CWE/AF AMB/SAR-T16/2026-27 SPECIAL REPAIR REPLACEMENT OF FOUR POLE STRUCTURE TO RMU AT CERTAIN LOCATIONS AT AF STN SARSAWA UNDER GE AF SARSAWA
2026_MES_781710_1
CWE/AF AMB/SAR-T16/2026-27
Open Tender
Civil Works
Item Rate
180 days
Sarsawa
For MES enlisted contractor Class D Category b ii and for un-enlisted contractor refer NIT
8 documents required · 8 mandatory
₹500
GE (AF) Sarsawa
₹97,680
Yes
30 Jul 2026
30 Jul 2026
22 Aug 2026
30 Jul 2026
20 Aug 2026
14 Aug 2026
30 Jul 2026 - 13 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply install testing and commisioning of 11KV Extensible Outdoor duty (IP 55 enclosure) SF6 gas insulated 3 way motor operated Ring Main Unit comprising of 1 no. 630 Amps Load Break Switch as incomer and 2nos. 630 Amps Vacuum Circuit Breaker as outgoing , cable termination from the front,breaking capacity 21KA/3sec (Internal Arc Classification AFLR 21kA-1sec with Bottom Exhaust both for tank and cable box as per IEC 62271-200), enclosed in robotically welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. Protection CTs shall be ring core type, complete all as specified and directed. The outer enclosure shall have IP 55 protection, it should be Top Opening Canopy type, Indoor RMU placed inside Outdoor Enclosure should not be acceptable. Both the Load break switch and Breaker should have line side earth switch.
Each of the Ring main unit shall comprise of the followings :- | 3 | Each Job | - | - |
| 1.01 | BOQ item No. 1.00 contd...../-
(A) NOTE:- Other details:- System Particulars:-
(i) Nominal System Voltage : 11kV. (ii) Voltage variation on supply side : ±10 %. (iii) Corresponding Highest System Voltage: 12kV. (iv)Frequency : 50 Hz with ± 3 % tolerance. (v) Transient condition : -20 % or + 10 % combined variation of Voltage and frequency. (vi) Number of Phase : 3 Phases. (vii) Neutral earthling :Solidly earthed.
(viii) Fault level (minimum) kA /Sec : 21/3). (ix) Lightning Impulse Withstand Voltage (kVp) : 75 (x) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV (xi) Rated Dynamic Withstand Current (kAp) : 52.5KA. (xii) Number of Short Circuit Operations at rated short circuit current of 21 kA for Breaker - 50 Nos.
(xiii) Earth switch should have 5 closing operation at short circuit current (making operations E2 class) independent of breaker. Earth switch manual closing shall be driven by a fast acting / snap action mechanism,independent of operator and VCB action. (xiv) Side and rear cable entry is not acceptable, all operation, interlock, cable terminations and door shall be front side only. | - | - | - | - |
| 1.02 | BOQ item No. 1.00 contd...../-
(B) Applicable Standards for this RMU scope of work - IEC 62271-200.
(i) The Ring Main Units shall conform to the latest applicable, IEC 62271-100, IEC 62271-200. (ii) All live parts, bus bars, shall preferably be enclosed in non- magnetic and non-ferrite grade stainless steel tank Grade SS441 of minimum 2 mm thickness. The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR with Bottom Exhaust for Safety of Personnel for both Tank as well as Cable Compartment as per IEC62271-200. The outer enclosure shall have IP 55 protection for complete switchgears, however it should be Top Opening Canopy & Indoor RMU placed inside Outdoor Enclosure should not be acceptable. The protection relay shall be for 3 O/C + 1E/F (IDMT Type) Self powered numerical protection relay with low and high set of over current and earth fault , MODBUS communication along with RS 485 Port / USB Port. (iii) Internal Arc Classification should be with Bottom exhaust only. RMUs should be manufactured, inspected, and invoiced from the OEM factory. (iv) Temperature & climatic sensor in each panel, Wireless & Self powered Temperature sensor should be mounted in Busbar & Breaker chamber and the same data should display on the panel. | - | - | - | - |
| 1.03 | BOQ item No. 1.00 contd...../-
(C) Air Insulated Bus Connected Unit comprising the following :-
(1) Air Insulated enclosure with necessary bus connection via bushing. VT’s from the manufacturer and according to IS 3156 shall be accepted.
(2) 11KV/rt3/110V/rt3; 50VA class 0.5. Single phase bus PT for metering.
(3) 11KV/230V AC, 1KVA control transformer – Optional is Aux supply at site is not available.
(4) MFM – EM 6400 NG Class 0.5 for each Incomer.
(5) Metering CT in respective Function’s Cable Compartment in RMU XX/1A, Class 0.5, 2.5 VA.
(D). Accessories :-
(1) Antireflex operating handle.
(2) Battery 24V DC , of suitable rating.
(3) Battery charger (I/P-230V AC, O/P - 24V DC).
(4) Manometer with remote contact.
(E) FRTU per RMU should be provided with provision to send data on SCADA. | - | - | - | - |
| 2 | Supply of 11KV Extensible Outdoor duty (IP 55 enclosure) SF6 gas insulated 4 way motor operated Ring Main Unit comprising of 1 no. 630 Amps Load Break Switch as incomer and 3nos. 630 Amps Vacuum Circuit Breaker as outgoing , cable termination from the front, breaking capacity 21KA/3sec (Internal Arc Classification AFLR 21kA-1sec with Bottom Exhaust both for tank and cable box as per IEC 62271-200), enclosed in robotically welded stainless steel tank having IP67 Degree of Protection, leak rate of SF6 gas less than 0.1% and tested as per IEC 60056/60694/60298. Protection CTs shall be ring core type, complete all as specified and directed. The outer enclosure shall have IP 55 protection, it should be Top Opening Canopy type, Indoor RMU placed inside Outdoor Enclosure should not be acceptable. Both the Load break switch and Breaker should have line side earth switch.
Each of the Ring main unit shall comprise of the followings:- | 1 | Each Job | - | - |
| 2.01 | BOQ item No. 2.00 contd...../-
(A) NOTE:- Other details:- System Particulars:-
(i) Nominal System Voltage : 11kV. (ii) Voltage variation on supply side : ±10 %.
(iii) Corresponding Highest System Voltage: 12kV. (iv) Frequency : 50 Hz with ± 3 % tolerance. (v) Transient condition : -20 % or + 10 % combined variation of Voltage and frequency. (vi) Number of Phase : 3 Phases. (vii) Neutral earthling : Solidly earthed.
(viii) Fault level (minimum) kA /Sec : 21/3). (ix) Lightning Impulse Withstand Voltage (kVp) : 75 (x) One minute dry/wet power frequency withstand voltage primary (kV rms) : 28KV (xi) Rated Dynamic Withstand Current (kAp) : 52.5KA. (xii) Number of Short Circuit Operations at rated short circuit current of 21 kA for Breaker - 50 Nos.
(xiii) Earth switch should have 5 closing operation at short circuit current (making operations E2 class) independent of breaker. Earth switch manual closing shall be driven by a fast acting / snap action mechanism, independent of operator and VCB action. (xiv) Side and rear cable entry is not acceptable, alloperation, interlock, cable terminations and door shall be front side only. | - | - | - | - |
| 2.02 | BOQ item No. 2.00 contd...../-
(B) Applicable Standards for this RMU scope of work - IEC 62271-200.
(i) The Ring Main Units shall conform to the latest applicable, IEC 62271-100, IEC 62271-200. (ii) All live parts, bus bars, shall preferably be enclosed in non- magnetic and non-ferrite grade stainless steel tank Grade SS441 of minimum 2 mm thickness. The RMU shall be type tested for internal arc test of 21KA/1 sec AFLR with Bottom Exhaust for Safety of Personnel for both Tank as well as Cable Compartment as per IEC62271-200. The outer enclosure shall have IP 55 protection for complete switchgears, however it should be Top Opening Canopy & Indoor RMU placed inside Outdoor Enclosure should not be acceptable. The protection relay shall be for 3 O/C + 1E/F (IDMT Type) Self powered numerical protection relay with low and high set of over current and earth fault , MODBUS communication along with RS 485 Port / USB Port. (iii) Internal Arc Classification should be with Bottom exhaust only. RMUs should be manufactured, inspected, and invoiced from the OEM factory. (iv) Temperature & climatic sensor in each panel, Wireless & Self powered Temperature sensor should be mounted in Busbar & Breaker chamber and the same data should display on the panel. | - | - | - | - |
| 2.03 | BOQ item No. 2.00 contd...../-
(C) Air Insulated Bus Connected Unit comprising the following:-
(1) Air Insulated enclosure with necessary bus connection via bushing. VT’s from the manufacturer and according to IS 3156 shall be accepted.
(2) 11KV/rt3/110V/rt3; 50VA class 0.5. Single phase bus PT for metering.
(3) 11KV/230V AC, 1KVA control transformer – Optional is Aux supply at site is not available.
(4) MFM – EM 6400 NG Class 0.5 for each Incomer.
(5) Metering CT in respective Function’s Cable Compartment in RMU XX/1A, Class 0.5, 2.5 VA.
(D). Accessories :-
(1) Antireflex operating handle.
(2) Battery 24V DC , of suitable rating.
(3) Battery charger (I/P-230V AC, O/P - 24V DC).
(4) Manometer with remote contact.
(E) FRTU per RMU should be provided with provision to send data on SCADA. | - | - | - | - |
| 3 | S&F cable jointing kit for 11 KV earthed grade cable, indoor termination heat shrinkable type joints with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified & directed. | 13 | Each | - | - |
| 4 | Dismantling/taking down of steel tubular poles, strut any size complete all as specified & directed. | 16 | Each Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
Tender16.pdf
Tender Documents • 0.86 MB
BOQ_875707.xls
BOQ • 0.61 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].