providing, Laying mild or tor steel reinforcement for RCC. Work including bending binding and placing in position complete upto floor two level Tor steel in all leads and lifts.
Booster Stage-Phase-I :Pumping Machinery
Supply of submersible pumping set of reputed make such as KSB/Clama/SU/Johanston/Lubi comprising to latest relevant BIS Code. The pump should be fitted with Bronze impeller of suitable alloys as per IS 8034-1976 latest suitable for clear water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP, RPM 2900 of KSB/Kirlosker/NGF/Crompton make conforming to BIS 9238-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps , cable clips and depth gauge etc. and suitable for operation on data given below:-
SITE CONDITIONS:-
Location of site:- River Beas
The altitude of place in which the motor is intended to work in ordinary service.- 450 mtrs.
Humidity:- Humid during rainy season
Nature of atmosphere:- Normal
Detail of quality of water:- clear water
Water free from sand or not:- Free from sand
Water corrosive or not:- Not corrosive
Turbidity:- Less than 50 ppm
Type of well:- Percolation well
Inside dia of well:- 6.00 meter dia.
Depth of water during HFL in the well:-
Maximum draw down:- mtrs.
Depth of well :- 10.00 mtrs.
Any other information if required.
OPERATING CONDITIONS
Type of current:- AC. Three phase
Operating frequency 50 Hz.
Rated voltage 400(+/-) 10% volts.
System of earthing if any to be adopted Double loop earthing as per BIS: 3243-1987 latest with upto date amendments .
Speed of revolutionTo be quoted by tenderer
Direction of rotation To be quoted by tenderer .
No. of working hours per day. 8 hours
The maximum temperature of cooling air and water in the place in which the pump set is intended to work in ordinary service Temperature of place to be specified 20oC to 42oC.
MOTOR
Ref. to BIS code BIS 9283-1979 with upto date amendments
Type of enclosure of motor. As per BIS-4691-1985 (Latest)
Type of duty : Continuous
Mechanical output in KW Suitable for driving submersible pumps required for duties specified against pumps. To avoid over loading of motor a margin of about 15-20% may be kept in the rated output to prime Mover.
Class of insulation Class –B
Max. Permissible temp. Rise of motor reqd. if different from that given in 8 (viii) above.To be specified by the tenderer.
Particulars of test reqd. & where they are to be conducted. AS per terms and conditions attached.
Particulars as to whether voltage limiting device will be employed. Oil immersed star delta starter to be installed between bus bar and motor. Shunt capacitor is also proposed to be installed for improving the power factor at site.Note:- Star delta starter upto 37.5 Kw.
Type of motor Star Delta strater up to 37.5 KW As per BIS 9283-1979 or latest.
Details of shaft extension required
Break way torque in terms of rated load torque and the corresponding break-way starting current which may be taken from the supply with the starting apparatus in circuit should not exceed 2.5 times of the full load current .
Nature of load and any information regarding the driven machine which has a bearing upon the torque reqd. during the accelerated period, the kinetic energy of the moving parts to be accelerated and No. of starts during a specified period.
Where possible fault capacity of the system to which the motor is connected.The motor should be able to withstand initial current of 2.5 times the rated current for two minutes without suffering damages or permanent deformations.
PUMPS
Nos. of pumps required. 2 No. pumps out of which one set will work at a time and one set will act as stand bye.
Spare parts required. For two years normal maintenance as recommended by manufacturer.
Type of drive. Electric induction motor.
Optional fittings required
Pump Operating conditions
Capacity 18.04 LPS for each Pump
Total head in meters 19.70 meter
Static head 13.50 meters
Minimum depth of water Meters
Variation in water level meter
Ground level to Max. water level meter
Ground level to delivery point Meter
Pressure in the suction tank.
Pressure in the delivery tank
Length of rising main 190 meters
Dia of rising main 150 mm dia
Turbidity of water < than 50PPM
Drive type Electric driven
Limits of total head in which the pump is required to operate. (-) 15% to (+) 10% of total head
Suction/Delivery size of pump
Efficiency of pump at
a) Duty head
b) (+) 10% head.
c) (-) 15% head.
Material of construction. To be specified by the tenderer (manufacturers certificate to be appended)
Supply of direct on line starter of MEI/Kilburn make conforming to BIS 8544-1987 (P-II)latest with upto date amendments for squirrel cage induction motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load release and gas-pots, time legs, under voltage release & initial oil filing of suitable capacity.
Supply of MS. Angle iron steel sheet 16 SWG fabricated floor mounting closed (Almirah type) switch board comprising and capable of mounting the following accessories and with all internal electric connections, duly painted. The drawing of pannel board shall be subject to approval of Engineer-in-Charge
ICTP switches with HRC fuses of Havells/L&T/standard /cromption make for required motor of suitable capacity and conforming to BIS: 4064-1978 latest with upto date amendments.
Bus bar chamber having 3 copper bars of suitable rating for full length of 3 phases and one bar of half the rating of full length for neutral conforming to BIS: 8084 –1976 and 11353-1985 read with 5578-1985 all latest with upto date amendments.
MCB of suitable capacity of Havells/standard/MDS/Jyoti/Kilburn make to feed motors offered by the tenderer conforming to BIS: 2516-1985 latest with upto date amendments with neutral linked under voltage release.
3 phase indicating lamps complete with toggle switches for individual motors conforming to BIS-3452 part-I & II latest with upto date ammendments. 15 Watt.
50 mm dial Hour run meter of CEE/NEE make of 0-9999 as per relevant BIS specifications.
Supply of Kirloskar/leader make . cast iron (class PN. 1.6 ) double flanged sluice valve having size one dia higher than delivery of pump and capable of with standing nominal seat pressure of 16.32 kg/cm2 as per IS :780-1984 (Part I)
Supply of Kirloskar/leader make cast iron (class PN. 1.6 ) double flanged ( swing check type) reflux valve having bye pass arrangement and having one dia higher to delivery of pump and capable of withstanding nominal seat pressure of 16.32 kg/cm2 as per BIS-5312-1984.(Part-I).
Providing and laying suitable size copper PVC insulated armoured power 3.5 core cable conforming to BIS 1554 (part-I) –1988 of latest with upto date amendments siemen/closter/ICC make form meter of HPSEB- to MCB and form MCB to Bus bar switch starter and to motor ( two meter one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles, flexible pipe solder, nuts and bolts, cable glands, etc. laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer.
Supply side Suitable size
Motor Side suitable size
Supply of Leader /Kirloskar/ make 150 mm dia. cast iron class PN. 1.6 double flanged (swing check type) reflux valve having bye pass arrangement and size equal to dia of rising i.e. 125 mm for withstanding nominal seat pressure of 16.32 Kg/Cm 2 as per BIS 5312-1984 (Part-I )
Supply of PVC joint less flat water proof cable as per BIS: 694-1990 latest with upto date amendments suitable for the pump sets offered from MCB to motor including all other electrical equipment/accessories such as thimbles, flexible pipes solder, nuts and bolts, cable glands etc laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities & in case of non acceptance by HPSEB authorities it shall have to be replaced by tender.
Providing and laying double loop earthing with G.I. wire & G.I plate complete with material such as charcoal, common salt, GI. Pipes, thimbles, nuts and bolts, digging of pits, GI. Wiring and aluminum strips of required capacity conforming to BIS: 3043-1987 latest with upto date amendments for above motors and other electrical equipment’s.
Supply of standard make circular dial pressure gauge 0-16 kg/cm2 range of feibig make with all accessories such s stop cock, copper tubing etc, conforming to BIS: 3624-1987 latest with upto date amendments.
Providing and laying delivery pipe 125mm dia. and common header 150 mm dia MSERW pipe jointed with MS flanges of table-5 as per IS: 6392-1971 (upto a length of 20 mtrs ) including rappers, flanges, rubber gaskets, nuts and bolts and specials upto 5 mtrs away from the outer wall of pump houses as per layout drawings approved by Engineer-in-Charge.
Supply of floor/wall mounted power factor shunt capacitor conforming to BIS: 2834-1986 latest with upto date amendments Baja/L&T/Asian/cromption make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of required KVAR each including cable of siemens/Gloster/ICC make form bus bar chamber to capacitor and also including L&T/LK/Kilburn make ICTP switches conforming to BIS –4064-1978 or latest with HRC fuses (range to be specified by the tendrerer).
Erection of all equipment including cost of tees, bends, tapers and any other fittings required as per site conditions and as per direction of Engineer-in-charge.
Intake 1 Stage-II: Centriugal pumping machinery
Providing horizontal spindle horizontal split casing/end suctions (back full out arrangement) single/double/ multistage centrifugal pump or combination of pump in series of recommended make such as KSB Mather & Platt/Jyoti/Kirloskar/WASP/Lubi confirming as per BIS-1520-1980 with up to date amendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate ( base plate to be from the manufacturers of the pumping unit only) to Squirrel Cage drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF and suitable for operation on 400 (+)/-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be at least 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with up to date amendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discahrge (Q) : -Total 18.04 LPS
Or Cum/Hour
Total dynamic head : 216.19 Mtr
(a) LWL in sump well (h) : 448.00 mtr
(b) Shaft level : 447.50 Mtr
(c ) Level at discahrge point : 600.00 mtr
(d) Suction lift :- 0.00 mtrs
(e) Residual head : 3.00 Mtr
(f) Static head : 152.50 mtrs
(i) Rising Main :
(a) Length 4500 Mtr
(b) Dia. : 150 mm
(iv) Pumping Hours : 8 Hours
(v) Altitude of installation above MSL : 500.00
(vi) Characteristics of water :
(a) Temperature : 20.00 0 C
(b) Ambient temperature 42.00 0 C
(c ) Turbidity Less than 50.00 ppm
(d) Alkalinity < than Mg/Ca Co3
(e) Size of the solids mm
(f) Other
Providing Side handled operated Change over switch of L&T/Crompton/Standard/ Havells make suitable capacity Operational rating as per IS: 4064-1978 with up to date amendments immediately after the power meter of HPSEB
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-
M.C.B. Havell/L&T/Standard of make of Suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516-1985 with up to date amendments with.
E.L.R. of Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition).
Power factor meter of AE/L&T Rishab make as per relevant IS codes with up to date amendments of suitable rating.
Frequency meter of AE/ L&T Rishab make as per relevant IS: Codes with up to date amendments of suitable rating.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments .
ICTP switches with HRC fuses of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064-1978 with up to date amendments.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments.
Providing Hour run meter of recommended make of (0-9999 H) as per IS: 722 (Latest edition)
Capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required rating according to HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of required KVAR range as per IS: 4064-1978 with upto date amendments
Providing suitable Auto transformer of MEI/Kilburn make as per IS:8544-1979 with upto date amendments for squarrel cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248(P-V)-1983 with upto date ammendments.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make of 150mm dia for the suction pipe and capable of withstanding the normal seat pressure 10.20 Kg/cm2 as per IS: 780-1984 Class 1.0 with up to date amendments.
Providing double flanged Cast steel sluice valve of Leader/ Kirloskar make and size one dia higher than pump for the delivery line of the pump and capable of with standing the normal seat pressure 52.00 kg/cm2 and as per IS –1414/ API-600(class-ASA-300) with up to date amendments.
Providing double flanged (Swing type) Cast steel reflux valve of Leader/Kirloskar make and one dia dia higher then pump having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure 52.00 kg/cm2 as per IS –1868/ API-600(class-ASA-300) with up to date amendments
Providing double flanged Cast Steel non return valve of Leader/ Kirloskar make and of 150 mm dia having bye pass arrangement for rising main and capable of with standing normal seat pressure 104.00 kg/cm2 as per per IS –1414/ API-600(class-ASA-300) up to date amendments
Providing 100mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52kg/cm2.
Installation of all the items appearing at s.No.25-34 and as per directions and to the entire satisfaction of Engineer-in-charge.
Providing and fixing double flanged MSERW piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing No.2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand including water hammer (Heavy class) flanged with M.S. flanges of Table - 28 in delivery side & common header.
The size of the various components to be as under:-
(i) Suction pipe 150 mm dia Min length of 20 mtrs. GI pipe(MC) flanged T-5.
(ii) Delivery pipe 125 mm dia Min length of 5 mtrs MSERW pipe flanged T-28.
(iii) Common Header 150 mm dia Min length of 10 mtrs - MSERW pipe flanged T-28
And will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/GICO/Grandly /National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: Suitable size
Supply side: Suitable size
Providing and fixing double loop earthing and G.I. plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx6mm G.I. strips & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Intake -I Stage-III: 1 to Point A:- Centriugal pumping machinery
Providing horizontal spindle horizontal split casing/end suctions (back full out arrangement) single/double/ multistage centrifugal pump or combination of pump in series of recommended make such as KSB Mather & Platt/Jyoti/Kirloskar/WASP/Lubi confirming as per BIS-1520-1980 with up to date amendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate ( base plate to be from the manufacturers of the pumping unit only) to Squirrel Cage drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF and suitable for operation on 400 (+)/-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be at least 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with up to date amendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discahrge (Q) : -Total 6.02 LPS
Or 21.67 Cum/Hour
Total dynamic head : 139.27 Mtr
(a) LWL in sump well (h) : 598.00 mtr
(b) Shaft level : 599.00 Mtr
(c ) Level at discahrge point : 690.00 mtr
(d) Suction lift :- 0.00 mtrs
(e) Residual head : 3.00 Mtr
(f) Static head : 91.00 mtrs
(i) Rising Main :
(a) Length 3450 Mtr
(b) Dia. : 100 mm
(iv) Pumping Hours : 8 Hours
(v) Altitude of installation above MSL : 500.00
(vi) Characteristics of water :
(a) Temperature : 20.00 0 C
(b) Ambient temperature 42.00 0 C
(c ) Turbidity Less than 50.00 ppm
(d) Alkalinity < than Mg/Ca Co3
(e) Size of the solids mm
(f) Other
Providing Side handled operated Change over switch of L&T/Crompton/Standard/ Havells make suitable capacity Operational rating as per IS: 4064-1978 with up to date amendments immediately after the power meter of HPSEB
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-
M.C.B. Havell/L&T/Standard of make of Suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516-1985 with up to date amendments with.
E.L.C.B. of Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition).
Power factor meter of AE/L&T Rishab make as per relevant IS codes with up to date amendments of suitable rating.
Frequency meter of AE/ L&T Rishab make as per relevant IS: Codes with up to date amendments of suitable rating.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments 63 Amp.
ICTP switches with HRC fuses of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064-1978 with up to date amendments.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments.
Providing Hour run meter of recommended make of (0-9999 H) as per IS: 722 (Latest edition)
Capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required rating according to HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of required KVAR range as per IS: 4064-1978 with upto date amendments
Providing suitable oil imersed star dalta starter of MEI/Kilburn make as per IS:8544-1979 with upto date amendments for squarrel cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248(P-V)-1983 with upto date ammendments.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make of 100mm dia for the suction pipe and capable of withstanding the normal seat pressure 10.20 Kg/cm2 as per IS: 780-1984 Class 1.0 with up to date amendments.
Providing double flanged Cast steel sluice valve of Leader/ Kirloskar make and size one dia higher than pump delivery for the delivery line of the pump and capable of with standing the normal seat pressure 52.00 kg/cm2 and as per IS –1414/ API-600(class-ASA-300) with up to date amendments.
Providing double flanged (Swing type) Cast steel reflux valve of Leader/Kirloskar make and one dia dia higher than pump delivery having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure 52.00 kg/cm2 as per IS –1868/ API-600(class-ASA-300) with up to date amendments
Providing double flanged Cast Steel non return valve of Leader/ Kirloskar make and of 100 mm dia having bye pass arrangement for rising main and capable of with standing normal seat pressure 52.00 kg/cm2 as per per IS –1414/ API-600(class-ASA-300) up to date amendments
Providing 100mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52kg/cm2.
Installation of all the items appearing at s.No.39-48 and as per directions and to the entire satisfaction of Engineer-in-charge.
Providing and fixing double flanged MSERW piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing No.2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand including water hammer in delivery side & common header.
The size of the various components to be as under:-
(i) Suction pipe 100 mm dia Min length of 20 mtrs. Flanged with T-5.
(ii) Delivery pipe 80 mm dia Min length of 5 mtrs-MSERW pipe flanged with T-28
(iii) Common Header 100 mm dia Min length of 10 mtrs- MSERW pipe flanged with T-28
And will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/GICO/Grandly /National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: Suitable size
Supply side: Suitable size
Providing and fixing double loop earthing and G.I. plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx6mm G.I. strips & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Intake -II : Point I:- Centriugal pumping machinery
Providing horizontal spindle horizontal split casing/end suctions (back full out arrangement) single/double/ multistage centrifugal pump or combination of pump in series of recommended make such as KSB Mather & Platt/Jyoti/Kirloskar/WASP/Lubi confirming as per BIS-1520-1980 with up to date amendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate ( base plate to be from the manufacturers of the pumping unit only) to Squirrel Cage drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF and suitable for operation on 400 (+)/-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be at least 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with up to date amendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discahrge (Q) : -Total 10.71 LPS
Or Cum/Hour
Total dynamic head : 84.00 Mtr
(a) LWL in sump well (h) : 482.00 mtr
(b) Shaft level : 480.00 Mtr
(c ) Level at discahrge point : 540.00 mtr
(d) Suction lift :- 0.00 mtrs
(e) Residual head : 3.00 Mtr
(f) Static head : 60.00 mtrs
(i) Rising Main :
(a) Length 1800 Mtr
(b) Dia. : 125 mm
(iv) Pumping Hours : 8 Hours
(v) Altitude of installation above MSL : 500.00
(vi) Characteristics of water :
(a) Temperature : 20.00 0 C
(b) Ambient temperature 42.00 0 C
(c ) Turbidity Less than 50.00 ppm
(d) Alkalinity < than Mg/Ca Co3
(e) Size of the solids mm
(f) Other
Providing Side handled operated Change over switch of L&T/Crompton/Standard/ Havells make Suitable capacity Operational rating as per IS: 4064-1978 with up to date amendments immediately after the power meter of HPSEB
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-
M.C.B. Havell/L&T/Standard of make of Suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516-1985 with up to date amendments with.
E.L.C.B. of Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition).
Power factor meter of AE/L&T Rishab make as per relevant IS codes with up to date amendments of suitable rating.
Frequency meter of AE/ L&T Rishab make as per relevant IS: Codes with up to date amendments of suitable rating.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments.
ICTP switches with HRC fuses of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064-1978 with up to date amendments.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments.
Providing Hour run meter of recommended make of (0-9999 H) as per IS: 722 (Latest edition)
Capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required rating according to HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of required KVAR range as per IS: 4064-1978 with upto date amendments
Providing suitable oil immersed star delta starter of MEI/Kilburn make as per IS:8544-1979 with upto date amendments for squarrel cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248(P-V)-1983 with upto date ammendments.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make of 125mm dia for the suction pipe and capable of withstanding the normal seat pressure 10.20 Kg/cm2 as per IS: 780-1984 Class 1.0 with up to date amendments.
Providing double flanged Cast steel sluice valve of Leader/ Kirloskar make and size one dia higher than pump for the delivery line of the pump and capable of with standing the normal seat pressure 21.00 kg/cm2 and as per IS –1414/ API-600(class-ASA-300) with up to date amendments.
Providing double flanged (Swing type) Cast steel reflux valve of Leader/Kirloskar make and one dia dia higher then pump having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure 21.00 kg/cm2 as per IS –1868/ API-600(class-ASA-300) with up to date amendments
Providing double flanged Cast Steel non return valve of Leader/ Kirloskar make and of 125 mm dia having bye pass arrangement for rising main and capable of with standing normal seat pressure 21.00 kg/cm2 as per per IS –1414/ API-600(class-ASA-300) up to date amendments
Providing 100mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-21kg/cm2.
Installation of all the items appearing at s.No.53-62 and as per directions and to the entire satisfaction of Engineer-in-charge.
Providing and fixing double flanged MSERW piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing No.2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head i/c. water hammer (Heavy class) flanged with M.S. flanges of Table - 28 in delivery side & common header.
The size of the various components to be as under:-
(i) Suction pipe 125 mm dia Min length of 20 mtrs.
(ii) Delivery pipe 100 mm dia Min length of 5 mtrs
(iii) Common Header 125 mm dia Min length of 10 mtrs
And will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/GICO/Grandly /National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: Suitable size
Supply side: Suitable size
Providing and fixing double loop earthing and G.I. plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx6mm G.I. strips & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Intake -II : Point N:- Centriugal pumping machinery
Providing horizontal spindle horizontal split casing/end suctions (back full out arrangement) single/double/ multistage centrifugal pump or combination of pump in series of recommended make such as KSB Mather & Platt/Jyoti/Kirloskar/WASP/Lubi confirming as per BIS-1520-1980 with up to date amendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate ( base plate to be from the manufacturers of the pumping unit only) to Squirrel Cage drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF and suitable for operation on 400 (+)/-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be at least 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with up to date amendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discahrge (Q) : -Total 4.31 LPS
Or Cum/Hour
Total dynamic head : 133.92.00 Mtr
(a) LWL in sump well (h) : 478.50 mtr
(b) Shaft level : 480.00 Mtr
(c ) Level at discahrge point : 560.00 mtr
(d) Suction lift :- 0.00 mtrs
(e) Residual head : 3.00 Mtr
(f) Static head : 80.00 mtrs
(i) Rising Main :
(a) Length 2400 Mtr
(b) Dia. : 80 mm
(iv) Pumping Hours : 8 Hours
(v) Altitude of installation above MSL : 500.00
(vi) Characteristics of water :
(a) Temperature : 20.00 0 C
(b) Ambient temperature 42.00 0 C
(c ) Turbidity Less than 50.00 ppm
(d) Alkalinity < than Mg/Ca Co3
(e) Size of the solids mm
(f) Other
Providing Side handled operated Change over switch of L&T/Crompton/Standard/ Havells make Suitable capacity Operational rating as per IS: 4064-1978 with up to date amendments immediately after the power meter of HPSEB
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-
M.C.B. Havell/L&T/Standard of make of Suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516-1985 with up to date amendments with.
E.L.C.B. of Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition).
Power factor meter of AE/L&T Rishab make as per relevant IS codes with up to date amendments of suitable rating.
Frequency meter of AE/ L&T Rishab make as per relevant IS: Codes with up to date amendments of suitable rating.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments 63 Amp.
ICTP switches with HRC fuses of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064-1978 with up to date amendments.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments.
Providing Hour run meter of recommended make of (0-9999 H) as per IS: 722 (Latest edition)
Capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required rating according to HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of required KVAR range as per IS: 4064-1978 with upto date amendments
Providing suitable oil immersed star delta starterof MEI/Kilburn make as per IS:8544-1979 with upto date amendments for squarrel cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248(P-V)-1983 with upto date ammendments.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make of 80mm dia for the suction pipe and capable of withstanding the normal seat pressure 10.20 Kg/cm2 as per IS: 780-1984 Class 1.0 with up to date amendments.
Providing double flanged Cast steel sluice valve of Leader/ Kirloskar make and size one dia higher than pump for the delivery line of the pump and capable of with standing the normal seat pressure 52.00 kg/cm2 and as per IS –1414/ API-600(class-ASA-300) with up to date amendments.
Providing double flanged (Swing type) Cast steel reflux valve of Leader/Kirloskar make and one dia dia higher then pump having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure 52.00 kg/cm2 as per IS –1868/ API-600(class-ASA-300) with up to date amendments
Providing double flanged Cast Steel non return valve of Leader/ Kirloskar make and of 80 mm dia having bye pass arrangement for rising main and capable of with standing normal seat pressure 52.00 kg/cm2 as per per IS –1414/ API-600(class-ASA-300) up to date amendments
Providing 100mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52kg/cm2.
Installation of all the items appearing at s.No.67-76 and as per directions and to the entire satisfaction of Engineer-in-charge.
Providing and fixing double flanged EMSERW piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing No.2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head including water hammer (Heavy class) flanged with M.S. flanges of Table - 5,17. in delivery side & common header.
The size of the various components to be as under:-
(i) Suction pipe 80 mm dia Min length of 20 mtrs.-GI pipe (M) flanged with T-5.
(ii) Delivery pipe 65 mm dia Min length of 5 mtrs- MSERW pipe flanged with T-17
(iii) Common Header 80 mm dia Min length of 10 mtrs MSERW pipe flanged with T-17
And will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/GICO/Grandly /National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: Suitable size
Supply side: Suitable size
Providing and fixing double loop earthing and G.I. plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx6mm G.I. strips & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Intake -III : Point W at Loharli:- Centriugal pumping machinery
Providing horizontal spindle horizontal split casing/end suctions (back full out arrangement) single/double/ multistage centrifugal pump or combination of pump in series of recommended make such as KSB Mather & Platt/Jyoti/Kirloskar/WASP/Lubi confirming as per BIS-1520-1980 with up to date amendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate ( base plate to be from the manufacturers of the pumping unit only) to Squirrel Cage drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF and suitable for operation on 400 (+)/-) 10% volts, 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be at least 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 15% of the duty point head. The motor should be as per IS: 325-1978 with up to date amendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:-
Discahrge (Q) : -Total 8.80 LPS
Or Cum/Hour
Total dynamic head : 169.80 Mtr
(a) LWL in sump well (h) : 512.00 mtr
(b) Shaft level : 513.30 Mtr
(c ) Level at discahrge point : 655.00 mtr
(d) Suction lift :- 0.00 mtrs
(e) Residual head : 3.00 Mtr
(f) Static head : 141.70 mtrs
(i) Rising Main :
(a) Length 2700 Mtr
(b) Dia. : 125 mm
(iv) Pumping Hours : 8 Hours
(v) Altitude of installation above MSL : 500.00
(vi) Characteristics of water :
(a) Temperature : 20.00 0 C
(b) Ambient temperature 42.00 0 C
(c ) Turbidity Less than 50.00 ppm
(d) Alkalinity < than Mg/Ca Co3
(e) Size of the solids mm
(f) Other
Providing Side handled operated Change over switch of L&T/Crompton/Standard/ Havells make Suitable capacity Operational rating as per IS: 4064-1978 with up to date amendments immediately after the power meter of HPSEB
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-
M.C.B. Havell/L&T/Standard of make of Suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516-1985 with up to date amendments with.
E.L.C.B. of Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition).
Power factor meter of AE/L&T Rishab make as per relevant IS codes with up to date amendments of suitable rating.
Frequency meter of AE/ L&T Rishab make as per relevant IS: Codes with up to date amendments of suitable rating.
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments 63 Amp.
ICTP switches with HRC fuses of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064-1978 with up to date amendments.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I&II) with up to date amendments.
Providing Hour run meter of recommended make of (0-9999 H) as per IS: 722 (Latest edition)
Capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required rating according to HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of required KVAR range as per IS: 4064-1978 with upto date amendments
Providing suitable oil immersed star delta starter of MEI/Kilburn make as per IS:8544-1979 with upto date amendments for squarrel cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248(P-V)-1983 with upto date ammendments.
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make of 125mm dia for the suction pipe and capable of withstanding the normal seat pressure 10.20 Kg/cm2 as per IS: 780-1984 Class 1.0 with up to date amendments.
Providing double flanged Cast steel sluice valve of Leader/ Kirloskar make and size one dia higher than pump for the delivery line of the pump and capable of with standing the normal seat pressure 52.00 kg/cm2 and as per IS –1414/ API-600(class-ASA-300) with up to date amendments.
Providing double flanged (Swing type) Cast steel reflux valve of Leader/Kirloskar make and one dia dia higher then pump having bye pass arrangement on the delivery line of pump and capable of with standing normal seat pressure 52.00 kg/cm2 as per IS –1868/ API-600(class-ASA-300) with up to date amendments
Providing double flanged Cast Steel non return valve of Leader/ Kirloskar make and of 125 mm dia having bye pass arrangement for rising main and capable of with standing normal seat pressure 52.00 kg/cm2 as per per IS –1414/ API-600(class-ASA-300) up to date amendments
Providing 100mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52kg/cm2.
Installation of all the items appearing at s.No.67-76 and as per directions and to the entire satisfaction of Engineer-in-charge.
Providing and fixing double flanged MSERW piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing No.2 including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand including water hammer flanged with M.S. flanges of Table -5,17 in delivery side & common header.
The size of the various components to be as under:-
(i) Suction pipe 125 mm dia Min length of 20 mtrs. - GI pipe flanged with T-5.
(ii) Delivery pipe 100 mm dia Min length of 5 mtrs- MSERW pipe flanged with T-28
(iii) Common Header 125 mm dia Min length of 10 mtrs MSERW pipe flanged with T-28
And will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/ IEC/ICC/GICO/Grandly /National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
Motor side: Suitable size 10 Rmt
Supply side: Suitable size 20 Rmt
Providing and fixing double loop earthing and G.I. plate 600mmx600mmx3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25mmx6mm G.I. strips & G.I. wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
sanjeev kumar
Dogra Construction Company Pvt Ltd
Vijay Kumar
KATIANI CONSTRUCTION
Universal Electric Engineers
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .