Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹81.5 LAccepted-AOC 33 CHANDASI HOUSE LANE NO 11 S K PURAM ARYA SAMAJ MANDIR ROAD RPS MORE BAILEY ROAD DANAPUR PATNA BIHAR 801503 | PATNA | PATNA | BIHAR | 801503 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹82.5 L+₹95,143.80 (1.17%)Rejected-Finance 2 EVEREST VIHAR PT T N MISHRA MARG NIRMAN NAGAR JAIPUR 302019 | JAIPUR | RAJASTHAN | 302019 | L2 | Rejected-Finance Other than Lowest | |
| 3 | L3₹82.8 L+₹1.2 L (1.51%)Rejected-Finance SHIV BARI ROAD NEAR KASUMAL HOTEL BIKANER 334003 RAJASTHAN | BIKANER | BIKANER | RAJASTHAN | 334003 | L3 | Rejected-Finance Other than Lowest | |
| 4 | L4₹93.5 L+₹12.0 L (14.7%)Rejected-Finance C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | L4 | Rejected-Finance Other than Lowest | |
| 5 | L5₹99.7 L+₹18.2 L (22.3%)Rejected-Finance H NO 1 8 3 22 4 SURYA NAGAR TADI COMPLEX CHIKKADAPALLY HYDERABAD 500020 | HYDERABAD | HYDERABAD | TELANGANA | 500020 | L5 | Rejected-Finance Other than Lowest |
| Sl No | Description | Qty | Unit | Rasam Engg Co. L2 | M/s Rohit Construction Co. L3 | UNITED AIR COOLING & PROJECTS L5 | SHRI HARI CONSTRUCTION L4 | KIRTIMAN TRADERS L6 | Roy and Sons Infrastructures L1 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply and Installation, testing and commissioning of outdoor type step down transformer 100 KVA, 11/0.433 KV, 3 Phase 50 Hz, ONAN Cooled Oil Immersed Copper wound complete with oil tank including first fill of ISI marked insulating oil up to top level, oil level indicator, breather with Silica gel, lifting hooks, drain valve, air vent valve, tackle wheel with channel and locking arrangement to put on the plinth with external cooling tubes, Core type, delta connected on primary side (HV) and star connected on secondary side LV) in accordance with vector symbol DYN-11 (vector Group-4) with neutral brought out on secondary side (LV Side) OFF load tap Changer with manual voltage regulation 0.433 KV in suitable steps/position on HV side to give output of 0.433 KV on LV side and provision of following accessories and connecting with electrical system, earthing etc. including all jointing materials, all as per IS 1180-2014 and energy efficiency level-II including filling of transformer oil having confirming to IS : 335-1993 of dyelectric strength more than 50KV complete all as specified and directed by Engineer -in- Charge and shall comprise of the following accessories as per manufactures direction :-
(a) 03 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nut and washers on primary(HV) side with HV Cable box (without cable Gland). | 11 | EACH JOB | 4,60,000 ₹50,60,000 Lowest | 4,70,000 ₹51,70,000 | 6,12,000 ₹67,32,000 | 5,35,000 ₹58,85,000 | 6,90,000 ₹75,90,000 | 4,90,000 ₹53,90,000 |
| 1.01Item No. 1.00 Contd ..... (b) 4 Nos porcelain bushings with brass/gun metal bushing rods complete with nut and washers on secondary(LV) side suitable for XLPE LT Cable with LV Cable Box (without Cable Gland) (c) Oil conservator with filter type drain valve and oil level gauge oil filter hole with caps/plugs and breather assemby. (d) De-hydrating breather with first fill dehydration agent (Silica gel). (e) Explosive vent. (f) Thermometer pocket on tank cover. (g) One No 100MM dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having minimum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals to be provided diagonally on either side of transformer body to facilitate fixing of 50x6 mm galvanised iron earth strip for body earthing. (j) Name plate and terminal marking . (k) Oil drain filter valve. (l) Lifting lugs. (m) Oil filling hole with cap/plug with conservative tank. (n) Four plain solid cast steel detachable rockters. (o) Provision of 2 Nos danger boards 250/200 mm size made out of 1.6 mm thick plate, vitreous enamel white, with letters figures of voltage and conventional skall and benes in signal red colours on front side. The rear side of the plate also be enamelled. (p) Any other fittings/accessories so as to confirm the whole transformer to 1180 : 2014. (q) Off load changer of range (+) 7.5% to (-) 7.5% instep of 2.5% each, 7 steps. | |||||||||
| 2.00 | Supply and Installation, testing and commissioning of outdoor type step down transformer 160 KVA, 11/0.433 KV, 3 Phase 50 Hz, ONAN Cooled Oil Immersed Copper wound complete with oil tank including first fill of ISI marked insulating oil up to top level, oil level indicator, breather with Silica gel, lifting hooks, drain valve, air vent valve, tackle wheel with channel and locking arrangement to put on the plinth with external cooling tubes, Core type, delta connected on primary side (HV) and star connected on secondary side LV) in accordance with vector symbol DYN-11 (vector Group-4) with neutral brought out on secondary side (LV Side) OFF load tap Changer with manual voltage regulation 0.433 KV in suitable steps/position on HV side to give output of 0.433 KV on LV side and provision of following accessories and connecting with electrical system, earthing etc. including all jointing materials, all as per IS 1180-2014 and energy efficiency level-II including filling of transformer oil having confirming to IS : 335-1993 of dyelectric strength more than 50KV complete all as specified and directed by Engineer -in- Charge and shall comprise of the following accessories as per manufactures direction :-
(a) 03 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nut and washers on primary(HV) side with HV Cable box (without cable Gland).
(b) 4 Nos porcelain bushings with brass/gun metal bushing rods complete with nut and washers on secondary(LV) side suitable for XLPE LT Cable with LV Cable Box (without Cable Gland) (c) Oil conservator with filter type drain valve and oil level gauge oil filter hole with caps/plugs and breather assemby. | 2 | EACH | 6,25,000 ₹12,50,000 | 6,90,000 ₹13,80,000 | 7,44,600 ₹14,89,200 | 8,20,000 ₹16,40,000 | 7,50,000 ₹15,00,000 | 5,90,000 ₹11,80,000 Lowest |
| 2.01Item No. 2.00 Contd ..... (d) De-hydrating breather with first fill dehydration agent (Silica gel). (e) Explosive vent. (f) Thermometer pocket on tank cover. (g) One No 100MM dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having minimum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals to be provided diagonally on either side of transformer body to facilitate fixing of 50x6 mm galvanised iron earth strip for body earthing. (j) Name plate and terminal marking . (k) Oil drain filter valve. (l) Lifting lugs. (m) Oil filling hole with cap/plug with conservative tank. (n) Four plain solid cast steel detachable rockters. (o) Provision of 2 Nos danger boards 250/200 mm size made out of 1.6 mm thick plate, vitreous enamel white, with letters figures of voltage and conventional skall and benes in signal red colours on front side. The rear side of the plate also be enamelled. (p) Any other fittings/accessories so as to confirm the whole transformer to 1180 : 2014. (q) Off load changer of range (+) 7.5% to (-) 7.5% instep of 2.5% each, 7 steps. | |||||||||
| 3.00 | Supply and Installation, testing and commissioning of outdoor type step down transformer 250 KVA, 11/0.433 KV, 3 Phase 50 Hz, ONAN Cooled Oil Immersed Copper wound complete with oil tank including first fill of ISI marked insulating oil up to top level, oil level indicator, breather with Silica gel, lifting hooks, drain valve, air vent valve, tackle wheel with channel and locking arrangement to put on the plinth with external cooling tubes, Core type, delta connected on primary side (HV) and star connected on secondary side LV) in accordance with vector symbol DYN-11 (vector Group-4) with neutral brought out on secondary side (LV Side) OFF load tap Changer with manual voltage regulation 0.433 KV in suitable steps/position on HV side to give output of 0.433 KV on LV side and provision of following accessories and connecting with electrical system, earthing etc. including all jointing materials, all as per IS 1180-2014 and energy efficiency level-II including filling of transformer oil having confirming to IS : 335-1993 of dyelectric strength more than 50KV complete all as specified and directed by Engineer -in- Charge and shall comprise of the following accessories as per manufactures direction :-
(a) 03 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nut and washers on primary(HV) side with HV Cable box (without cable Gland).
(b) 4 Nos porcelain bushings with brass/gun metal bushing rods complete with nut and washers on secondary(LV) side suitable for XLPE LT Cable with LV Cable Box (without Cable Gland) (c) Oil conservator with filter type drain valve and oil level gauge oil filter hole with caps/plugs and breather assemby. | 1 | EACH | 9,50,000 ₹9,50,000 | 9,00,000 ₹9,00,000 | 9,07,800 ₹9,07,800 | 10,00,000 ₹10,00,000 | 9,00,000 ₹9,00,000 | 7,40,000 ₹7,40,000 Lowest |
| 3.01Item No. 3.00 Contd ..... (d) De-hydrating breather with first fill dehydration agent (Silica gel). (e) Explosive vent. (f) Thermometer pocket on tank cover. (g) One No 100MM dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having minimum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals to be provided diagonally on either side of transformer body to facilitate fixing of 50x6 mm galvanised iron earth strip for body earthing. (j) Name plate and terminal marking . (k) Oil drain filter valve. (l) Lifting lugs. (m) Oil filling hole with cap/plug with conservative tank. (n) Four plain solid cast steel detachable rockters. (o) Provision of 2 Nos danger boards 250/200 mm size made out of 1.6 mm thick plate, vitreous enamel white, with letters figures of voltage and conventional skall and benes in signal red colours on front side. The rear side of the plate also be enamelled. (p) Any other fittings/accessories so as to confirm the whole transformer to 1180 : 2014. (q) Off load changer of range (+) 7.5% to (-) 7.5% instep of 2.5% each, 7 steps. | |||||||||
| 4.00 | M&L for bore earthing not less than 250 mm dia 16 feet deep filled with black soil up to 7 feet from bottom complete with galvanized iron pipe 40 mm bore medium grade 3 meter long tapers at bottom & provided 12 mm holes (staggered) at 75 mm centre to centre up to 2.5 meter of length from bottom , burried directly in ground filled with 45 cm alternate layer of chemical magnisium sulphate & salt and Charcoal up to ground level connected to galvanized iron strip 32 x 6 mm as earthing lead by means of bolt and nut, check nuts and washer of galvanized iron or steel including brazing work and 40mm dia light grade pipe for earth lead protection including all necessary earth work, excavation, earth chamber with PCC 1:3:6, type C1 and RCC chamber cover of PCC 1:2:4 with handle and 20mm dia GI watering pipe with funnel and wire mesh etc and testing on complete all as specified and directed by Engineer -in- Charge. | 51 | EACH JOB | 12,500 ₹6,37,500 | 10,000 ₹5,10,000 | 8,500 ₹4,33,500 | 9,000 ₹4,59,000 | 10,000 ₹5,10,000 | 8,000 ₹4,08,000 Lowest |
| 5.00 | S&F galvaniased iron (GI) strip 32mm x 6 mm buried in ground/ Passed through pipe including connected by means of exothermic brazing, nuts and bolts where required complete all as specified and directed by Engineer -in- Charge | 130 | RM | 200 ₹26,000 | 160 ₹20,800 | 85 ₹11,050 Lowest | 90 ₹11,700 | 100 ₹13,000 | 250 ₹32,500 |
| 6.00 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, laying of cable/pipe etc not exceeding 10 sqm on plan and getting out in soft/loose soil complete and disposal of surplus excavated soil as directed within a lead of 50m all as specified & directed by Engineer-in-Charge. | 15 | CUM | 300 ₹4,500 | 400 ₹6,000 | 700 ₹10,500 | 150 ₹2,250 Lowest | 250 ₹3,750 | 300 ₹4,500 |
| 7.00 | Excavation in trenches n.exc 1.5 m wide and exc 1.5 m depth but not exceeding 3.0 m depth and getting out soft/loose soil, including trimming the sides and forming bottom surface to required levels for laying cables complete all as specified and directed by Engineer -in- Charge. | 1.08 | CUM | 500 ₹540 | 500 ₹540 | 700 ₹756 | 950 ₹1,026 | 300 ₹324 Lowest | 390 ₹421.2 |
Tender Value
₹96.9 L
EMD Value
₹1.7 L
Closing Date
6 Nov 2025, 6:00 pmClosed
CWE (A) Jaisalmer
HQ CWE ARMY JAISALMER 345001 RAJASTHAN
SPECIAL REPAIR FOR REPLACEMENT OF DISTRIBUTION TRANSFORMER AGAINST BER IN PH-II AND PROVN OF 01 X 100 KVA TRANSFORMER AND ALLIED WORKS FOR SECURITY AND UTILITY AREA AT TCP-3 UNDER GE (A) JAISALMER
2025_MES_734380_1
84365/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JAISALMER
AS PER NIT
8 documents required · 8 mandatory
₹1,000
GE ARMY JAISALMER
₹1.7 L
Yes
18 Dec 2025
9 Oct 2025
8 Nov 2025
9 Oct 2025
6 Nov 2025
30 Oct 2025
9 Oct 2025 - 16 Oct 2025
Amount
Supply and Installation, testing and commissioning of outdoor type step down transformer 100 KVA, 11/0.433 KV, 3 Phase 50 Hz, ONAN Cooled Oil Immersed Copper wound complete with oil tank including first fill of ISI marked insulating oil up to top level, oil level indicator, breather with Silica gel, lifting hooks, drain valve, air vent valve, tackle wheel with channel and locking arrangement to put on the plinth with external cooling tubes, Core type, delta connected on primary side (HV) and star connected on secondary side LV) in accordance with vector symbol DYN-11 (vector Group-4) with neutral brought out on secondary side (LV Side) OFF load tap Changer with manual voltage regulation 0.433 KV in suitable steps/position on HV side to give output of 0.433 KV on LV side and provision of following accessories and connecting with electrical system, earthing etc. including all jointing materials, all as per IS 1180-2014 and energy efficiency level-II including filling of transformer oil having confirming to IS : 335-1993 of dyelectric strength more than 50KV complete all as specified and directed by Engineer -in- Charge and shall comprise of the following accessories as per manufactures direction :- (a) 03 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nut and washers on primary(HV) side with HV Cable box (without cable Gland).
Item No. 1.00 Contd ..... (b) 4 Nos porcelain bushings with brass/gun metal bushing rods complete with nut and washers on secondary(LV) side suitable for XLPE LT Cable with LV Cable Box (without Cable Gland) (c) Oil conservator with filter type drain valve and oil level gauge oil filter hole with caps/plugs and breather assemby. (d) De-hydrating breather with first fill dehydration agent (Silica gel). (e) Explosive vent. (f) Thermometer pocket on tank cover. (g) One No 100MM dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having minimum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals to be provided diagonally on either side of transformer body to facilitate fixing of 50x6 mm galvanised iron earth strip for body earthing. (j) Name plate and terminal marking . (k) Oil drain filter valve. (l) Lifting lugs. (m) Oil filling hole with cap/plug with conservative tank. (n) Four plain solid cast steel detachable rockters. (o) Provision of 2 Nos danger boards 250/200 mm size made out of 1.6 mm thick plate, vitreous enamel white, with letters figures of voltage and conventional skall and benes in signal red colours on front side. The rear side of the plate also be enamelled. (p) Any other fittings/accessories so as to confirm the whole transformer to 1180 : 2014. (q) Off load changer of range (+) 7.5% to (-) 7.5% instep of 2.5% each, 7 steps.
Supply and Installation, testing and commissioning of outdoor type step down transformer 160 KVA, 11/0.433 KV, 3 Phase 50 Hz, ONAN Cooled Oil Immersed Copper wound complete with oil tank including first fill of ISI marked insulating oil up to top level, oil level indicator, breather with Silica gel, lifting hooks, drain valve, air vent valve, tackle wheel with channel and locking arrangement to put on the plinth with external cooling tubes, Core type, delta connected on primary side (HV) and star connected on secondary side LV) in accordance with vector symbol DYN-11 (vector Group-4) with neutral brought out on secondary side (LV Side) OFF load tap Changer with manual voltage regulation 0.433 KV in suitable steps/position on HV side to give output of 0.433 KV on LV side and provision of following accessories and connecting with electrical system, earthing etc. including all jointing materials, all as per IS 1180-2014 and energy efficiency level-II including filling of transformer oil having confirming to IS : 335-1993 of dyelectric strength more than 50KV complete all as specified and directed by Engineer -in- Charge and shall comprise of the following accessories as per manufactures direction :- (a) 03 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nut and washers on primary(HV) side with HV Cable box (without cable Gland). (b) 4 Nos porcelain bushings with brass/gun metal bushing rods complete with nut and washers on secondary(LV) side suitable for XLPE LT Cable with LV Cable Box (without Cable Gland) (c) Oil conservator with filter type drain valve and oil level gauge oil filter hole with caps/plugs and breather assemby.
Item No. 2.00 Contd ..... (d) De-hydrating breather with first fill dehydration agent (Silica gel). (e) Explosive vent. (f) Thermometer pocket on tank cover. (g) One No 100MM dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having minimum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals to be provided diagonally on either side of transformer body to facilitate fixing of 50x6 mm galvanised iron earth strip for body earthing. (j) Name plate and terminal marking . (k) Oil drain filter valve. (l) Lifting lugs. (m) Oil filling hole with cap/plug with conservative tank. (n) Four plain solid cast steel detachable rockters. (o) Provision of 2 Nos danger boards 250/200 mm size made out of 1.6 mm thick plate, vitreous enamel white, with letters figures of voltage and conventional skall and benes in signal red colours on front side. The rear side of the plate also be enamelled. (p) Any other fittings/accessories so as to confirm the whole transformer to 1180 : 2014. (q) Off load changer of range (+) 7.5% to (-) 7.5% instep of 2.5% each, 7 steps.
Supply and Installation, testing and commissioning of outdoor type step down transformer 250 KVA, 11/0.433 KV, 3 Phase 50 Hz, ONAN Cooled Oil Immersed Copper wound complete with oil tank including first fill of ISI marked insulating oil up to top level, oil level indicator, breather with Silica gel, lifting hooks, drain valve, air vent valve, tackle wheel with channel and locking arrangement to put on the plinth with external cooling tubes, Core type, delta connected on primary side (HV) and star connected on secondary side LV) in accordance with vector symbol DYN-11 (vector Group-4) with neutral brought out on secondary side (LV Side) OFF load tap Changer with manual voltage regulation 0.433 KV in suitable steps/position on HV side to give output of 0.433 KV on LV side and provision of following accessories and connecting with electrical system, earthing etc. including all jointing materials, all as per IS 1180-2014 and energy efficiency level-II including filling of transformer oil having confirming to IS : 335-1993 of dyelectric strength more than 50KV complete all as specified and directed by Engineer -in- Charge and shall comprise of the following accessories as per manufactures direction :- (a) 03 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nut and washers on primary(HV) side with HV Cable box (without cable Gland). (b) 4 Nos porcelain bushings with brass/gun metal bushing rods complete with nut and washers on secondary(LV) side suitable for XLPE LT Cable with LV Cable Box (without Cable Gland) (c) Oil conservator with filter type drain valve and oil level gauge oil filter hole with caps/plugs and breather assemby.
Item No. 3.00 Contd ..... (d) De-hydrating breather with first fill dehydration agent (Silica gel). (e) Explosive vent. (f) Thermometer pocket on tank cover. (g) One No 100MM dia, dial type thermometer, vapour pressure type having range 0-120 degree Celsius with metal guard having minimum perimeter reading temperature indicator with resisting device for transformer. (h) Two earthing terminals to be provided diagonally on either side of transformer body to facilitate fixing of 50x6 mm galvanised iron earth strip for body earthing. (j) Name plate and terminal marking . (k) Oil drain filter valve. (l) Lifting lugs. (m) Oil filling hole with cap/plug with conservative tank. (n) Four plain solid cast steel detachable rockters. (o) Provision of 2 Nos danger boards 250/200 mm size made out of 1.6 mm thick plate, vitreous enamel white, with letters figures of voltage and conventional skall and benes in signal red colours on front side. The rear side of the plate also be enamelled. (p) Any other fittings/accessories so as to confirm the whole transformer to 1180 : 2014. (q) Off load changer of range (+) 7.5% to (-) 7.5% instep of 2.5% each, 7 steps.
M&L for bore earthing not less than 250 mm dia 16 feet deep filled with black soil up to 7 feet from bottom complete with galvanized iron pipe 40 mm bore medium grade 3 meter long tapers at bottom & provided 12 mm holes (staggered) at 75 mm centre to centre up to 2.5 meter of length from bottom , burried directly in ground filled with 45 cm alternate layer of chemical magnisium sulphate & salt and Charcoal up to ground level connected to galvanized iron strip 32 x 6 mm as earthing lead by means of bolt and nut, check nuts and washer of galvanized iron or steel including brazing work and 40mm dia light grade pipe for earth lead protection including all necessary earth work, excavation, earth chamber with PCC 1:3:6, type C1 and RCC chamber cover of PCC 1:2:4 with handle and 20mm dia GI watering pipe with funnel and wire mesh etc and testing on complete all as specified and directed by Engineer -in- Charge.
S&F galvaniased iron (GI) strip 32mm x 6 mm buried in ground/ Passed through pipe including connected by means of exothermic brazing, nuts and bolts where required complete all as specified and directed by Engineer -in- Charge
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, laying of cable/pipe etc not exceeding 10 sqm on plan and getting out in soft/loose soil complete and disposal of surplus excavated soil as directed within a lead of 50m all as specified & directed by Engineer-in-Charge.
Excavation in trenches n.exc 1.5 m wide and exc 1.5 m depth but not exceeding 3.0 m depth and getting out soft/loose soil, including trimming the sides and forming bottom surface to required levels for laying cables complete all as specified and directed by Engineer -in- Charge.
Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick soft/loose soil in complete all as specified and directed by Engineer -in- Charge.
Removing excavated material soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer -in- Charge.
Supply & laying 40 to 50 mm thick roughly hammer dressed Jodhpur stone patti cable cover 25 cm to 30 cm wide and n.exc 60 cm long each laid dry abutting with each other with maximum gap between adjacent slabs n.exc 10 mm complete all as specified and directed by Engineer -in- Charge.
Supply, Install, Testing & Commissioning self-supporting outdoor type totally enclosed LT Panel board of suitable size, IP-65, compartmentalised design, dust and vermin proof of suitable size suitable for 440 Volt 3 phase 4 wire system made out of 3.0mm thick CRCA sheet and built upon rigid frame work having front and rear hinged doors with neoprene rubber gasket including danger plate, earthing strip point and, ventilation louvers at the rear side, bottom detachable gland plate complete with suitable size of Zinc/Cromium plated and nuts, bolts ;and washers etc. The panel shall be painted with two coats of red oxide primer and final finish of synthetic enamelled grey paint and incoming/outgoing cable holes at the bottom. The Panel shall be embedded with 50 x 5 mm MS Angle Iron frame and 30 cm above the normal ground level complete with PCC foundation (1:2:4 ) type B-2 complete all as specified and directed by Engineer -in- Charge. (Loc : Near Transformer) Note : All Internal connection of MCCB from BUS Bar made By using Aluminium busbar of rated Capacity :- (a) Aluminium bas bar 400 amps - 04 Nos, supported with suitable size of heavy duty PVC stand lock with suitable size of brass nut, bolts and washer with heat shrinkable PVC sleeving. The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral. (b) MCCB 250 amps, 415 volt, 35 KA Breaking capacity 4 pole duly connected to bus bar As in coming -01 Nos
Item No. 11.00 Contd ..... OUTGOING :- (c) MCCB 160 amps, 415 volt, 25 KA Breaking capacity 4 pole duly connected to bus bar As in coming -01 Nos (d) MCB TPN 100 amps , 415 volt, duly connected to Bus Bar As out going - 02 No -02 Nos (e) MCB SPN 63 amps , 230 volt, duly connected to Bus Bar As out going - 06 No -06 Nos (f) Digital VAF Meter (j) LED Indicating lamp (set of three) - 01 Set. (k) Internal control wiring with 1100 volt grade 1.5 Sq.mm stranded copper cable as per colour coding for all connections with suitable size lugs as required and as specified.
Supply, laying & testing HT electric cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 95 sq mm 3 core complete all as specified and directed by Engineer -in- Charge.
M &L steel tubular swaged poles and complete with cast iron / M.S base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11 mtrs long) including applying two coats of aluminium paint over a coat of red oxide metal primer and the pole shall conform to IS 2713:1980 and each component pipe shall be ISI marked and conform to IS 1161 complete all as specified and directed by Engineer -in- Charge.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and including applying one coat of paint over a coat of primer complete all as specified and directed by Engineer -in- Charge.
S&F disc type insulator, porcelain, vitreous with hardware, 145mm high and 255mm dia ball and socket type, white, brown or green, single disc assembly for 11000 volts grade complete all as specified and directed by Engineer -in- Charge.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed by Engineer -in- Charge.
Supply and fix cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 95 sq mm etc complete all as specified and directed by Engineer -in- Charge.
S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and directed by Engineer -in- Charge.
S & F Air break Switch gang operated HT 11 KV Volt grade triple pole with 12 insulators, 200 amps rating with drop out fuse assembly with fuse carrier, fuse element mounted on insulator and fitted on steel frame vertical type operated mechanism from ground level consisting of operating rod of 25mm bore medium grade GI pipe ISI marked of suitable length worked from ground level and with locking arrangement flat iron clamp 50mm x 6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts, and washers complete all as specified and directed by Engineer -in- Charge. Note :- Channel, cross arms, bracings etc shall be measured and paid separately under relevant Items.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed by Engineer -in- Charge.
M&L for cutting the existing bituminous road / hard standing to size not exceeding 45cm wide and depth not less than 45cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 400mm depth with plain cement concrete 1:3:6, type C1 using 20mm graded aggregate complete all as specified and directed by Engineer -in- Charge.
S&F GI pipe light grade of dia 100 mm laying in road and along with poles for cable protection complete complete all as specified and directed by Engineer -in- Charge.
All as per item No. 22.00 here-in-before above butt size 80mm dia.
M&L for aluminium conductor, steel reinforced complete all as specified and directed by Engineer -in- Charge.
M&L for PCC 1:4:8 type D-2 (using 40 mm graded stone aggregate) as in foundation for pole/four pole structure etc complete all as specified and directed by Engineer -in- Charge.
M&L for PCC 1:3:6 type C-1 (using 20 mm graded stone aggregate) as in coping/stay of pole etc. including necessary formwork & finishing the surfaces even & smooth without using extra cement complete all as specified and directed by Engineer -in- Charge.
M&L for plain cement concrete (1:2:4) type B-1 using (20mm graded stone aggregate) as in coping and footing for poles etc including necessary formwork complete all as specified and directed by Engineer -in- Charge.
M& L for plateform of size 2.5 mx 2.5 mx1.6m for transformer with hard core of guage exc 63mm but n.exc 100mm deposited and stone masonry with soil block exc 10cm width, PCC 1:4:8 type D2 (using 40mm graded) stone aggregate in foundation and filling and mass concrete and PCC 1:2:4 as in floor finishing complete all as specified and directed by Engineer -in- Charge. Note : Excavation, earthwork, PCC, stone masonry work deemed to be included in relevent items.
Rasam Engg Co. (BID ID -3468372)
M/s Rohit Construction Co. (BID ID -3468374)
SHRI HARI CONSTRUCTION (BID ID -3473633)
UNITED AIR COOLING & PROJECTS (BID ID -3473414)
KIRTIMAN TRADERS (BID ID -3466254)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
BOQ_822314.xls
BOQ • 0.29 MB
TENDER_84365.pdf
Tender Documents • 3.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .