Loading…
Loading…
Tender Value
₹1.2 Cr
EMD Value
₹2.4 L
Closing Date
29 Jun 2026, 3:00 pm
Electrical work in connection with Provision of Automatic Block signaling with Centralized Traffic Control (CTC) system Lucknow- Gorakhpur cant section, Upgradation of maintenance facilities of old coaching depot at GKP, Provision of P.P. shelter at 12 Nos. of different station over LJN-DIV, provision of deep tube well with pumphouse at Tulsipur and Barhni of Lucknow Division, Raising of platform from low level to high level at Gangadham PF-1 & 2 & Biseshwarganj PF-1 & 2.
SRDEE-LJN-11-2026
SRDEE-LJN-11-2026
Open
6 Months
Gorakhpur, Uttar Pradesh
₹0
₹2.4 L
2 Jun 2026
2 Jun 2026
15 Jun 2026
A-Electrical work in connection with Provision of Automatic Block
Supply and recessing/fixing of PVC Conduit pipe 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories, junction box, etc including making chase, plastering/ clamping etc as per technical specifications.
Supply and fixing of PVC Conduit pipe on surface 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories, junction box, etc including clamping etc as per required.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 2.5 3 Sq. mm conforming to IS: 694(latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 4.0 4 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 6.0 5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.
Wiring for circuit / sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 10sq. mm+ 1 x 10 sq. mm earth wire.
Supply and Installation of Ceiling rose 3 plate as per IS No. 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification.
Supply of PVC insulated multi stranded copper conductor single core FRLS cable 1.5 8 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for Earth Wire as required as per technical specification including connections, testing and commissioning.
Carting of Material from Railway site supervisor's depot to site (Only for the material supplied by Railway and returning of Released material from site to store depot of Supervisor)
Supply, Erection, Testing and Commissioning of following Modular Type switch 6/10A (1-way) complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 2/3 Pin 6/10A complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular Type switch 16/20A (1-way) complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 5/3 Pin 16/20A complete in all respect.
Supply, Erection, Testing and Commissioning of following Modular type step type Electronic Fan Regulator complete in all respect.
Supply and Erection of Modular type switch blanking set to fill the blank spece White finished mounting cover plate complete in all respect.
Supply and Erection of Fan Sheet Cover POP type complete in all respect including hardware material for fixing.
Supply and Erection of Junction Box cover POP type complete in all respect including hardware material for fixing.
Supply and Erection of white finish single mounting cover plate with base frame suitable 3 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring.
Supply and Erection of white finish single mounting cover plate with base frame suitable 8 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring.
Supply and Erection of white finish single mounting cover plate with base frame suitable 12 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring.
Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 3 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall.
Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 8 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall.
Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 12 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall.
Installation, connection with Twin core PVC insulated flexible copper conductor HRFR 24 cable of size 14/0.193 mm (0.41 Sq. mm) testing and commissioning of 1200/ 1400 mm sweep AC ceiling fan (on the installed CI/MS Box) including earthing as per technical specification. (NOTE:- A.C. Ceiling fan in packed conditions will be supplied by Railways.)
Supply and recessing/fixing on surface of 6 SWG GI wire conforming to IS: 280/2006 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule.
Fabrication and Supply of Ceiling Fan Down Rod 3 feet long fabricated by 12 mm mild steel pipe duly painted with clamp, Fastners, Insulator and split pin complete in all respect
Fabrication, Supply and Fixing of Fan Hook with clamp duly painted made of 50x6 mm MS Flat with nut bolts suitable to fix on PP shelter bracing angle as required.
Installation on Wall/Ceiling with grouting of M.S. Nut Bolts 3/8 inch dia, connection 28 with Twin core PVC insulated flexible copper conductor FRLS cable of size 14/0.193 mm including testing & commissioning of pre-wired indoor LED fitting complete with as per technical specification including earthing complete in all respect. NOTE:- LED fitting will be supplied by Railways in packed conditions.
Supply, Installation, Testing and Commissioning of Earthing with pipe 4.5 meter long 29 and 40 mm dia with masonry enclosure on the top with RCC Cover including earth connection to equipment with 4 mm dia G.I. wire in 15 mm dia G.I. pipe and using salt and charcoal for pipe earth electrode as per drawing L/16/STD/86 as enclosed as per IS 3043/1987 (latest Version).
Supply, erection, testing & commissioning of maintenance free earthing arrangement 30 (Chemical earthing with low impedance, corrosion resistant & long life). Earth electrode is made up of high tensile low carbon steel circular rods bonded with copper on outer surface and interconnection of earth electrode with suitable size copper strip. The earth electrode shall be of minimum 17.0 mm diameter and 3.66 meter length as per details given technical specification
Laying of L. T. Cable of required size in open/air/along wall/ along pole with clamping arrangement conforming to IS:1255/1983 (Latest Version). Cable will be supplied by Railway)
Laying of 1 No. XLPE insulated and PVC sheathed L. T. power cable of grade 1.1 KV size 3½/4 core size exceeding 25 Sq mm but not exceeding to 400/120 sq. mm Alluminium conductor cable direct in ground including excavation, sand cushioning, protective covering and 32 refilling the trench etc. as required. Cable laying should be as per IS-1255/1983 with latest ammendments. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Laying and Fixing of one No. Additional PVC/XLPE Insulated PVC sheathed aluminium conductor L.T. power cable 3½/4 core of grade 1.1 KV of size exceeding 25 Sq. mm but not exceeding 400/120 Sq. mm in ground in the same trench in one tier horizontal formation including 33 excavation, sand cushioning, protective covering and refilling the trench etc. as required. Cable laying should be as per IS-1255/1983 with latest ammendments. Digging of trench in all kinds of soil up to the depth of 1000 mm and 350 mm wide for laying of cable with supply and placing of second- class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Cable will be supplied by Railway)
Supply, Installation, Testing and Commissioning of Busbar Chamber System 63 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Supply, Installation, Testing and Commissioning of Busbar Chamber System 200 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout 35 stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Supply, Installation, Testing and Commissioning of Busbar Chamber System 400 A Rating Four Pole 4 way type conforming to IS:8623 and IS:2147 with latest version busbar layout 36 stack layer type short circuit withstand capacity 35 KA Degree of protection IP 31 fabricated with sheet steel (CRCA) 1.6 mm thickness and epoxy powder coated, bus bar section made of ETP grade copper dull tin plated with DMC support, Neutral bus bar fully rated, top and bottom end plate detachable suitable for 440 V 50 HZ AC Supply complete in all respect.
Installation and Commissioning of LED Street Light/Flood Light fitting on pole including connection with Twin core PVC insulated flexible copper conductor cable of size 1.5 Sq. mm complete in all respect. ( LED Street Light/Flood Light fitting will be supplied by Railway)
Installation, Testing and Commissioning on wall with grouting of MS Nut & bolt 3/8" 38 dia, connection with Twin core PVC insulated flexible copper conductor HRFR cable of size 14/0.193 mm (0.41 Sq. mm) including testing & commissioning of Exhaust fan 300/380/450 mm sweep complete with louver shutters as per Tech. specification including earthing. NOTE:- Exhaust Fan & Louver shutters will be supplied by Railways in packed conditions.
All work pertaining to Horizontal Directional Drilling (HDD)/Boring and trench less cabling. It includes supply, transportation and insertion of self-lubricated HDPE pipe and laying of 39 cable in boring under the track/road by using different sizes of pipes depending on total number of cables will be crossed. The depth of horizontal boring should be 3 mtrs from rail flange/road level. This item will be used for track crossing of running lines.) By using self-lubricated HDPE pipe of 120/125 mm outer dia (PN-6) as per IS:4984 or latest in the bore and the laying of cables in the track/road. (HDPE Pipe shall be supplied by Contractor)
Supply and Laying of G.I. Pipe 50 mm dia. class B ISI marked under road/rail clamping with erected pole or wall as per technical specification for passing cable of different size.
Supply and Laying of G.I. Pipe 80 mm dia. class B ISI marked under road/rail clamping with erected pole or wall as per technical specification for passing cable of different size.
Supply & Laying of 100 mm dia C. I. Pipe (Spun pipe) conforming to IS 1536/2001 with latest amendment class LA & ISI Marked
Cement Concrete Foundation, ratio 1:2:4 with 20 mm and down graded stone aggregate and coarse sand as per site requirement.
Supply, Fabrication and Erection of angle iron 35 x 35 x 5 mm / 40 x 40 x 6 mm / 50x 44 50 x 6 mm conforming to IS: 808/1989 (Latest Version)/M.S. Plate for making structure/ bracket as supporting arrangement for any equiment complete with clamp, nut bolt etc. complete in all respect as per site requirement.
Supplying, fabrication, installing, fixing of MS sheet junction box (outdoor type) size 450x450x200 mm made of 1.6 mm thick M.S. sheet having lockable cover duly painted with gray 45 paint over red oxide primer duly naming 240/415 volts with red paint complete with 3 phase aluminium bus-bar one for neutral with Al. strips 40x10 mm fixed with bus-bar insulators including suitable size of cable gland in bottom side for incoming & outgoing cable and including double earthing stud complete in all respect.
Supply, Installation, Testing and Commissioning of Phase Selector TPN Distribution 46 Board with Metal door powder painted with inbuilt 3 Nos 63 Amp Phase Selector, 100 A copper busbar for each phase and neutral bar duly wired and provision for 8 Module for incomer, 24 module for SP outgoing (8 Way in each phase), earth bar and Din rail etc. conforming to IS: 13032/1991 and IS 8623 (Pt I and III)/1993. along with supply and fixing of 01 No. MCB 63 Amp 4 pole, 10 KA, 230 VAC and 24 No. MCB Single Pole 6/10/16/25 Amp 10 KA, 230 VAC complete in all respect including connection as required
Manufacturing, Supply, Erection, Testing and Commissioning of Feeder Pillar equipped with three phase & Neutral bus bar aluminium capable for 400 Amp capacity for each 47 phase and neutral. Size of fidder panel box 1000 mm height x 600 mm width x 350 mm depth and feeder pillar to be grouted on ground with help of four No. mounting angle of size 50x50x6 mm of length 500 mm the cost should also be include the cost of end cable termination with proper size cable lugs & cable glands.
Supply of Submersible pump set for clear cold and fresh water with radial flow impellers coupled with water filled in multi stage contruction with SS jacket capacity 25.00 HP/18.5 48 KW, suitable for operation on 400 + 10% - 15% Voltage range of three phase AC supply, with discharge of 30 to 75 cubic meter per hour on 108 to 33 meter head respectively with starting method Star Delta with NRV size 75 mm (internal) / 100 (external) complete in all respect with +/- 10 Mtr. tolerance in head and +/- 5% tolerance in discharge.
Installation, Testing and Commissioning of 25.00 HP/18.5 KW capacity submersible pump set with 51 to 60 Mtr. column pipe, sluice valve, reflux valve, supporting clamp, bend, Tee 49 along with the supply of distance piece nipple flanged, reducer, cable clip, holding clamp for pump motor set, rubber packing, nut bolts etc. as required at per site requirement. (Only Submersible Pump, Column pipe, Reflux valve, Sluice valve, Non Return Valve, bend, Tee & Supporting clamp will be supplied by Railway)
Supply, Laying, Testing, and Commissioning of Multistranded flexible flat PVC Sheathed PVC Insulated copper conductor Submersible cable of size 3 core x 10 Sq. mm conforming to IS: 694/1990 (Latest Version).
Supply, Installation, Testing and Commissioning of fully automatic Star-Delta starter, 51 three phase with Single Phase Preventer suitable for 25 HP submersible pump along with over current, dry run, over voltage, under voltage protection etc. and measuring instrument of current & voltage and indication lamp etc complete in all respect.
Supply, Installation, Testing & Commissioning of MCCB 32/63 Amps, 4 pole breaking 52 capacity 25 KA at 415 V,50 Hz, thermal release range 25-32A/50-63 A, Ics = 100% Icu including hard wares and insulators as required along with sheet steel enclosure duly painted complete in all respect.
Fabrication and Supply of Column Pipe class 'C' heavy gauge 100 mm dia conforming IS:1239/Pt-I/1990 - Pt-II/1992 (Latest Version) with flanged at every 3 Mtr. Length with 6/8 Nos holes and slot for cable in flange of size not less than 150 mm.
Supply of Sluice Valve flanged type 100 mm dia complete with had wheel and conforming to IS:780/1980 (Latest Version) ISI marked.
Supply of Reflux Valve flanged type 100 mm dia conforming to IS:5312/1969 (Latest Version) ISI marked.
Supply of Supporting clamp suitable for 100 mm dia column pipe & bear the load of entire raising main & submersible pump.
Supply of C. I. Bend 100 mm dia ISI marked conforming to IS: 1538/1993 (Latest Version).
Supply of C.I. Tee 100 mm dia ISI marked conforming to IS: 1538/1993 (Latest Version).
Supply, Installaion, Testing and Commissioning of SPN MCB Distribution Board 8 Way double door made with 1.2mm thickness CRCA sheet fully powder coated of 50-70 micron with 01 No. MCB 02 Pole 40 Amp 10 KA 230V as incoming and 06 Nos. MCB of 6-20 Amp single pole 10 KA 230 Volt as outgoing complete in all respect including connection as required.
Supply, Erection, Testing and Commissioning of following Modular type Socket with MCB 25 Amps for AC Unit complete in all respect.
Supply and Fixing of Hot Dip galvanized perforated type cable tray 100 mm width and 50 mm height made with 14 SWG Sheet.
Supply and fixing of Hot Dip galvanized type cover plate for 100 mm width cable tray with 18 SWG Sheet.
Supply and Fixing of Coupler plate with hardware for 50 mm Height Hot Dip galvanized/powder coated type cable trays
This item work is mainly consist of Supply, Installation, Testing & Commissioning of 64 LED batten fitting 50 (Relevant & latest IS) watt rated volt -240 V AC, 50 Hz, Operating voltage 160- 300 V & 4 KV surge protection 100 lm/w 5000K. Make- Philips, Bajaj, Havells or other equivalent reputed brand.
Supply, Installation, Testing and Commissioning of 5 Mtr. High Hot dip galvanized octagonal pole with longitudinal seam weld throughout the length with bottom 130 mm across face, 65 Top 70 mm across face made of 3 mm thick High Tensile plate and 200 mm x 200 mm x 12 mm base plate complete with one arm of 300 mm for fitting installation and 04 No. M20 (EN 8 Gr) x 700 mm long J type foundation bolt set complete in all respect with RCC foundation as per attached drawing. The material shall be inspected at manufacturer's premises by RITES and inspection charges shall be borne by the firm.
Supply, Installation, Testing and Commissioning of 7 Mt. High Hot dip galvanized octagonal pole with longitudinal seam weld throughout the length with bottom 130 mm across face, 66 Top 70 mm across face made of 3 mm thick High Tensile plate and 220 mm x 220 mm x 12 mm base plate complete with one arm of 500 mm for fitting installation and 04 No. M20 (EN 8 Gr) x 700 mm long J type foundation bolt set complete in all respect with RCC foundation as per attached drawing.
Dismantling of Damaged Single Rail/Tubular Pole and handed over to concern SSE
Cutting of CC work of Platform/Road for laying of cable and supply of Cement and sand for repairing of the CC work of platform/Road as per the directive of site in charge complete in all respect.
Supply of Double wall corrugated (DWC) pipes for under ground power cable 69 protection with IS:14930 Part - II mark on duly printed at every one meter interval along with the socket coupler with IP 67 protecting for coupling where ever required. The DWC pipe shall be rodent proof and fire resistant and size of outer dia 90 mm and inner dia 76 mm. Material shall be inspected by RITES and the inspection charges any shall be borne by the firm.
Excavation of cable trench of 110 Cm Depth and 30 Cm wide in all kinds of soil and its refilling with the same excavated soft soil.
Laying of DWC pipe (90/76 mm) with socket coupler in trenches as per requirement.
Fabrication, Supply, Installation, Testing and Commissioning of Mobile Charging Station made of 18 mm MDF with Deco Paint Branded Electric wiring with MCB. The Size of the 72 system is Height - 5', Width - 24 ", Base - 30" (It can be customised as per client requirement) The charging station is to charge 24 Nos. of Cell Phone/Laptop together at Single Place (12 Nos. at Each Side) . Branding of Mobile Charging station as desired by Railway.Material shall be inspected by RITES and the inspection charges any shall be borne by the firm.
Supply, Installation, Testing and Commissioning of 12.5 Mtr. Hot dip Galvanized suitable for wind velocity of 44 M/Sec as per IS 875 Part 3 1987 latest version High Mast system 73 alongwith head frame, steel wire rope, double drum winch, galvanized lantern carriage suitable for 8 luminaries & its CG boxes & lightning finial, integral type high powered reversible power tool for raising and lowering of lantern carriage, gear box coupled with the winch & torque limiter, foundation bolt of special steel with nuts washers, anchor plates, templates, LED beam flood light luminaries 200 W, shallow foundation considering the safe soil bearing capacity at site as 10 T/Sq. Mtr. at 2 Mtr Depth, twin dome aviation obstruction light, heavy gauge hot dipped galvanized lighting finals, Feeder Panel comprising main incoming switch MCB's, time switch, contactor, reversing starter and protective system etc. as required and maintenance free Earthing etc.
Supply, Installation, Testing and Commissioning of Station name in 3D letters as in a frame in Hindi, English and Urdu matters (Unit Each means Ht Inches).
Supply, Erection, Testing and Commissioning of LED building contour lighting, IP 67 with aluminium channel and gripping.
Supply, Erection, Testing and Commissioning of floor mounted indoor panel (1 Incomer 630 Amp ACB and out going 2 x 250 Amp, 2 x 100 Amp and 2 x 63 Amp MCCB).
Supply installation testing & commissioning of MCCB 400 Amps , 4 pole breaking 77 capacity 35/36 KA at 415 V,50 Hz, thermal release range 320-400 A, Adjustable short circuit setting 6-10, Ics = 100% Icu including hard wares and insulators as required as per CEE'S Specification No. CEE/Spec./LT-Panel with 400Amp. ACB/06 December - 2008 or latest.
Supply installation testing & commissioning of MCCB 200 Amps , 4 pole breaking 78 capacity 35/36 KA at 415 V,50 Hz, thermal release range 160-200 A, Adjustable short circuit setting 6-10, Ics = 100% Icu including hard wares and insulators as required as per CEE'S Specification No. CEE/Spec./LT-Panel with 400Amp. ACB/06 December - 2008 or latest.
Supply installation testing & commissioning of MCCB 100 Amps , 4 pole breaking 79 capacity 25 KA at 415 V,50 Hz, thermal release range 80-100 A, Ics = 100% Icu including hard wares and insulators as required as per CEE'S Specification No. CEE/Spec./LT-Panel with 400Amp. ACB/06 December - 2008 or latest.
Installation, Testing and Commissioning of 1.5 TR Split type Air Conditioner both indoor and outdoor including fixing arrangement etc. (1.5 /2 TR Air Conditioner will be supplied by Railway)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC-APRIL-2022.pdf
ATTACHMENT
BGFormat-NEW_merged.pdf
ATTACHMENT
EARTHING.pdf
ATTACHMENT
LTPanel.pdf
ATTACHMENT
12.5MtrHighMast.pdf
ATTACHMENT
OCTAPole.pdf
ATTACHMENT
PipeEarth.pdf
ATTACHMENT
ACS 1 10
ATTACHMENT
GCCACS11_compressed.pdf
ATTACHMENT
Exp.TLRBNY.pdf
ATTACHMENT
TCTLRBNY.pdf
ATTACHMENT
GCCACS-01to10_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid