Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | H1₹1.7 LAccepted-Finance | ₹1.7 L | H1 | Accepted-Finance Responsive |
| 2 | H2₹1.5 L−₹25,424.61 (14.7%)Accepted-Finance | ₹1.5 L−₹25,424.61 (14.7%) | H2 | Accepted-Finance Responsive |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-deficit in experience criteria |
Tender Value
₹2.0 L
EMD Value
₹3,940
Closing Date
30 Jun 2026, 2:30 pmClosed
Executive Engineer, ED-II, Rajbagh,Srinagar
Office Executive Engineer, ED-II, Rajbagh,Srinagar
Supply, Installation, Testing and commissioning of CT/PT unit along with HT bidirectional Meter for 630 KVA dedicated DT of SPS Museum , srinagar
2026_PDD_311405_1
e-NIT No ED-II 02 of 2026-27 dt 2-06-2026
Open Tender
Electrical Works
Percentage
45 days
SPS Museum srinagar
as per SBD
8 documents required · 8 mandatory
₹200
Executive Engineer, ED-II, Rajbagh,Srinagar
₹3,940
29 Jul 2026
3 Jun 2026
2 Jul 2026
5 Jun 2026
30 Jun 2026
6 Jun 2026
5 Jun 2026 - 6 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing and commissioning of CT/PT unit along with HT bidirectional Meter for 630 KVA dedicated DT of SPS Museum , srinagar | - | - | - | - |
| 2 | Loading, unloading,carriage,insurance,Supply,installation,testing and commisioning of below mentioned items of the BOQ | - | - | - | - |
| 3 | 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No G.I channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. | 1 | Job | 74,507 | ₹74,507 |
| 4 | A)Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5.
The CT ratio shall be as 15/5 or 20/5 or 25/5 or 50/50 or 75/5 as per requirement to be verfied by concerned sub-Division.
B)11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute. | 1 | Job | 32,038 | ₹32,038 |
| 5 | Bus Bar details:
A)CTs bus bar:- 40x6 mm copper strip or adequate size
PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size
duly insulated by the monoplast tape
B)PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm² (RYB) and for PT wiring minimum wire size shall be 2.5 mm² (RYB).
C)Copper Lugs preferably ring type duly crimped for termination of wires and tapes D)Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm² | 1 | Job | 8,941 | ₹8,941 |
| 6 | A) 3Ph3 Wire HT CT/PT operated Fully static bidirectional Smart Tri-Vector Energy meters DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc.
B)Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment
C)Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 5) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts - 2 Feet in height with eartning | 1 | Job | 22,352 | ₹22,352 |
| 7 | 3 Core 11 kV Aluminium cable XLPE armoured 185 mm² including cost of clamp for its fixing where ever required. | 20 | mtr | 1,000 | ₹20,000 |
| 8 | Cable termination kits suitable for 3 x 185 mm² XLPE Cable (Indoor/Outdoor) | 4 | Set | 4,698 | ₹18,792 |
| 9 | Earthing by way of 40 mm 2.5 mtr long GI Pipe. Job includes , excavation, enhancement material and Main Hole Chamber (500x450x600)mm with frame and cover. | 2 | Job | 10,230 | ₹20,460 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.78 MB
Tendernotice_2.pdf
PDF • 1.67 MB
NIT02.pdf
Tender Documents • 0.76 MB
SBD2.pdf
Tender Documents • 1.65 MB
SpecsGTP20_compressed.pdf
Additional Documents • 25.50 MB
GTPmeter.pdf
Other Document • 0.13 MB
BOQ_1008352.xls
BOQ • 0.40 MB
extension_notice.pdf
PDF • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .