Executive Engineer
E400 kV Substation Division Agra
erection and commissioning of new 400 kV bus bar protection panel nelumbo make after dismantling of existing old and defected obsolete 400 kv bus bar protection panel at 400 kv substation Agra
2022_UPTCL_763042_1
ET-E400kVSSD(A)/2022-23
Open Tender
Electrical Works
Fixed-rate
90 days
E400 kV SSD Agra
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
E400 kV SSD Agra
₹2,000
Yes
20 Jan 2023
28 Dec 2022
20 Jan 2023
28 Dec 2022
20 Jan 2023
28 Dec 2022
Amount
Erection and Commissioning work of new 400 kV Busbar Protection panel in control room premises at 400 kV S/S Agra, The work consists following activities:
Preparation of inter connection wiring diagram and cable schedule as per new panel drawing to complete the job satisfactory including all 400 kV Isolator and CBs as required. The job also includes providing as executed inter connection wiring schedule drawing in 3 set.
Dismantling of existing and old 400 kV bus bar protection panels in 03/04 parts after opening of inter connection wiring, shorting of CTs & disconnected tripping of all 8-10 Nos. 400 kV feeder/bay. Including work of opening earthing strip/nut bolt etc. and safely shifting & carriage from control room building to JE store and all associated work to complete the job satisfactory. Safely opening CT connection after shorting at CT junction box of each bay & safely removal tripping connection to take care to avoid any trappings.
Erection of new 400 kV bus bar protection panels (02no. in parts) (Nelumbo make) in control room in place of the removed old panel after safely shifting from site store to erection site Including earthing of panels after making proper place for new panel and making gap filled by MS sheet and painting on it by appropriate colour.
Making inter connection wiring of 10Nos. 400 kV bay/feeder to connect each other for bus bar protection as wiring, termination of all internal connection wiring of all 10 nos. 400 kV bays as per prepared internal connection wiring diagram. Internal wiring shall be made crimping type and tinned copper lug with insulation sleeves and shall be provided proper ferrules at both end, ferrules should be marked to correspond with panel at both end wire and all other necessary work to complete the job satisfactory. The Work also includes all consumable materials such as: 1.5/2.5 sq.mm. flexible cables, lugs, gland, ferruls etc. excluding control cable and to assist the panel manufacturing company commissioning engineer at site till work complete in all respect.
Laying of control cable from different 400 kV isolators/CB to appropriate C&R panel/bus bar control panel in control room as required status in busbar panel. (As required), The work also includes checking and tracing existing control cables from different 400 kV Isolators to C/R panel.
14Cx2.5sqmm
10Cx2.5sqmm
4Cx2.5sqmm
2Cx2.5sqmm
Termination of following control cable including, lugs, ferrules, glands etc.
14Cx2.5sqmm
10Cx2.5sqmm
4Cx2.5sqmm
2Cx2.5sqmm
ELECTRO SALES INDUSTRIES
TIRUPATI ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .