RequiredCompliance of BoQ specification and supporting document
Eligibility Criteria
Experience
3 yrs
Min Turnover
₹3
Purchase Preferences
MII Purchase Preference
Fee & Financial Details
EMD Fee Amount
₹2.3 L
Important Dates
Last Activity
17 Apr 2025
Published
2 Mar 2023
Bid Opening
23 Mar 2023
Bill of Quantities
Item Wise
GeM BOQ Items (48 items)
Item No
Item Title
Description
Qty
Unit
Consignee
Delivery (days)
Spec
1
Item no 1-i
Supply , Installation , Testing and commissioning of Factory built floor mounted chilled water double skin type horizontal air handling unit made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete woth blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section with 50 mm thick washable synthetic box type pre filters and provision to accommodate electrostatic filters, belt drive package with TEFC drive motor of efficiency class IE 3 suitable for 415 � 10% volts, 50Hz, 3 Phase AC supply suitably designed for VFD applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.) and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, AHU foundation , necessary vibration isolation arrangement etc. complete as per technical specification and of following capacities.
a) 9200 CFM capacity , TSP 65 mmWg
1
Set
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
2
Item no 1-ii
Supply , Installation , Testing and commissioning of Factory built floor mounted chilled water double skin type horizontal air handling unit made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete woth blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section with 50 mm thick washable synthetic box type pre filters and provision to accommodate electrostatic filters, belt drive package with TEFC drive motor of efficiency class IE 3 suitable for 415 � 10% volts, 50Hz, 3 Phase AC supply suitably designed for VFD applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.) and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, AHU foundation , necessary vibration isolation arrangement etc. complete as per technical specification and of following capacities.
b) 13000 CFM capacity , TSP 65 mmWg
2
Set
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
3
Item no 1-iii
Supply , Installation , Testing and commissioning of Factory built floor mounted chilled water double skin type horizontal air handling unit made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete woth blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section with 50 mm thick washable synthetic box type pre filters and provision to accommodate electrostatic filters, belt drive package with TEFC drive motor of efficiency class IE 3 suitable for 415 � 10% volts, 50Hz, 3 Phase AC supply suitably designed for VFD applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.) and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, AHU foundation , necessary vibration isolation arrangement etc. complete as per technical specification and of following capacities.
c) 18500 CFM capacity ,TSP 65 mmWg
1
Set
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
4
Item no 2-i
Supplying, fixing, testing and commissioning of following size BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O ring PN 16 pressure rating for chilled water/hot water circulation including insulation and .63 mm aluminium cladding etc complete as required.
a) 50 mm dia Valve
2
each
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
5
Item no 2-ii
Supplying, fixing, testing and commissioning of following size BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O ring PN 16 pressure rating for chilled water/hot water circulation including insulation and .63 mm aluminium cladding etc complete as required.
b) 80 mm dia Valve
6
each
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
6
Item no 3-i
Supplying, fixing, testing and commissioning of following size Three Way Control Valve in a single body equipped with electronic modulating actuator and digital microcontroller based temperature controller /thermostat working on 2-10 V DC, 4- 20 mA electric signal including control/supply wiring etc complete as required
a) 50 mm dia Valve
1
each
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
7
Item no 3-ii
Supplying, fixing, testing and commissioning of following size Three Way Control Valve in a single body equipped with electronic modulating actuator and digital microcontroller based temperature controller /thermostat working on 2-10 V DC, 4- 20 mA electric signal including control/supply wiring etc complete as required
b) 80 mm dia Valve
3
each
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
8
Item no 4
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of 1.25 mm thick sheet thickness as per IS 655-2006 etc complete as required.
80
sqmtr
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
9
Item no 5-i
Supply, fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring from AHU starter panel and all other accessories including damper/actuator control panel, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per technical specifications.
a) Fire Damper
14
sqmtr
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
10
Item no 5-ii
Supply, fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring from AHU starter panel and all other accessories including damper/actuator control panel, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per technical specifications.
b) Actuator
25
each
Kamlesh Anand
110037,Airports Authorityof India Operational Offices New ATS Complex, IGI Airport, New Delhi-110037
122
Stage Documents
Award of Contract
contract_GEMC-511687792045582.pdf
GEM_CONTRACT • 0.20 MB
contract_GEMC-511687761196632.pdf
GEM_CONTRACT
Documents
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .