Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 204 BLDG NO 3 CHAITANYA CHSL S V ROAD SIDDHARTH NAGAR GOREGAON W MUMBAI 400 104 | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance PLOT 1 SECTOR B POCKET 1 LOCAL SHOPPING COMPLEX VASANT KUNJ NEW DELHI 110070 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance PLOT NO 137 2ND FLOOR AVTAR ENCLAVE PASCHIM VIHAR NEW DELHI 110063 | WEST | DELHI | 110063 | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
4 Feb 2021, 3:00 pmClosed
Associate Vice President (ID), HITES
B-14A, Sector 62, NOIDA (UP) 201307
Construction of Linear Accelerator Complex including Bunker and Nuclear Medicine Building in the campus of Pt. B.D. Sharma University of Health Science, Rohtak
2021_HLL_66226_1
HITES/IDN/PGIMS-ROHTAK/2020-21
Open Tender
Construction Works
Works
540 days
Rohtak
Please refer Tender documents.
6 documents required · 6 mandatory
₹10,000
Yes
Payable To HLL Infra Tech Services Limited
Exempted
Noida
8 Mar 2021
6 Jan 2021
5 Feb 2021
6 Jan 2021
4 Feb 2021
6 Jan 2021
6 Jan 2021 - 14 Jan 2021
15 Jan 2021
Amount
Sub- Head - I , Earth Work
Earth work in excavation over areas (exceeding 30 cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, irrespective of lead within the site; disposed earth to be leveled and neatly dressed. All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, irrespective of lead within the site;
Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or stacked materials. All kinds of soil
Supplying and filling in plinth with fine sand under floors, including watering, ramming, consolidating and dressing complete.
Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos /Lindane emulsifiable concentrate of 20%
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc.: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Treatment of soil under floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
Pipes, cables etc exceeding 80 mm dia but not exceeding 300 mm dia
Disposal of surplus excavated earth by mechanical transport including loading unloading and stacking irrespective of lead within the site;
Sub - Head - II , Concrete Work
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size).
1:5:10 ( 1 Cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size)
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five level, excluding the cost of centering, shuttering and finishing : 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5mm nominal size).
Extra for providing and mixing water proofing material in cement concrete work @ 1kg per 50 Kg of cement.
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement :3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand including finishing the top smooth
Sub - Head - III , RCC Work
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete.
Walls ( any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Suspended floors, roofs, landings, balconies and access platform.
Lintles, beams, plinth beams, girders, bressumers and cantilevers.
Columns, Pillars, Piers, Abutments, Posts and Struts.
Stairs, (Excluding landings) except spiral -staircases.
Cornices and mouldings
Weather shade, Chajjas, corbels etc., including edges
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 3.5 m for every additional height of 1 metre or part thereof (Plan area to be measured.) Suspended floors, roofs, landing, beams and balconies (Plan area to be measured).
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo - Mechanically Treated bars
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo - Mechanically Treated bars
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately). All works upto plinth level.
All works above plinth level upto floor V level.
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using fly ash and cement content as per approved design mix, and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately. (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC All works upto plinth level.
All works above plinth level upto floor V level.
Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable /recoverable separately. Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note : Cement content considered in M-30 is @340 kg/ cum)
Add (or deduct) for using extra ( or less) cement in the items of design mix over and above the specified cement content therein.
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical location in load application areas that accommodates multi directional seismic movement without stress to it’s components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self – centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in- Charge . (Material shall confirm to ASTM 6063.) Floor Joint of 100 mm gap
Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In- Charge.The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement.(Material shall confirm to ASTM 6063.) Roof Joint of 100 mm gap
Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates asper ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. All lifting/Shifting arrangements for material equipments labor, temprory working platforms and other incidental as required and during execution of work is deemed to be inclusive of quoted rates nothing extra shall be payable on this account. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement.Material shall confirm to ASTM 6063. Roof Joint of 100 mm gap
Providing and fixing in position Stainless steel Grade 304 plate-1.0 mm thick as per design for expansion joints. 200 mm wide.
Sub- Head IV - Brick Work
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)
Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in : Cement mortar 1:6 (1 cement : 6 Coarse sand)
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 ( 1 cement :4 coarse sand)
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry
Sub Head - V Stone Massonary Work
Stone work (machine cut edges) for wall lining etc. (veneer work) upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade : (To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately) : Red / White sand stone - Exposed face fine dressed with rough backing. 30 mm thick
Providing and fixing stainless steel cramps of required size and shape for anchoring stone wall lining to the backing or securing adjacent stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand), including making the necessary chases in stone and holes in walls wherever required.
Providing and fixing copper pins 7.5 cm long 6 mm diameter for securing adjacent stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand), including making the necessary chases
Stone work, plain in copings, cornices, string courses and plinth courses, upto 75 mm thick in Cement mortar 1:6 (1 cement : 6 coarse sand), including pointing with white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade. Red / White sand stone
Applying breathable, non-reactive, antifungal, and water repellant Silane/Siloxane chemical as approved by Archaeological Survey of India/ Engineer-in-charge, of approved brand and manufacture, diluted with solvent mineral Turpentine oil in the ratio of 1:12 (One part of approved chemical :12 Part of Turpentine oil), on the existing sand stone masonry surface with two or more coats to give uniform application of chemical on the surface, all complete as per direction of Engineer-In-charge (The rate is inclusive of all materials & labours involved except scaffolding
Sub Head - VI Stone /Marble / stone Work
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) for wall lining (veneer work), backing filled with a grout of average 12 mm thick in cement mortar 1:3 (1 cement : 3 coarse sand) including pointing with white cement mortar 1:2 (1 white cement : 2 marble dust) with an admixture of pigment to match the marble shade: (To be secured to the backing by means of cramps, which shall be paid for separately).(Basic rate of Stone to be Rs.1800/- sqm Granite of any colour and shade Area of slab over 0.50 sqm.
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.(Basic rate stone to be Rs.1800/- sqm Granite of any colour and shade Area of slab upto 0.50 sqm
Area of slab over 0.50 sqm.
Extra for fixing marble /granite stone over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive including cleaning etc. complete.
Sub- Head - VII Wood Work & PVC Work
Providing and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters : 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws.
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
Providing and fixing in position metallic single / double, leaf fire check doors and frames at all levels of approved design, finish, tested and certified at CBRI, Roorkee etc. complete in all respect as per specifications and direction of Engineer-In-Charge and consisting of :- a) Door frame shall be Single rebate Grooved profile of size 125 x 60 mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet confirming to IS 2260 & 4351 with grooved seal. Frames shall be Mitered and field assembled with self tabs. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers should be provided on the striking jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be grouted with cement & sand slurry necessary for fire doors on the clear masonry opening. b) Door leaf shall be 46mm thick fully flush double skin door with or without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core with fire rated properitory insulation filler bonded to both faces of sheet with lock seam joints at style edges. All doors shall be factory prepped for receiving apropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a beeding and screws from inside. c)The door frames and door shutters shall be primed with 'H' primer and finished with PU/Powder coated . The shutter would be mounted with SS Ball Bearing Hinges of size 100mm x 75mm x 3.0mm of Iclean ( 4Nos per leaf ),appropriate openings for vision panel glass. Prototype Test certificate for a test carried out earlier at CBRI Roorkee for fire rating of doors, shall be attached along with manufacturers test certificate. d) All door shall be factory made and rate shall include , Fire rated hardwares like hinges, panic bar, door closer,Vision Panel 300mm x 200mm, Glass, lock,handles, coordinator and installation etc. as desired with necessary reinforcement and direction of Engineer in charge. Note:- Surface area of shutter including door frame in elevation (one side Only) shall be measured for payment..
Supply & Fixing of Lead Lined Clean room doors frames and shutters made of Skin pass galvanized Iron sheet (Conform to Base Steel as per IS 513 “D” Quality, Galvanized as per IS 277 with Hot Zinc Coating of 120 grams / Sq.Mtr).with powder coating of thickness 60-65 Microns, frame of 1.60mm thick galvanized steel sheet (Conform to IS 277) formed to Single/double rebate profile of size 100mm X 58mm/ 143x58mm, door frames with a single / multi Layer of Lead sheet varying thickness from 3mm /1mm to 2mm depends on radiation level, the shutter with 1.2 mm thick Galvanized Steel Sheet (Conform to IS 277) formed to provide a 46mm thick fully flush, double skin door shell with Lock Seam joints at stile edges with a single / multi Layer of Lead sheet varying thickness from 3mm /1mm to 2mm depends on radiation level, the lead sheets extend the full width and height of the door, Lead thickness is equal to the shielding in the adjacent wall, the door frames and door shutters are coated with polyester powders of Pure polyester/ epoxy polyester or polyurethane powder for powder coating of thickness 60 – 65 microns, coated with Zinc Phosphate Primer to receive any paint on site or finished with Thermosetting Polyurethane paint of Aliphatic Grade providing high levels of scratch resistance and durability, hardware with Stainless Steel Ball Bearing Butt Hinges 3 mm thick fixed flush to the frame and shutter etc complete for finished item
Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter. The frame shall be finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge . (Cost of SS ball bearing hinges is excluded).
Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 min Fire Rating confirming to IS:3614 (Part II) or EN1634- 1:1999, tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc coating not less than 120gm/m²) duly filled mineral wool insulation having density min 96 kg/m³ and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm of approved make, including applying a coat of approved fire resistant primer or powder coating not less than 30 micron etc all complete as per direction of Engineer-in-charge (panelling to be paid for seperately).
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per direction of Engineer-in-charge. The glass shall be clear, toughened, interlayered, non-wired fire resistant having 11 mm thickness of approved brand with 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments).
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per direction of Engineer-in-charge. The glass shall be clear, toughened, interlayered, non-wired fire resistant having 11 mm thickness of approved brand with 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 15 min of insulation (EI15) and having a sound reduction of 37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category of Impact Resistance as per EN 12600. The glass should be manufactured in UL & TUV audited Facility and including UL-EU Certification.The maximum glazing size cannot be more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report for the complete system (Glazed Door or Partition) will be considered valid only if it contains the stamp and signature of the authorized signatory from the glass manufacturer. (Actual glass size is to be measured at site for payments). Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete
Providing and fixing 250x16mm Stainless steel (Grade 316 ) satin finish sliding door bolts superior quality with necessary SS screws etc. complete:Heavy Duty (i) 250x16mm
Providing and fixing Stainless Steel (Grade-304) tower bolts, ISI marked, matt finish with necessary screws etc. complete 300 x10 mm
Providing and fixing 25mm dia , 300 mm long in cranked / square shape stainless steel (Grade 316 ) satin finish pull handle with necessary screws etc. complete.
Providing and fixing Stainless Steel (Grade-304) hanging floor door stopper, ISI marked matt finish with necessary screws etc. complete. Double rubber stopper
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt / suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S including cost of adhesive of approved quality. 1.00 mm thick
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately).
Supply & fixing of wall guards having vinyl snap on cover (lead free) and bumper of 2mm thickness each and aluminum retainer of 2mm thickness that shall be fabricated from 6063-T5 aluminum having high impact resistance with size 152 mm X 25 mm. The rigid vinyl profile shall resist an impact of 30.4 ft-lbs/ inch as per ASTM D-256-90b and shall not support fungal or bacterial growth in accordance with ASTM G-21. The system shall also confirm to class A fire rating and ASTM D-543 for chemical and stain resistance. The color and design as per engineer incharge
Sub- Head - VIII , Steel Work
Providing and fixing circular / Hexagonal cast iron or M.S sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S sheet box by means of 3.3 mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S bar bent to shape as per standard drawing.
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete Electric resistance or induction butt welded tubes
Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.
Providing and fixing carbon steel galvanised ( minimum coating 5 micron ) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge. 10 x80 mm
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc. including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge. ( for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
Sub- Head - IX FLOORING
Kota stone slab flooring over 20mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 ( 1 cement : 4 coarse sand): 25 mm thick.
Kota stone slabs 25 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm ( average) thick cement mortar 1: 3 ( 1 cement : 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.
Extra for marble stone flooring in treads of steps and risers using single length up to 2.00 metre
Extra for pre finished nosing in treads of steps of Marble stone/ Granite stone slab
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Providing and laying Ceramic anti skid floor tiles of size 450x450 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey,Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4Coarse sand), including pointing the joints with white cement and matching pigment etc, complete.
Providing and laying GVT satin finish vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption's less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with white cement and matching pigments etc., complete. (Note : The tile shall be used laid with 3mm spacer with epoxy grount filling. Necessary deduction for not grounting joint with white cement shall be done. Payment for epoxy grounting of 3mm joint to be made separately under relevant item.The tile shall be laid in pattern/design as approved by Engineer-in- charge,nothing extra shall be payable for same.) Size of Tile 600x600 mm
Providing and laying GVT satin finish vitrified floor tiles in different sizes (thickness to be specified by manufacturer) with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make in all colours & shade in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. (Note : The tile shall be used laid with 3mm spacer with epoxy grount filling. Necessary deduction for not grounting joint with white cement shall be done. Payment for epoxy grounting of 3mm joint to be made separately under relevant item.The tile shall be laid in pattern/design as approved by Engineer-in- charge,nothing extra shall be payable for same.) Size of Tile 600x600 mm Note: - The vitrified tiles for all the above items shall be from the double/multi charged range of tiles.
Deduct for not grouting the joints with white cement and matching pigment in the items of fixing of vitrified tiles.
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados,with adhesive, including pointing in white cement mixed with pigment of matching shade complete. (Note : The tile of minimum size 600x1200mm shall be used.)
Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm
Providing and laying polished granite stone flooring in required design and pattern in linear as well as carvilinear portion of the building, all complete as per the architectural drawings with 18 mm thick stone slab over 20mm average thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc complete as specified and as directed by the engineer in charge . (Basic rate Rs.1800/- sqm Polished granite stone slab jet black, cherry red, elite brown, cat eye or equivalent.
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge (Basic Rate Rs.1000/- sqm Flamed granite stone slab jet black, cherry red, elite brown, cat eye or equivalent.
Providing and fixing conductive vinyl flooring of 2mm thick homogeneous flooring with veined surface pattern and non directional chip texture as per EN649. The tile size should be 615mm x615mm. The floor should have residual indentation of 0.035mm as per EN 433, the light fastness>6 as per ISO105-B02 and electrical resistance should be 5x104<R<106 Ω as per EN1081 for EC. The product should also confirm to Class Bfl-s1 in flammability test as per EN13501-1,slip resistance of R9as per DIN 51130, dynamic coefficient of friction with class DS as per EN13893. The wear group of sheet is M as per EN 660-2. Flooring should have excellent chemical resistanceas per EN423.The joints to be welded with hot welding coils,rate include all material and labour etc. involved complete all as per approval and direction of engineer in charge
Providing and application of self levelling compound in the average thickness 3-4mm with two coats of primer of approved manufacturer in the packaging of 25 kg bags,The work shall be carried out as per manufacturers specifications and as per direction of Engineer in charge.
Providing and fixing Glass mossaic tiles on finished plain wall surface of size 20 mm x 20 mm x 4 mm in all colour, design , fixing in customize design as per direction of Engineer-in- Charge. The glass mosaic tiles to be fixed on the wall surface with the help of approved adhesive applied at the rate of 2.5 kg per sqm and grouting of the same. The rate is inclusive of all operation, material and required pattern approved by Engineer-in-Charge
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge
Sub- Head - X ROOFING
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. Plain bend 87.5 deg 110 mm dia
Shoe (Plain) 110 mm dia
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
Providing and fixing thermal insulation with Resin bonded rock wool conforming to IS: 8183, density 48 kg/m3, 50 mm thick, wrapped in 200 G virgin Polythene bags placed over existing false ceilng and held in position by criss-crossing Gl wire
Supply and installation of polycarbonate multilayered system, a complete assembly of extruded multilayer UV protected polycarbonate panels incorporated into a complete system. Co-extruded UV protected polycarbonate panel system of min 18 mm thick panel of 1200 mm width. Panels shall have six –seven layers with opaque and translucent clear combination as per required lux level with all fixing accessories to ensure best performance for wind uplift, vibration, oil canning and visual appearance. Panels shall be manufactured with vertical offset standing seam at both sides of the panel. Panels shall be fixed on Purlin with snap on connectors with grip lock locking mechanism and will be secured on MS structure (will be paid Separately) with 3 numbers self drilling screws & trapezoid SS fasteners holding the base of the standing seam offering best stability having a pull-out load of min. 7000N (7KN) tested as per ISO 6892:1998 and IS 1608: 2005. Panels to satisfy Dart drop impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a min. of 500 Hours as per ASTM G 155.Panels shall not have Yellowness Index as per ASTM D 1925 of 15 units when tested on a sample exposed to UV for 500 Hours as per ASTM G 155. U value shall not be more than 2.0 W/m2K as per EN ISO 10077-2:2018. Panel shall be with additional End cap / Aluminium U / F Profile / Glazing Bar (mill finish) for ends as required. Panel shall be fixed over M S structural steel / MS purlin (paid separately) conforming to the detail technical specifications as per approved architectural drawings. Trained and factory authorized labour with supervision to complete the entire panel installation as per drawing & direction of the engineer in charge.
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations : Applying a slurry coat of neat cement using 2.75 kg/sqm. of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks /brick bats 25 mm to 115 size wiht 50 % of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer -in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement : 5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of juncitons of walls and slabs. After two days of proper curing applying a second coat of cement slurry using 2.7 kg/sqm of cement admixed with water proofing compound conforming to SI : 2645 and approved by Engineer -in-charge. Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 ( 1 cement : 4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer -in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern fo 300 x 300 mm square 3 mm deep. The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer -in- charge. With average thickness of 120mm and minimum thickness at khurra as 65 mm.
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : Fully Perforated Gypsum Plaster Board of size 1200 x 2400x12.5 mm having approx. 15 % perforated area with perforation size and pattern as approved by the Engineerin- charge and as per manufacturer's specification, with all 4 side tapered and backed by acoustical tissue with NRC value not less than 0.60
Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-incharge. With 20 mm thick beveled tegular mineral fibre false ceiling tile (NRC 0.7)
Sub- Head - XI FINISHING
12 mm cement plaster of mix : 1 : 6 (1 cement : 6 fine sand )
15 mm cement plaster on the rough side of single or half brick wall of mix : 1 : 6 (1 cement : 6 fine sand )
6 mm cement plaster to ceilings of mix : 1 : 3 ( 1 cement : 3 fine sand)
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand).
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Extra for addition of synthetic Polyester triangular fibre of length 6 mm, effective diameter 10-40 microns and specific gravity of 1.34 to 1.40 in cement plaster/mortar by using 125 gms. of synthetic Polyester triangular fibre for 50 Kgs. cement used in cement mortar as per directions of Engineer-in-Charge.
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : Two or more coats on new work\
Distempering with 1st quality acrylic washable distemper having VOC (Volatile Organic Compound) content less than 50 gms/per litre of approved brand and manufacturer including applying additional coats wherever required to achieve even shade and colour . Two or more coats on new work.
Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm.(Note : This item included exterior paint of required shade over textured surface).
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : Water thinnable cement primer
Supply and applying of low VOC , highly washable , water based sanitizing Ultrasatin (D-11205) anti bacterial coating application to all kind of surface and enhancing protection against bacteria for Hygienic environment and conforming to JIS Z 2801:2100 test Protocols for Anti- Bacterial Coatings test. The material should be reactive curing acrylic resin water based coating . The antibacterial painting system shall be one coat of water based arcylic primer after that apply two coats of water based Ultrasatin (D-11205) Anti-bacterial coating over soomth putty surface preparation & scaffolidng , apply by roller/brush/spray as per approved colour & shades, all complete as per manufacturer's specification with the direction of Engineer in charge.
Painting with synthetic enamel paint, having VOC (Volatile Organic Compound) content less than 150 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two coats or more coats.
Sub- Head - XII, Aluminium Work
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of PVC/ neoprene gasket required ( Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the Architectural drawings and the direction of Engineer - in - Charge (Cost of aluminium snap beading shall be paid in basic item) : With float glass panes of 5.50 mm thickness
Providing and fixing fly proof stainless steel grade 304 wire gauge, to Aluminium windows using wire gauge with average width of aperture 1.4 mm in both directions with wire of dia. 0.50 mm all complete. With 12 mm Aluminium U beading.
Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineer-in-charge complete. 355 X 19 mm
Providing & fixing automatic sensor B1_Parting sliding door operator ES200 STD micro processor control unit, automatic door reversal on contact with obstruction, panic closing facility, facility for connecting battery pack, lock, all door parameters load bearing capacity of double/single door for opening of following sizes. (Cost of frameless 12mm thick toughened supersilver green reflecting glass included). Approx. opening size 2400x2400mm
Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawiongs, the aluminium quality as per grade 6063T5or T6 as per BS 1474 including super durable poweder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer -in-Charge The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication extruded aluminium frame work, Nothing extra shall be paid on this account
Designing, fabricating, testing, protection, installing and fixing in position semi(grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels including: (a) Structural analysis, design and preparation of shop drawings for the specified designloads conforming to IS 875 part III (the system nust passed the proof test at 1.5 times design with pressure without any failure including functional design of the aluminium sections for fixing glasing panels of various thickness, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc. structural and weather silicone sealants, flashings, fire stop (barrier)-cum smoke seats, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including : (b) Fabricating and supplying serrated M.S. hot dip galvanished/ aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect vertically and proper fixing of structural glazing system with the RCC/masonry/structural steel framework of building structure using stainless steel anchor fasteeners/bolts, nylon separator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. (c ) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory/work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade brand and manufacturer, as per the approved sealant design, within and all around the perimeter for holding glass. (d) Providing and fixing in position flashings of solid aluminium sheet 1mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it water tight. (e) making provision for drainage of moisture/water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing labour for fabricating and installation of aluminium grid, installation of glazed units T&P scaffolding and other incidental charges including wastage etc. enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design checked and all the shop drawings vetted by the Principals of the structural glazing system. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over the building for occupation. In the end the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required as per the Architectural drawings as per item description as specified as per the approved shop drawings and as directed as specified as per the approved shop drawings and as directed by the Engineer-in-charge. Note :- 1- The cost of providing extruded aluminium frames, shadow boxes, fire stop (barrier)-cum-smoke seals, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub-head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves) on the external face shall be measured in sqm. up to two decimal places. 2- The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 sqm from the certified laboratories accredited by NABL(National Accreditation Board for Testing and Calibration laboratories) Department of Science & Technologies, India. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system : Tests to be conducted in the NABL certified laboratories 1-Performance laboratory Test for air Leakage Test (-50pa to 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1to 200mVhr"l. 2- Static Water Penetration Test (50pa to 1500pa) as per ASTM E-331-09 testing method for a range upto 2000ml" 3- Dynamic Water penetration (50pa to 1500pa) as per AAMA 501.01-05 testing method for a range upto 2000ml 4- Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure without any failure) as per ASTM E-330-10 testing method for a range upto 50mm" 5- Seismic Movement Test (Upto 30mm) as per AAMA 501.4-09 testing method for Qualitative test; Tests to be conducted on site 6- On site Test for Water leakage for a pressure range 50 kpa to 240kpa (35psi) upto 2000ml'
Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade so as to match the colour and shade of the IGUs in the vision panels etc. ,all complete for the required performances as specified, as per the Architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- inCharge.“For payment, only the actual area of glass on face # 1 of the glass panels (but excluding the area of grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (Payment for fixing of Spandrel Glass Panels in the curtain glazing is included in cost of relevent Item*). (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
Sub- Head - XIII, Water Proofing
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of : i) Ist course of applying cement slurry @ 4.4 Kg/sqm mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface ii) IInd course of 20mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 Kg. per sqm of area. iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 Kg/sqm.) iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 Kg/sqm.)
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.
SUB HEAD-XIV External development
Providing and laying in position bitumen hot sealing compound for expansion joints etc. Using grade ‘A’ sealing compound
Providing and applying 2.5mm thick road marking strips ( retro reflective) of specified shade/colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint aplicator machine fitted with profile shoe, glass beads dispenser, propane tank heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirts, seals, oil grease and foerign material etc complete as per direction of engineer in charge and accordance with applicable specifications.
Providing and laying 60mm thick factory made glazed cement concrete interlocking paver block, of any shade, of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.Note :- One row of paver block with tactile pattern shall be provide in the footpath/ Shoulders as per the direction of Engineer - in - charge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete, in position to the required line, level and curvature jointed with cement mortar 1:3 (1 cement :3 coarse sand) including making joints with or without grooves ( thickness of joints except at sharp curve shall not to more than 5 mm) including making drainage opening wherever required complete etc. as per direction of Engineer -in -charge ( Length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer -in -charge.
"Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 20 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required,laying at site, spreading and compacting mechanically by using needle and surface/ screed vibrators, vacuum de-watering process, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints ( 10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars considered under relevant item separately). (Note :- Cement content considered in this item is @ 340 kg/cum & Excess cement beyond this is considered under relevant item). Cement concrete prepared with Automatic batch mixing plant.
Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable /recoverable separately. Providing M-40 grade concrete instead of M-30 grade BMC/RMC. (Note : Cement content considered in M-40 is @360 kg/ cum)
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge With material conforming to Grade-II (size range 53 mm to 0.075 mm ) having CBR Value-25
Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/ cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineer-in- charge.
Providing and Placing in position of PVC membrane sheet of 125 micron thickness in between of CC and DLC work and as per direction of Engineer-in-charge.
Providing and Placing in position of 32mm dia. uPVC pipe sleeves with end cap of length 250 mm for 28mm M.S.Dowel Bar at Road CC work and fixed to the reinforcement with binding wire before pouring concrete etc. complete as per direction of Engineer-in-charge. ( Note: Payment for MS rod shall be done under relevant item)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Mild steel and Medium Tensile steel bars
Supplying and stacking of good earth at site including royalty and carriage upto 5 km complete (earth measured in stacks will be reduced by 20% for payment).
Supply and stacking well decayed cattle manure at site including royalty & carriage for all leads and lift (sludge manure in stacks will be reduced by 8% for payment).
Fine Dressing of the Ground
Spreading of sludge, dump manure and/or good earth in required thickness as per direction of officer-in-charge (cost of sludge, dump manure and/ or good earth to be paid separately).
Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge
Filling mixture of earth and sludge or manure in the desired proportion in trenches , flooding with water and levelling (cost of supplying earth and sludge or manure and mixing excluded)
Flooding the ground with water including making kiaries and dismantling the same.
Supply and stacking of Azadirachta indica ( Neem ) plant of height 120-130cm in big polybag of size 25 cm as per direction of the officer-in-charge.
Supply and stacking of Cassia fistula (Amaltash) plant of height 120-135 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge.
Supply and stacking of Delonix regia (Gulmohar) plant of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge
Providing and stacking of Bauhinia acuminata height 60-75 cm. in earthen pots of size 20 cm as per direction of the officer-in-charge.
Providing and stacking of Caesalpinia pulcherrima species of height 45-60 cm. in earthen pot of size 20 cm as per direction of the officer-in-charge.
Providing and stacking of Hamelia patens of height 90-105 cm. bushy in big size HDPE bags as per direction of the officer-in-charge.
Providing and stacking of Bignonia venusta (Golden shower) of height 30 cm to 45 cm. in 20 cm size of Earthen pots / Plastic pots & as per direction of the officer-in-charge.
Providing. Fabricating and fixing of Aluminium Composite Panel Signages with 3mm thick ACP Sheet, using 25X25 mm MS pipe Frame of approved qualiy with anti rust coating, back with G.I. and 5 Sides with ACP Sheet (alucobond or equivalent approved make), lettering to be done with 5mm Acrylic Sheet and Vinyl's( if Needed), backlit with (Philips or approved equivalent) Slim Lite Tube light Fittings, Acrylic Letters to Protrude out and be lit, together with a timer for switching on and off automatically at night and day including transportation and fixing at site as per the direction of the site engineer.
Providing, fabricating installation and fixing of LED LIT glass finish SS & acrylic letters sides made of 20 gauge SS 304 sheet of required size and shape with neatly fabricated joints properly welded and grinded with all corners rubbed and polished and top made of white imported acrylic sheet with bright white LEDs inside with arrangement of screws in the letters itself for mounting on the walls including cost of screws and fixing complete as per directions of engineer. (max length and max height of each letter to be used for finding area)
Providing & Laying of GrassCrete GC-1,4” Grass Crete formers type , 100 mm deep laid on a consolidated sub-base with a 20mm blinding layer of sand. Steel mesh reinforcement to BS4483 reference A193 (10mm dia), weighing 4.27kgs/m2. Concrete 30MN/m2 at 28 days with air entrainment of 3%. 10mm maximum aggregated and 100mm slump placed around formers and mesh and leveled to tops of formers. Void Former size: 600x600x100mm ,Paving Depth: 100mm Reinforcement: A193 ,Concrete Coverage: 15.50m2/m3 Topsoil Coverage: 18m2/m3
Sub Head – XV Sanitary Installation
Providing, fixing, testing and commissioning of vitreous china wall mounted water closet with dual flush fitting, of flushing capacity 2 litre/ 4 litre including flush pipe, concealed cistern with lid concealo 80 mm, conforming to IS : 7231 with all fittings and fixtures complete, including cutting and making good the wall and floors wherever required. Gap between fixtures and walls shall be filled up with approved polysulphide sealant.
Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS:7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required. White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests.
Providing and fixing matrix set for Handicap toilet consisting of 1 no. EWC with vitreous 10 litre capacity dual flushing system cistern with 1 no. hinged rail of 76 cm, 1 no. wash basin with all fittings and bottle trap, with one pair of mounting brackets and 4 nos. grab rails, 1 no. tower ring and 1 no. paper holder all complete as per the manufacturer's specification
Providing and fixing white vitreous china battery/electric based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water ( 250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge
Providing and fixining frameless urinal partition with 8 mm glass & SS fittings approved make all complete as directed by the Engineer-in-Charge.
Providing and fixing white glazed Vitreous China wash basin under counter basin, with C.I. concealed type brackets fixed to walls with GI rag bolts or approved fasteners etc., including 32 mm CP brass waste coupling inlet connection, including painting of fittings and brackets, cutting and making good the walls wherever required all complete (Granite counter top will be measured and paid separately under relevent item):
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board 510x1040 mm bowl depth 250 mm
Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required : Size 600x450x200 mm
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe 40 mm dia
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
Providing and fixing toilet paper holder: C.P Brass
Providing and fixing soil, waste and vent pipes : 100 mm dia. Hubless centrifugally cast (spun) iron pipe epoxy inside & outside IS: 15905
Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including cost of cutting holes and making good the walls etc. : For 100 mm dia. Pipe
Providing and fixing plain bend of required degree. 100 mm Hubless centrifugally cast (spun) iron pipe epoxy inside & outside IS: 15905
Providing and fixing plain bend of required degree. 100 mm Hubless centrifugally cast (spun) iron pipe epoxy inside & outside IS: 15905
Providing and fixing heel rest sanitary bend 100 mm dia Sand cast iron S&S as per IS - 3989
Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100x100x100 mm Sand cast iron S&S as per IS - 3989
Providing and fixing single equal plain junction of required degree 100x100x100 mm Hubless centrifugally cast (spun) iron epoxy coated inside & outside I.S. 15905
Providing and fixing terminal guard: 100 mm Hubless centrifugally cast (spun) iron epoxy coated inside & outside I.S. 15905
Providing and fixing shielded coupling for hubless centrifugally cast iron pipes 100 mm S S 304 grade coupling with EPDM rubber gasket
Providing and fixing M.S. stays and clamps for sand cast iron/centrifugally cast (spun) iron pipes of diameter : 100 mm
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 100 mm inlet and 100 mm outlet Hubless centrifugally cast (spun) iron pipe epoxy inside & outside IS: 15905
Painting sand cast iron/ centrifugally cast (spun) iron soil, waste vent pipes and fittings with two coats of synthetic enamel paint of any colour such as chocolate grey, or buff etc. over a coat of primer (of approved quality) for new work : 100 mm diameter pipe
Providing and fixing 32mm C.P brass bottle Trap of approved quality & make as per the direction of engineer-in-incharge.
Providing and fixing G.I floor drain consisting of 100x50mm G.I elbow (grating and G.I pipe to be paid separately), complete as per instructions.
Providing and fixing 125 mm dia S.S grating (with or without hole)for , floor or Nahani trap.
Providing and fixing stainless steeel soap dispensser ( heavy trafic ) with all complete as directed by the Engineer-in-Charge.
Providing and fixing CP brass auto closing system basin pillar tap of Jaquar PRS - 031 or Equivalent as approved by Engineer- In Charge
Providing and fixing of 600mm long towel rail , all complete with required acceessories as directed by the Engineer-in-Charge.
Providing and fixing stainless steel hand dryer (Heavy Traffic ) all complete as directed by the Engineer-in-Charge. -in-Charge.
Providing and fixing of G.I soil / waste pipe wall/ under floor , cutting chases and making good with complete. 32 mm dia. nominal bore
40 mm dia. nominal bore
50 mm dia. nominal bore
Providing and fixing 100mm dia G.I. inlet fitting consisting of 100mm dia main G.I pipe with multiple G.I. sockets (Inlets) of required diameter welded to it (as per site requirement) and fixing the same to C.I trap and setting in cement concrete, complete as per instructions of the Engineer in charge.
Sub Head – XVI Water Supply
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work – Exposed on wall. 20 mm dia. nominal bore
25 mm dia. nominal bore
32 mm dia. nominal bore
40 mm dia. nominal bore
50 mm dia. nominal bore
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. 15 mm nominal outer dia Pipes
20 mm nominal outer dia Pipes
25 mm nominal outer dia Pipes
Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. 40 mm dia. nominal bore
50 mm dia. nominal bore
65 mm dia. nominal bore
80 mm dia. nominal bore
providing and fixing Gun metal gate valve with C.I. wheel of approved quality (screwed end) 20 mm nominal bore
25 mm nominal bore
32 mm nominal bore
40 mm nominal bore
50 mm nominal bore
65 mm nominal bore
80 mm nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 25 mm nominal bore
Providing and fixing gun metal non- return valve of approved quality (screwed end) : 50 mm nominal bore Vertical
Supply and fixing 15mm S.S braided connection pipe 450 mm long with wall flange / brass union of approved engineer-in-charge
Providing and fixing C.P. brass overhead shower 105 mm dia round shape multi flow with air effect (ABS Body & face chrome plated ) with rubit cleaning system including shower arm casted 190 mm long flat shap for wll mounted shower with wall flange etc
Providing and fixing 32mm C.P single lever telephonic wall mixer of approved quality & make as per the direction of engineer-in-incharge.15 mm nominal dia
Providing and fixing hand held ablution fitting (health faucet) with one meter long flexible tube and wall hook, all complete approved engineer-in-charge
Supply and fixing of 15mm CP brass 2 Way Bib Cock with wall flange and suitable length CP brass extension pipe all of approved engineer-in-charge
Providing and fixing C.P. brass stop cock (concealed) of approved quality condorming to IS standards 8931. 15 mm nominal bore
Providing and fixing C.P. brass long body bib cock of approved quality condorming to IS standards and weighing not less than 690 gms. 15 mm nominal bore
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality condorming to IS:8931 15mm nominal bore
Supply and fixing 15mm CP brass single lever sink Cock mixer with swinging casted spout wall flange and suitable length CP brass extension pipe all of approved engineer-in-charge.
Providing and fixing C.P. brass wall mounting drinking water fountain tap with wall flange .
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and over flow pipes but without fittings and the base support for tank
Supply, installation, testing & commissioning Portable RO water system with UV suitable Flow rate (preferably 10 to 12LPH) with min. 10 lit water storage,interconnecting piping, valves, cartridge filters, diaphragm type pumps, RO membranes, cable, drain pipe & other related accessories.The system shall be suitable for a supply of 240 V AC / 50 Hz.
Sub Head – XVII Drainage
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not lessthan 4.50 kg and frame to be not less than 2.70 kg as per standard design : 180x150 mm size P type With common burnt clay . (non modular) bricks of class designation 7.5 180x150 mm size P type With common burnt clay . (non modular) bricks of class designation 7.5
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 150 mm dia. R.C.C. Pipe
250 mm dia. R.C.C. pipe
300 mm dia. R.C.C. pipe
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement :4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size),foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size), inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : With common burnt clay (non modular) bricks of class designation 7.5
Constructing brick masonry circular type manhole 0.91m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra depth for circular type manhole 0.91m internal dia (at bottom) beyond 0.91m to 1.67m With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Constructing brick masonry circular type manhole 1.22m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : 1.68m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Extra depth for circular type manhole 1.22m internal dia (at bottom) beyond 1.68m to 2.29m With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design : With 20x20 mm square bar
Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay d.P.S. (non modular) bricks of class designation 7.5
SUB HEAD- XVIII Miscellaneous
Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level. All types of soil 400 mm dia
Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge. 200 mm nominal size dia
Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 200 mm nominal size dia
Supplying, filling, spreading & leveling stone boulders of size range5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.
Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.
Supplying, filling, spreading & leveling coarse sand of sizerange 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in-charge.
Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge.
Providing and fixing factory made precast RCC perforated drain covers, having concrete of strength not less than M-25, of size 1000 x 450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 to 125 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineer-in-charge.
Providing and fixing M.S. clamp of required dia to the top of casing/housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 200 mm clamp
Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). 200 mm dia
Providing and fixing in position precast R.C .C manhole cover and frame of required shape and approved quality. HD - 20 Circular shape 560 mm internal diameter
Sub Head – XIX WTP & Water Supply Pump
Supply, installation, testing and commissioning of continuous duty submersible centrifugal non-clogging drainage pumps complete with 3 phase motor with all necessary protection and mechanical seal etc. complete with all ancillaries etc required.( UGT+STP Floor Drainage pump ) Flow rate : 21.6 cum/hr ( 360 LPM ) Head : 12 Mts Solid Handling : 10 – 12 MM Purpose : Drainage MOC : CI
Design , P&I, hydraulic & layout. Supply, Installation, Testing and commissioning of 50 KLD Water Treatment Plant for domestic puposes, complete as per direction of Engineer in Charge. Filter Feed Pump , 10.0 M3/HR @ 30 MTR , TYPE: HORIZONTAL PUMP - 2 Nos. MSEP Pressurized Multi grade Filter - 1500 mm , MSEP Activeted Cabon Filter - 1500 mm , Pressure Gauge , Butterfly Valve , Flow Meter , Piping and fitting , electrical panel and cavling and cabletray etc
Sub Head – XX : Fire Fighting System
Supply, installation, testing & commissioning of electric driven main fire pump suitable for automatic operation and consisting of following: complete in all respect as required. Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze/ stainless steel impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. 1620 lpm at 56 m Head
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze/ stainless steel impeller with stainless steel shaft,mechanical seal conforming to IS 1520.. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulatedwith 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required Suitable cement concrete foundation duly plastered with anti vibration pads. 1620 lpm at 56 m Head
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze/ stainless steel impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325 M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. 180 lpm at 56 m Head
Supplying and Laying of XLPE insulated, PVC sheathed alluminium conductor 1.1 KV grade armoured U.G Cable, conforming to IS-7098, of following sizes on surface/ in existing cable tray suitably clamped as required 3.5 C X 120 sq.mm
Supplying and laying of XLPE insulated, PVC sheathed stranded copper conductor 1.1 KV grade (un-armoured) cable, conforming to IS-7098, of following size on existing cable tray suitably clamped including termination with copper lugs at both ends as required. 3 core 35 sq.mm
3 core 16 sq.mm
Supplying and making end termination with brass compression gland & Al.lugs for following sizes of XLPE insulated, PVC sheathed Al.conductor cables of 1.1 KV grade as required 3.5 C X120 sq.mm
3x25 sq.mm
Earthing with GI Earth plate 600 mm x 600 mm x 6 mm th.including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe with charcoal or coke and salt complete as required.
Providing & fixing 25 mm x 5 mm G.I. Strip in 40 mm dia GI pipe from earth electrode including connections with GI nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing & fixing 25 mm x 5 mm G.I. Strip in on surface or in recess for connections etc as required.
Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop earthing as required.
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. 300 mm (W) x 50 mm (D) x 1.6 mm (T)
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts,gaskets etc. in ground including welding,excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 80 mm dia
150 mm dia (External line)
Supplying and fixing 63mm dia, 15mtr. Long RRL hose pipe with 63mm dia Male and Female Gun metal couplings duly binded with GI wire, rivets etc. conforming to IS 636 (type-A) as required. Gun Metal
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Gun Metal
Providing & Fixing of MS door made up of 16 gauge MS Sheet capable of accommodating fire hose reel, landing valve, hose pipes, fittings, 1 No. CO2 & 1 No. Dry podwer type portable fire extinguishers,with suitable fireman Axe and complete accessories as per NBC-2016. The door shall have a front glass of thickness 4 mm with lock and key arrangement & shall be painted with one coat of primer & two coat of finished stove enamelled post office red colour paint & "FIRE HOSE" written on front. (Approx. size of door: 2100 mm (H) X 1200 mm (W) X 800 mm (D) or as per NBC-2016 Norms
Supplying and fixing of hose cabinet of size 750mm x 600mm x 250mm made of 2mm thick M.S. sheet with 6mm thick glazed glass door including necessary locking arrangment suitable to accomodate external hydrant with butterfly valve, 2 nos. 15 mtr. long hose pipe, 1 no. branch pipe mounted on wall or raised brick platform and duly painted with post office red externally and white internally with synthetic enamel paint complete in all respect for external hydrant as required.
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 including fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps and painting with two or more coats of synthetic enamel paint of required shade complete as required. 25 mm dia
32 mm dia
40mm dia
50mm dia
65mm dia
80mm dia
100mm dia
150mm dia
200mm dia
Supplying and fixing single headed internal hydrant valve with instantanous Gun metal couplings of 63mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type-A) with blank Gunmetal cap and chain as required Single headed Gunmetal
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gun metal coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal cap and chain as required. Single headed Gunmetal
Supplying, fixing, testing and commissioning of following size butterfly valve (manual) with CI body SS disc nitrile sheet & O-ring & PN 16 pressure rating as specified. 200 mm dia
150 mm dia
100 mm dia
80 mm dia
40 mm dia
Supplying, fixing, testing and commissioning of following size non return valve with dual plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified. 200 mm dia
150 mm dia
100 mm dia
80 mm dia
Supplying and fixing orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing value of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete as per specifications as required.
Supplying, fixing, testing and commissioning of following size Y-Strainer of ductile CI body flanged ends with stainless steel strainer as specified. 150 mm dia
200 mm dia
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipments on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 M
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way-100 mm dia M.S. Pipe
3 way-100 mm dia M.S. Pipe
Supplying and fixing Air Vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia Gun metal wheel valve, with required supporting legs, accessories, pressure gauge and painting with synthetic enamel pain of approved shade as required.
Providing & fixing angle iron (40 mmx 40mm x 5 mm) door frame and M.S. sheet (2 mm thick) cum glass shutter of size 2.1 mtr. X 1.2mtr. (N.S) with 25mm x 25mm x 3mm angle frame all around & stiffened in between i/c hinges, handle, locking arrangement, painting with approved synthetic enamel paint i/c sign writing on glass at internal hydrant including providing & fixing M.S. sheet 2 mm thick on remaining portion above door to close opening i/c painting etc. as required.
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 100 mm dia
150 mm dia
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm andhydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150 mm dia
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000 mm
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required.
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Pendent Sprinkler
Upright Sprinkler
Horizontal side wall Sprinkler
Providing and fixing of ABC powder type fire extinguisher consisting of welded MS cylindrical body squeeze lever discharge valve fitted with pressoer indicating guage, internal discharge tube 30 cms long high pressor discharge hose, discharge nozzle, suspension (confirming to IS 13949 finished externally with red enamel paint and fix to wall with (complete with intrenal dishchage ) capicity 6 kg ISI marked
Providing and fixing Carbon-di-oxide fire extinguishers consisting of welded M.S cylinderical body,squeeze lever discharge valve fitted with internal dischargetube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, confirming to IS : 934 finished externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners complete with internal charge. Capacity 4.5 kg. I.S.I. Marked.
Sub Head - XXI- Internal Electrical Work
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for light/power plug with 2x4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed steel conduit alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light/power plug with 4x4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed steel conduit alongwith 2 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing of following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required including Connector. 1 or 2 Module (75mm X 75mm)
MDB - U - LINAC Block Incoming: 160 A FP MCCB, 25 KA - 1 Nos. 200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set Outgoings: 32 A FP MCCB, 25 KA - 4 Nos. 63 A FP MCCB, 25 KA - 4 No 40 A FP MCCB, 25 KA - 2 No
MDB - P - Nuclear Medicine Block - Main LT Panel conforming to IEC-61439 Incoming: 1600 A, FP ACB - EDO (50 KA) - 1 Nos. 2000 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set Outgoings: 1000 A FP ACB, 50 KA, MDO - 1 Nos. 630 A FP MCCB, 36 KA - 3 Nos. 400 A FP MCCB, 36 KA - 4 Nos. 250 A FP MCCB, 36 KA - 4 Nos. 200 A FP MCCB, 25 KA - 4 Nos. 160 A FP MCCB, 25 KA - 4 Nos. 100 A FP MCCB, 25 KA - 2 Nos 63 A FP MCCB, 25 KA - 5 Nos.
MDB - U - Nuclear Medicine Block Incoming: 160 A FP MCCB, 25 KA - 1 Nos. 200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set Outgoings: 32 A FP MCCB, 25 KA - 4 Nos. 63 A FP MCCB, 25 KA - 2 Nos. 100 A FP MCCB, 25 KA - 2 Nos.
Lift Panel Incoming: 100 A, FP, Automatic Transfer Switch (ATS) - 1 Nos. 200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set Outgoings: 63 A FP MCCB, 25 KA - 4 Nos. 32 A, DP MCB - 4 Nos.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 A, 36 KA,FP MCCB
100 Amp, 36 KA, FP MCCB
Supplying and fixing following way, horizontal type Single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB /RCCB / Isolator) 6 way Double door
Supplying and fixing of following way Horizontal Type three pole & Neutral sheet steel, MCB distribution board 415 V on surface /recess, complete with tinned copper bus bar, neutral bus bar, earth bar,interconnections powder painted including earthing etc.as required. (but without MCB / RCCB / isolator) 8 way (4+ 24), Double door
Supplying and fixing of following ways surface / recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel,dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, base for mounting MCCBs (but without MCBs and incomer MCCB) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required). 4 way (4 + 12), Double door
8 way (4 + 24), Double door
Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc. as required. For 6 way, Double door SPN MCBDB
Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. For 8 way, Double door TPN MCBDB
Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, MCB suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Double Pole
Triple pole
Triple pole and neutral
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
Supplying and fixing TP sheet steel enclosure on surface/ recess along with following Amp 415 V "C" curve TP MCB complete with connections, testing and commissioning etc. as required. 63 amps
Providing and fixing M.V. danger plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with insciption in single red colour on front side as required.
Supplying of PVC sheathed, XLPE insulated Aluminium conductor, Armoured cable of 1.1 KV grade of following sizes conforming to IS: 7098 (Part I). 4 X 10 sq. Mm
4 x 16 sq mm
4 x 25 sq mm
3.5 x 50 sq mm
3.5 x 95 sq mm
3.5 x 120 sq mm
3.5 x 185 sq mm
3.5 x 300 sq mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. Mm
Above 35 sq. mm & upto 95 sq.mm
Above 95 sq. mm & upto 185 sq.mm
Above 185 sq. mm and upto 400 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall/ surface/ cable tray as required. Upto 35 sq. mm (clamped with 1 mm thick saddle)
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Above 95 sq mm and upto 185 sq mm (clamped with 25/40x3mm MS flat clamp).
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq mm (25 mm)
4 x 16 sq mm (28 mm)
3.5 X 25 sq. mm (28mm)
3.5 x 50 sq mm (35 mm)
3.5 x 95 sq mm (35 mm)
3½ X 120 sq. mm (45mm)
3.5 x 185 sq mm (57 mm)
3½ X 300 sq. mm (70mm)
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150 mm dia
Supplying & installing following size of perforated Hot Dipped Galvanized Iron cable trays (galvanization thickness not less than 50 microns) with perforation not more than 17.5% in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts & nuts etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying & installing following size of perforated Hot Dipped Galvanized Iron "Bends" (galvanization thickness not less than 50 microns) with perforation not more than 17.5% in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts & nuts etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying & installing following size of perforated Hot Dipped Galvanized Iron "Tee" (galvanization thickness not less than 50 microns) with perforation not more than 17.5% in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts & nuts etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying & installing following size of perforated Hot Dipped Galvanized Iron "Cross Member" (galvanization thickness not less than 50 microns) with perforation not more than 17.5% in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bolts & nuts etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 62.5 mm depth X 2.0 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
Installation, testing and commissioning of prewired, fluorescent fitting / LED fittings of all types , complete with all accessories and tube etc. directly on ceiling/wall, including connections with 1.5 sq.mm. PVC insulated, copper conductor, single core cable etc. as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep
Extra for fixing the louvers / shutters complete with frame for a exhaust fan of all sizes.
Supplying of following Surface / Recessed LED light Fittings of Wattage as specified below conforming to IS-10322 & IEC-60598 and have a rated system lifetime of 50,000 burning hours minimum at L70 with Unified Glare Rating (UGR<=19) The fixture should be complete with driver and suitable mounting accessories etc. as required as per directions of Engineer-In-Charge. Supplying of LED Recessed/surface Downlighter with a nominal system Wattage <= 8 W, system efficacy at System level (Not Chip Level) >110 Lumens/watt, Life of fixture 50000 hrs @ L70% Lumen maintenance, CCT Range 5700-6500 K, CRI >80, PF >0.95, THD <10%. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. The luminaire shall meet IP20 rating. The luminaire housing should made of pressure die cast aluminium and the luminaire optics shall have a high efficiency diffuser with more than 85% transmittance.The fixture should comply with the parameters as per IS10322.
Supplying of LED Bulkhead with Wattage including driver <= 12 W, Fixture efficacy at System level (Not Chip Level) >100 Lumens/watt, Life of fixture 50000 hrs @ L70% Lumen maintenance, CCT Range 5700-6500 K, CRI >70, PF >0.9, THD <10%. Life of fixture 50000hrs@L70% Lumen maintenance, The luminaire shall meet IP65 rating and IK 08 rating . The luminaire housing should made of High pressure die cast Aluminium/ UV stabilized polycarbonate with polycarbonate front diffuser.
Supplying of LED Batten having length 1150-1250 mm with a nominal system Wattage <= 20 W, Fixture efficacy at System level (Not Chip Level) >110 lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT Range 5700-6500 K, CRI >80, PF >0.95, THD <10%. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70.The luminaire shall meet IP20. The luminaire housing should made of CRCA /extruded Al with diffused optics.
Supplying of LED Recessed/surface Downlighter with a nominal system Wattage <= 12 W,system efficacy at System level (Not Chip Level) >110lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT Range 5700-6500 K, CRI >80, PF >0.95, THD <10%. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. The luminaire shall meet IP20 rating. The luminaire housing should made of pressure die cast aluminium and the luminaire optics shall have a high efficiency diffuser with more than 85% transmittance.The fixture should comply with the parameters as per IS10322.
Supplying of LED Recessed/surface Downlighter with a nominal system Wattage <= 15 W, system efficacy at System level (Not Chip Level) >110lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT Range 5700-6500 K, CRI >80, PF >0.95, THD <10%. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70. The luminaire shall meet IP20 rating. The luminaire housing should made of pressure die cast aluminium and the luminaire optics shall have a high efficiency diffuser with more than 85% transmittance.The fixture should comply with the parameters as per IS10322.
Supplying of LED based 600mm X 600 mm, Surface Mounted Luminaire with minimum system efficacy of 110 lm/W. The luminaire shall have a rated system lifetime of 50000 burning hours @L70B50. The luminaire shall have a IP20 Rating with PF>0.9 and THD<10% an operating Voltage Range of 140 - 270 V. THe luminare housing should be made of aluminium Extrusion with Polycarbonate Diffuser . The total power consumption should not exceed 10 W (including driver).
Supplying of surface/ recessed type (290-300) X (290-300) X (10-15)mm fitting made of CRCA powder quoted finish /PDC Alloy Aluminium with Fully Covered by PMMA Acrylic Diffuser,Wattage <= 14W, Fixture efficacy at System level (Not Chip Level) >=110 lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT Range 5700-6500, CRI >80, PF >0.95, THD <10% an operating Voltage Range of 140 - 270 V. The fixture should comply with the parameters as per IS10322 and IEC60598
Supplying of LED Batten having length 1150-1250 mm with a nominal system Wattage <= 36 W ,Fixture efficacy at System level (Not Chip Level) >=110lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT Range 5700-6500 K, CRI >80, PF >0.95, THD <10%. The luminaire shall have a rated system lifetime of 50,000 burning hours at L70.The luminaire shall meet IP20. The luminaire housing should made of CRCA /extruded Al with diffused optics.
Supplying of Recessed LED luminaire dimension: (L x W) (590- 600)x(590-600) mm fitting made of CRCA powder quoted finish /PDC Alloy Aluminium with Fully Covered by PMMA Acrylic Diffuser, Wattage <= 30W, Fixture efficacy at System level (Not Chip Level) >=110lumens/watt, Life of fixture 50000hrs@L70% Lumen maintenance, CCT Range 5700-6500, CRI >80, PF >0.95, THD <10% an operating Voltage Range of 140 - 270 V.The fixture should comply with the parameters as per IS10322 and IEC60598
Supplying of 5-6 W LED Exit Signage of Red/Green Colour as per site requirement, Light with inbuilt battery backup of 2 hours, including drivers, fixing accessories complete as required. The fixture should have sufficient intensity and all fixing arrangement complete as required at site.
Supplying of Recessed Clean room type LED luminaire dimension: (L x W) (590- 600)x(590-600) mm fitting made of CRCA powder quoted finish /PDC Alloy Aluminium with Fully Covered by PMMA Acrylic Diffuser, UGR <= 19 , Wattage <= 30W, Fixture efficacy at System level (Not Chip Level) >=110lumens/watt, Life of fixture 50000 hrs @ L70% Lumen maintenance, CCT Range 5700-6500, CRI >80, PF >0.95, THD <10%, an operating Voltage Range of 140 - 270 V.The fixture should comply with the parameters as per IS10322 and IEC60598
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, Ceiling Fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Colour - White/ Off white.
Supplying of Exhaust fans Heavy Duty with MS Blades suitable for 230 Volt, 50 Hz, Single phase, A.C. supply and complete with suitable louvres and all standard accessories required. 300 mm dia.
450 mm dia.
Supplying, installation, testing and commissioning of Microwave technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10 A, for mounting height up to 2.6 meter and for 5m X 20m coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Sub Head
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, GI tube, having single prong at top, with 85 mm dia 6 mm thick GI base plate including holes etc. complete as required.
Providing & fixing of G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run)
Providing & fixing of G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run)
Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
Providing and fixing testing joint, made of 20 mm X 3 mm thick GI strip, 125 mm long, with 4 nos. of tinned GI bolts, nuts, chuck nuts and spring washers etc. complete as required.
Providing & fixing 6 SWG dia G.I. Wire on surface or recess for loop earthing as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. TV antena socket outlet
Supplying and laying co-Axial Cable RG-6 grade, 0.7 mm solid copper conductor PE Insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/recessed steel/PVC conduit as required.
Supplying and fixing 20 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 amps “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Providing and fixing 4 Pole, 160 A, MCCB, 25 kA breaking capacity with thermomagnetic release and terminal spreaders in 2 mm thick cubical panel board including ON/ OFF indicating lamps , lock, drilling holes in cubicle panel, making connections, etc. as required.
Sub Head - XXII- External Lighting & Solar Power Generation System
Supplying, Installation, Testing and commissiong of 6 mtr height Hot dip Galvanized Octagonal pole with Single overhang bracket of length upto 2 metre, duly primed and painted. The Octagonal Poles shall be designed to withstand the maximum wind speed as per IS 875.The top loading i.e. area and the weight of fixtures are to be considered to calculate maximum deflection of the pole and the same shall meet the requirement of BSEN 40-2- 1 & 3.The pole shaft shall be made from sheet steel confirming to BSEN 10025 having yield strength of 355 N/sqm and silicon content less than 0.04%.The octagonal Poles shall have door of approximate 500 mm length at the elevation of 500 mm from the Base plate. The door shall be vandal resistance and shall be weather proof to ensure safety of inside connections.There shall not be any circumferential weld joint.The poles shall be hot dip galvanized as per BSEN ISO 1461 standard with average coating thickness of 70 micron. The galvanized mounting bracket shall be supplied along with the Octagonal Poles for installation of the luminaries.The column shall be provided with inbuilt loop box with 4 way 32Amp Heavy duty connector, 1 No SPMCB with wiring from MCB to fitting with 3x1.5 sq.mm PVC / XLPE ARMOURED Cables with COPPER Conductor 1100 V. Grade conrming to IS : 7098 (Pt-1) 1988 and shall have matching flush door,fabricated painted complete with RCC foundation including foundation bolts, suitable DWC / PVC pipe laid within the foundation for incoming and outgoing cables as per the Department's requirement. Top dia - 70mm. Bottom dia - 130mm. Base plate - 200 x 200 x 12mm thick duly welded in column.
Supply, Installation, Testing and Commissioning of "All-in- One" integrated solar street lighting system including the 6 mtr height GI Octagonal Pole, single arm,with 40 W LED luminaire with suitable capacity Solar Panel Module, housing of Die-cast aluminium, UV stabilized polycarbonate cover, Lumen efficacy of complete system not less than 120 lm/W. Luminaire has Integrated MPPT charger with Driver with charger efficiency >90% and should be available in CCT of 5700K. Luminaire should have highly safe & Advanced long life maintenance free Lithium ferro Phosphate (LiFePO4) battery with 2 days Autonomy of entire system along with inbiult PIR sensor with dimming profile. Luminaire should be capable of operating at line voltage without any separate power supply from 100-240 V AC. Lifetime should be at least 50,000 burning hours at L70. Battery charging time should not be more than 1 Day, System shall be IP-65, Operating Temperature range -10 Deg. C to + 55 Deg. C. Civil foundation work including foundation bolts complete, as required is included in this item. Luminaire should be IEC60598-2-3, IS-10322 and other IS/IEC codes as applicable.
Supplying, Installation, Testing and commissiong of 3 mtr high GI Octagonal pole. The column shall be provided with inbuilt loop box with 4 way 32Amp Heavy duty connector, 1 No SPMCB with wiring from MCB to fitting with 3x1.5 sq.mm PVC / XLPE ARMOURED Cables with COPPER Conductor 1100 V. Grade conrming to IS : 7098 (Pt-1) 1988 and shall have matching flush door,fabricated painted complete with RCC foundation including foundation bolts , suitable DWC / PVC pipe laid within the foundation for incoming and outgoing cables as per the Department's requirement.
Supplying, Installation, Testing and commissiong of min 35 watt LED, 5700 K with minimum lumen output of 4000 lumens, diffused LED Post Top lanteran, pressure diecast aluminium alloy housing with corrosion resistance powder coating using nano technology, IP 66 protection fitting, heavy duty copper wound ballst and accessories complete as required. Suitable earthing and Civil foundation work as required is included in the item.
Supplying, Installation, Testing and commissiong of 10 W, 5700 K, IP 66 square decorative LED bollard, with CRI 80, Life of LED 50000K @L70 , PF >0.9 with die cast Aluminium housing with corrosion resistance powder coating using nano technology in approved color suitable for landscape application with control gear of 160mm dia and overall height of 600mm with base flange / plate suitable for mounting above ground level, with foundation complete as required.
Supply,Installation,Testing and Commissioning of min. 60 W LED, 5700 K with minimum lumen output of 7200 lumens, street light luminaries IP:66 made out of die cast Aluminium housing with corrosion resistance powder coating using nano technology in approved color, heat resistant and toughened glass cover, gasket including accessories like copper ballast etc. complete as required to fit onn the pole at site.
Supply, fixing, Testing and Commissioning of Electric Push Button type Boom Barrier of Length (3 - 6) Mtr. at Entry & exit Gates of Complex including Motors & all accessories complete as required at site.
Supply, Installation, Testing and Commissioning of ongrid Solar Photo voltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium /GI structure of suitable strength with following components complete as required:-a) Solar Photo voltaic Module of capacity 330Wp or above, manufactured in India, conforming to IS14286/IEC61215, IS/IEC61730-Part-1, IS/IEC61730-Part-2. Solar Photo voltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants /systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800VDC Input voltage range and 400 VAC, three phase, 4 wire, 50Hz+/-2.5Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d) Fixing of Array junction box & Main junction box with IP65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f)Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel / conduit lugs and other accessories etc. as required.
Sub Head - XXIII - CCTV System
Supply, Installation, Testing & Commissioning of EN & UL approved IR IP 5MP Dome camera with 1/2.9” Progressive Scan CMOS Automatic Varifocal lens 3.2-10 mm DC Iris with motorized focus & zoom, Video Compression :H.265,H.264 and M-jpeg streams with fully configurable 3 streams at camera, sensitivity Color 0.06 lx & Mono 0.02 lx, Built in IR illuminator with 30 m Viewing Distance,Wide Dynamic range minimum 120dB, Resolution 5MP @20FPS/ 4MP@25FPS/ 2MP@30FPS, Ethernet 10/100 Base-T, Extra audio line input and output,onvif profile S, G compliant ,Motion & tamper detection with edge based essential video analytics like Line crossing, Enter / leave field, Follow route, Loitering, Idle / removed object, People counting, Crowd density estimation, 3D tracking , storage over SD Card support up to 2TB, POE Weather rating IP66 and Vandal Rating IK10.
Supply, Installation, Testing & Commissioning of EN & UL approved IR IP 5MP Bullet camera with 1/2.9” Progressive Scan CMOS Automatic Varifocal lens 3.2-10 mm DC Iris with motorized focus & zoom, Video Compression :H.265,H.264 and M-jpeg streams with fully configurable 3 streams at camera, sensitivity Color 0.06 lx & Mono 0.02 lx, Built in IR illuminator with 30 m Viewing Distance,Wide Dynamic range minimum 120dB, Resolution 5MP @20FPS/4MP@25FPS/2MP@30FPS, Ethernet 10/100 Base-T, Extra audio line input and output,onvif profile S, G compliant ,Motion & tamper detection with edge based essential video analytics like Line crossing, Enter / leave field, Follow route, Loitering, Idle / removed object, People counting, Crowd density estimation, 3D tracking , storage over SD Card support up to 2TB, POE Weather rating IP66 and Vandal Rating IK10.
Supply, Installation, Testing & Commissioning of EN & UL approved Outdoor IR 2MP PTZ dome camera , 1/2.8” Progressive Scan CMOS, Full HD(1080p)@60FPS, Lens : 30x Optical Zoom, 4.5 mm - 135 mm (F1.6 - F4.4) , or better, digital zoom : 16x , Video Compression :H.265,H.264 and M-jpeg, Quad streaming with fully configurable 3 streams at camera H.265 mode and 1 M-jpeg ,sensitivity: Color 0.05, Mono 0.01 , wide dynamic range 90dB , Signal to noise ratio > 55 dB ( with AGC off ) , with edge based essential video analytics like line crossing, loitering, idle / removed object detection, crowd density estimation, occupancy and people counting ,IR illumination Range 180 mtrs,Pan range : 360° continuous , Tilt range (-90° to 3°), 256 nos. of presets and 2 nos of guard tour, 10 Base T/100Base-T, multi Streaming H.264, sodium vapour lamp white balance, Intelligent digital noise reduction, storage over SD card, support up to 2TB. PoE support, complete with Power suppply and Mounting accessories Weather Rating IP66, complete as required.
Supply, Installation, Testing and commissioning of Monitor, 43" LED high resolution monitor with high performance 240VAC, 50 Hz. 24x7 for spot display including all accessories as per specifications and as required to complete the system. For CCTV and MATV system
Supply of NVR support up to 32 channels (all channels pre-licensed) Network storage solution with (minimum usable capacity 16TB is required) energy efficient power supply and cooling fans. 2 x Gigabit LAN Ethernet ports for highest speed iSCSI connectivity. It shall offer Remote monitoring via desktop application, browser or SNMP. It shall provide a minimum of 32 concurrent iSCSI connections. Server Configuration Bandwidth 310mbps minimum Processor-Intel N3150 (2 MB Cache, 2.08 GHz) RAM-4 GB, DDR3L‑1333 MHz Hard drives 4 Trays: 3.5-inch SATA Operating temp +10 °C to +35 °C Approved Make- Bosch/Axis/ Sony/Avigilon
Supply, Installation, Testing and commissioning of Client Workstation supports Windows 8.1 /10 (64-bit,Professional or Enterprise),Internet Explorer 11, Intel Core i7 4770 3.4 GHz (up to 3.9 GHz), Minimum 8 GB RAM,1000Base-T,Video resolution 1280x1024 pixels or higher,32 bit 102-key keyboard and mouse.
Video management system software for 200 cameras,5 client work stations and future expendable up to 250 cameras, support integration of third-party cameras, storage and further systems into VMS,Edge Video Content Analysis and centralised recording management, windows based redundent system software architecture,Embedded resilience keeps operations up and running in case both the management server and recording server/s fail etc,complete as required.
Per channel license for 1 Camera expension.
Per channel license for 1 work station expension.
PTZ Control Keyboard with jog shuttle, joystick 38backlit keys, alarm buzzer, 4-axis HID joystick for a smooth PTZ control etc fully programmable and USB Powered.
Server for VMS Application supports Windows Server 2016 (64-bit), Intel Xeon E5-2620v3 (2.4 GHz,6-core, 15MB, 85W) ,with 8GB RAM,15GB Free disc space with Min 1 Gigabit/s network interface card etc.
Sub Head - XXIV - UPS System
Supply, installation, testing, commissioning of microprocessor based UPS System, at 0.95 power factor true online double conversion UPS using PWM IGBT technology, 3 Phase input 430 V + 10 % - 15% and input frequency 50 Hertz plus minus 5%, 3 phase output fixed setting at 380, 415 and 430 V, UPS operating in parallel redundancy mode and each comprising of the following. 125% rated rectifier cum charger unit + 100% rated inverter, integrated in UPS module. Anit harmonic filter at rectifier input for achieving THD < 5% and input power factor of greater than 0.99 or IGBT rectifier. 100% rated galvanic isolation transformer of H-class delta/ Zigzag type at the inverter output .(before static Switch ). 100% rated inbuilt static switch at the inverter output. 100% rated inbuilt static switch at the static bypass line. 100% rated inbuilt Maintenance bypass. 100% rated MCCB having I Thermal, magnetic and automatic U/V trip mechanics. Web-enabled monitoring and management through SNMP protocols for multi-OS environment. RS232/ RS486 BMS connectivity with software. Built in Air circulating fan. Supply, Installation, Testing & commissioning of sealed valve regulated lead Acid batteries (minimum life 2 years) for UPS system, for providing min. 30 minutes backup including interconnecting copper cables as required. Supply/ fixing of matching racks to house batteries for the UPS system including interconnecting copper cables between UPS Unit & batterries. 1 X 40 KVA
Supply, installation, testing, commissioning of microprocessor based UPS System, at 0.95 power factor true online double conversion UPS using PWM IGBT technology, 3 Phase input 430 V + 10 % - 15% and input frequency 50 Hertz plus minus 5%, 3 phase output fixed setting at 380, 415 and 430 V, UPS operating in parallel redundancy mode and each comprising of the following. 125% rated rectifier cum charger unit + 100% rated inverter, integrated in UPS module. Anit harmonic filter at rectifier input for achieving THD < 5% and input power factor of greater than 0.99 or IGBT rectifier. 100% rated galvanic isolation transformer of H-class delta/ Zigzag type at the inverter output .(before static Switch ) 100% rated inbuilt static switch at the inverter output. 100% rated inbuilt static switch at the static bypass line. 100% rated inbuilt Maintenance bypass. 100% rated MCCB having I Thermal, magnetic and automatic U/V trip mechanics. Web-enabled monitoring and management through SNMP protocols for multi-OS environment. RS232/ RS486 BMS connectivity with software. Built in Air circulating fan. Supply, Installation, Testing & commissioning of sealed valve regulated lead Acid batteries (minimum life 2 years) for UPS system, for providing min. 30 minutes backup including interconnecting copper cables as required. Supply/ fixing of matching racks to house batteries for the UPS system including interconnecting copper cables between UPS Unit & batterries. 1 X 60 KVA
Sub Head - XXV - Fire Detection & PA System
Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermister complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Supplying, installation, testing & commissioning of addressable phone control module complete as required.
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying communication links between building management system and fire alarm control panel complete as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
Supplying, installation, testing & commissioning of 6 inches dia, 2 watts, 25/70 volts ceiling speaker complete as required.
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. speaker cable Two pair, 2-core, 1.5 sqmm
Supplying and drawing following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/PVC as required. 2 x 1.5 sq. Mm
Sub Head - XXVI - LAN & EPABX System
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25 mm
Supply, Laying, Installation, Testing and Commissioning of 10G, ETL Verified Category 6A U/UTP Cable, Blue/grey/white/other jacket, LSZH Sheath as per flame rating standard IEC 60332-3-22, IEC 61034-2, IEC 60754-2, 4 pair count, in the existing surface/ recessed steel/ PVC conduit as required.
Supply, Installation, Testing and Commissioning of Cat 6A, 10G Information Outlet, UL Listed, Color Blue (I/O) for Data, Voice & Wi-Fi User end.
Supply , Installtion , Testing and comissioning of 15U wall mount rack with fans, 2 cable managers, satationary shelf, 2 Nos of hardware pkts & 5Nos. 6/16A sockets PDU also complete as required..
Supplying & Installation of Cat 6A-10G, Solid Low Smoke Zero Halogen Cordage Modular Patch Cord as per IEC 60332-3-22, IEC 60754-2, IEC 61034-2, Blue Jacket, 3 Feet (user end)
Supplying & Installation of Cat 6A-10G, Solid Low Smoke Zero Halogen Cordage Modular Patch Cord as per IEC 60332-3-22, IEC 60754-2, IEC 61034-2, Blue Jacket, 7 Feet (Rack end)
Supply, Installation, Testing and Commissioning of Category 6A U/UTP Loaded Patch Panel, 24 port, Intelligent Upgradable for DATA, Voice, CCTV, Wifi etc.
Supply, Installation, Testing and Commissioning of 1 and 2 port, 3X3 , Square faceplate white for I/O fixing at user side.
Supply, Laying, Installation, Testing and Commissioning of 6 core Multi Mode, Outside Plant, Bend Insensitive, Stranded Multi Loose Tube, Gel-Free, Metallic Armored, LSZH, OM4, Telcordia GR-20.
Supply, Installation, Testing and Commissioning of 19" Rack Mount, 12F LIU, 1U Sliding shelf with 4 slots for accepts 4 Nos. of LC Multi mode,OM4 Cassette. loaded with LC Milti Mode, Bend Insensitive Fiber Pigtails & Splice Tray etc.
Supply, Installation, Testing and Commissioning of LC to LC, Multi Mode Fiber Patch Cord, 1.6 mm Duplex, 10 Feet., OM4
Supply, Laying, Installation, Testing and Commissioning of 12 core Single Mode, Outside Plant, Bend Insensitive, Stranded Multi Loose Tube, Gel-Free, Metallic Armored, G.652.D & G.657.A1, OS2, Telcordia GR-20.
Supply, Installation, Testing and Commissioning of 19" Rack Mount, 24F LIU, 1U Sliding shelf with 4 slots for accepts 4 Nos. of LC Single mode, OS2 Cassette. loaded with LC Single Mode, Bend Insensitive Fiber Pigtails & Splice Tray etc.
Supply, Installation, Testing and Commissioning of LC to LC, Single Mode Fiber Patch Cord, 1.6 mm Duplex, 10 Feet., Meet G.652.D & G.657.A1, OS2
SITC of Distribution switch with 24-port 1/10/25G Gigabit Ethernet, 4 x 40/100G uplink ports and integrated redundent power supply. The switches, should be implemented in Active - Active, redundant topology for High Availability with Redundant Power Supply.
SITC of 24 Port 10/100/1000Mbps PoE + 2 ports for optional SFP+/SR Modules supporting 10G, layer 2 switch (Non blocking switch fabric, IPv6 ready), option for RPS
Supply & Installation of dual-band (5 GHz and 2.4 GHz concurrent) & Dual Radio 802.11ac (867Mbps) Wireless Access Point with PoE (802.3af) support/ capability. These indoor AP's should be capable of being used with inline & external power source (Thin & thick AP), with Mounting brackets.
Supplying, installation, testing & commissioning of Pure IP at core Server Based voice Communication System (1+1 HA Mode) with 04 Port Voicemail ,04 Port FXS ,04 Port FXO ,1 PRI Trunk lines (30 Ch) Circuit with CLIP Facility ,100 IP users License , 01 Nos. IP Operator Console,100 Party Conference ,Speed Dial, Music on Hold , Internal/ External ring difference, Call Barring, Call Pickup etc. complete as required.
Supplying, installation, testing & commissioning of Type 1 IP Phone with 1 Voip account, full duplex speaker phone, IPV6 2XLAN PoE complete as required.
Sub Head - XXVII - LIFTS
Sub Head - XXVI - LAN & EPABX System
Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400 V +/- 10%, 3 Phase, 50 Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The scope shall include electrical isolator switches of adequate rating suitable for outdoor application fixed on suitable stand next to each outdoor unit & scope shall also include suitable MS structure, duly painted with primer & 2 coats of approved shade paint alongwith suitable foundation on terrace as per original equipment manufacturers' recommendations. The ODU shall have low noise condenser fans with external static pressure of the outdoor unit shall be more than 75 Pa to avoid hot air recirculation, auto address setting, auto check function for connection error and complete with indoor and outdoor units with individual controller and with fittings etc. The compressor and VRV/VRF Outdoor make should be same. For enhanced energy savings the COP of each refrigerant circuit system mentioned below shall be 7.50 minimum at 50% load, at Outdoor Condition 35 Deg C DBT and Indoor condition: 27 deg C DBT and 19 Deg C WBT in cooling mode. The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respect to load for better comfort and energy efficiency. (Unit shall deliver atleast 87% of mentioned nominal capacity @ 43 Deg C). The Unit should have free phase technology so that unit can work in case of phase reversal also without tripping of units
10 Lb Novec 1230/ FK5-1-12, DLP Assembly with automatic valve mounted on DOT approved cylinder, push in connector for tube, 4 Kg Novec 1230/ FK5-1-12 gas, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation.
Linear pneumatic heat Detection Tube with all necessary fittings & supports.
Master Control Unit with Audio Visual Alarm including wiring to make complete system operational. The Control Panel should have provision for integration with Fire Alarm/SCADA/BMS System.
Sub Head - XXIX - HVAC
Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400 V +/- 10%, 3 Phase, 50 Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. The scope shall include electrical isolator switches of adequate rating suitable for outdoor application fixed on suitable stand next to each outdoor unit & scope shall also include suitable MS structure, duly painted with primer & 2 coats of approved shade paint alongwith suitable foundation on terrace as per original equipment manufacturers' recommendations. The ODU shall have low noise condenser fans with external static pressure of the outdoor unit shall be more than 75 Pa to avoid hot air recirculation, auto address setting, auto check function for connection error and complete with indoor and outdoor units with individual controller and with fittings etc. The compressor and VRV/VRF Outdoor make should be same. For enhanced energy savings the COP of each refrigerant circuit system mentioned below shall be 7.50 minimum at 50% load, at Outdoor Condition 35 Deg C DBT and Indoor condition: 27 deg C DBT and 19 Deg C WBT in cooling mode. The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respect to load for better comfort and energy efficiency. (Unit shall deliver atleast 87% of mentioned nominal capacity @ 43 Deg C). The Unit should have free phase technology so that unit can work in case of phase reversal also without tripping of units
Supply, installation, testing and commissioning of VRV/VRF Cassette Type Round Flow ceiling mounted Indoor units- Sensiflow/ equivalent equipped with, pre-filter, fan section with suitable static fan, multispeed motor suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, coil section with DX coil, electronic expansion valve, outer cabinet, all four independent louvers control, drain pan, drain pump, Occupancy sensor and Floor temperature sensor, insulation, pipe connections, variable evaporative temperature control, necessary supports, vibration isolation, cord less remote control etc. The cassettes units shall have dual sensor which detect the presence of people and floor temperature to provide comfortable air-conditioning and energy saving. The sensor should detects human presence and adjust the airflow direction automatically to prevent drafts. Room temperature should be increase upto 4 deg C/ switch off when no people are detected. The sensor should detects the floor temperature and automatically adjusts the airflow of the indoor unit to reduce the temperature difference between the ceiling and the floor. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System/fire alarm / key card adaptor, so that the unit automatically stops in case of fire or key card removal. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. CKT 1 (20HP) Nuclear Medicine 2 TR Each
3.2 TR Each CKT 2 (20HP) Nuclear Medicine
3.2 TR Each CKT 3 (20HP) Nuclear Medicine
2 TR Each
3.2 TR Each CKT 4 (20HP) Nuclear Medicine
2 TR Each
3.2 TR Each
4 TR Each CKT 5 (18HP) Nuclear Medicine
4 TR Each CKT 6 (16HP) Nuclear Medicine
2 TR Each CKT 7 (16HP) Nuclear Medicine
2 TR Each
4 TR Each CKT 12 (18HP) Nuclear Medicine
2 TR Each CKT 1 (20HP) LINAC
2.8 TR Each
4 TR Each CKT 2 (16HP) LINAC
2 TR Each
4 TR Each
Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. CKT 1 (20HP) Nuclear Medicine 1.3 TR
1.65 TR CKT 2 (20HP) Nuclear Medicine
2 TR CKT 5 (18HP) Nuclear Medicine
1.3 TR CKT 6 (16HP) Nuclear Medicine
1.3 TR CKT 13 (20HP) Nuclear Medicine
1.3 TR CKT 14 (8HP) Nuclear Medicine
2 TR CKT 1 (20HP) LINAC
1.65 TR CKT 2 (16HP) LINAC
Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. CKT 1 (20HP) Nuclear Medicine 1.6 TR (Low static) CKT 12 (18HP) Nuclear Medicine
2.6 TR CKT 13 (20HP) Nuclear Medicine
3.4 TR CKT 1 (20HP) LINAC
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, the scope shall include Y joints & all accessories as per specifications etc. as required : 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
Supply , Installation, Testing and Commissioning of Refrigerant piping (Outside of Building) insulated with Nitrile rubber of 19 mm thickness & then covered with Fiber Glass cloth & UV protective coating. Laminated insulated Refrigerant piping shall be layed in Perforated GI cable tray and covered with raceway, complete in all respects for following size. 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
38.1 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
Supply, Installation, Testing and Commissioning of Y-joints and headers of required sizes for connections of refrigerant pipes to units (Liquid & gas).
DX type VRV/VRF Air Handling units (AHUs) Supply, Installation, Testing and commissioning of factory built floor mounted DX type double skin type horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6 mm outside layer and 0.6 mm inside layer with polyurethane foam (PUF) insulation of density 32(+5%) kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters efficiency 90% down to 10 micron (MERV 8) & Fine filter (Bag filters) efficiency 99% down to 3 micron (MERV 13), belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply or Direct Driven EC motor, suitably designed for variable frequency drive applications, drain connections, stainless steel (18G) drain pan with insulation, silicon coated flexible duct connector, wherever required, necessary vibration isolation arrangement, fresh air damper etc. complete as required of following capacities. Note: The scope shall include 1. AHU control kit complete with EEV( Expansion kit), corded remote, DX cooling coil complete with distributor, return header, etc as required. 2. Each AHU shall have two coils staged one above the other & each coil connected to independent ODU. 3. Refrigerant R-410 A top up. 4. AHU mounted VFD drive complete with incoming electrical isolator in enclosure & DP sensors across filters. 5. The scope shall include UVGI System for AHU to kill microbes growth on the coil and keep the surface clean. UVGI System should be self contained unit. All metallic components in contact with air (wetted parts) shall be of Aluminium. All the lamps should be High Output lamps with 800µW/cm² at 10" from lamp. Full efficiency period of UV tube should not be less than 9,000 Hours. The energy consumed by each lamp based on 441mm length should not exceed 40W. The control panel should have high frequency electronic ballast with high power factor 0.99. The control panel should have lamp on indicators, run hour meter and 5Amp MCB for ON/OFF function for the system. The reflectors should be of high reflectance of minimum 80%. The AHU doors shall be electrically interlocked with UVGI System, so that upon opening of AHU doors the UV tube shall get switched OFF automatically. 6. Contractor shall guarantee maximum canvas temp of 13.5 Deg C or Less for 25 Deg C (return air + fresh air temp.) measured near AHU filters. Air Cap (CMH) Static Pr. (mm) Filtration Class ODU Capacity 10200 65 MERV13 2# x 18HP
6800 65 MERV13 2# x 16HP
Drain Piping Supply, Installation, Testing and commissioning of PVC (minimum 15kg/sq. cm pressure rated) drain water piping complete with fittings (elbows, tees, reducers, sockets, U trap etc.) supports, jointing duct insulated with XLPE class O tubular insulation and any other item required to make the system complete. Nominal diameters of pipe in mms as indicated below: 25 mm dia pipe, Insulation thickness -9 mm
32 mm dia pipe, Insulation thickness -9 mm
40 mm dia pipe, Insulation thickness -9 mm
50 mm dia pipe, Insulation thickness -9 mm
Centralized controller Supply, Installation, Testing and Commissioning of touch screen type centralized controller for controlling, monitoring, scheduling all the indoor units and outdoor units
Supply, Installation & interconnecting of control & transmission Copper conductor wires, FRLS, PVC insulated of size 2C x 1.5 sqmm as required laid in 25 mm PVC conduit.
Supply, installation, testing and commissioning of Duct mounted in-line exhaust air fans comprising of Housing made out of heavy gauge galvanized sheets, DIDW forward curved centrifugal fan complete with internal rotor motor suitable for single phase, 230 volts, 50 Hz required for the exhaust. The fan shall be complete with speed regulator, external gravity louvers, thermal overload release for the motor as well as terminal box for termination of external power supply for the following Capacities. (Toilets) 100 cfm 8 mm static pressure
200 cfm 8 mm static pressure
400 cfm 12 mm static pressure
550 cfm 12 mm static pressure
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Thickness 1.25mm Sheet
Thickness 1.00mm Sheet
Thickness 0.80mm Sheet
Thickness 0.63mm Sheet
Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (class "O") insulation on existing duct after applying two coats of cold setting adhesive (CPR X compound). The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. 25 mm
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
Supplying, fixing, testing & commissioning of powder coated extruded aluminium section fresh air louvers in weather maker room with aluminium volume control dampers, bird screen etc completed as required.
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Fire Damper
Motorised Actuator
VRV / VRF Electrical Panel Supplying, installation, testing & commissioning of cubical type wall / floor mounted Distribution Panel, weather proof suitable for out door application with 415 V, 3-Phase, 4-Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having Suitable Amp capacity extensible type Copper bus bars of high conductivity, SMC bus bar supports, with short circuit withstand capacity of 35kA for I Sec. with entire panel shall have a common earth bus of suitable size at the rear with 2 Nos earth stud, solid connections from main bus bar to switch gears with required size of Copper bus bars and control wiring with 1.5 sq.mm. PVC insulated FRLS copper conductor Single Core cable, cable alleys, cable gland plates in two half, including additional NO/NC contacts in all outgoings for automatic operation through BMS and providing & fixing following switch gears:- Bus Bar: TPN Copper main bus bars and auxiliary bus bars of suitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 35 kA for 1 Sec. Each MCCB shall be with the following. Extended Rotary Operating Handle, Phase Spreader links and Phase barriers. 1 Set - Digital Ammeter with inbuilt ASS, metering C.T.s "CAST RESIN" type, 15VA, and accuracy class-1of 800/5A for measuring current in each phase 1 Set - Digital Voltmeter with inbuilt VSS, with 2Amp. Back up MCB 1 Set - 3 Nos. Phase indication LED lamps with 2Amp back up MCB, Breaker 'ON/OFF' indicating light with 2A MCB, test terminal block set, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. - 2 Set. VRV / VRF Panel (Location Nuclear medicine building Terrace)
Incomer : 1 No. - 630 Amps Four Pole, 36 KA (ICU=ICS) for 1 sec, MCCB with Thermal Magnetic release with O/C, S/C & E/F protection release. Bus Bar: Bus bars of minimum of 800 A capacity (As per capacity of corresponding incoming / Bus couplers). Outgoings Supplying and fixing following outgoing complete connection, inter-connection etc. as required. 63 Amp, 25KA, FP, MCCB - 20 No 40 Amp, 25KA, FP MCCB - 4 No VRV / VRF Panel (Location LINAC building Terrace)
Incomer : 1 No. - 160 Amps Four Pole, 36 KA (ICU=ICS) for 1 sec, MCCB with Thermal Magnetic release with O/C, S/C & E/F protection release. Bus Bar: Bus bars of minimum of 200 A capacity (As per capacity of corresponding incoming / Bus couplers). Outgoings Supplying and fixing following outgoing complete connection, inter-connection etc. as required. 63 Amp, 25KA, FP, MCCB - 6 No 40 Amp, 25KA, FP MCCB - 4 No Supply and laying of following size XLPE insulated, PVC sheathed, Copper conductor, Armoured cable, 1.1 KV grade as per IS-7098, complete with suitable size perforated & hot dip galvanized cable trays, GI/ Aluminium clamps, saddles etc including effective proper termination & connection at both ends with suitable size lugs, glands as required. 4C X 16 sqmm
4C X 10 sqmm
4C X 6 sqmm
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Anurag Enterprises
SG Construction Co.
RMS CONSTRUCTION PVT LTD
SHIVALAYA CONSTRUCTION CO PVT LTD
TRICON REALTECH PRIVATE LIMITED
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .