Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.3 LAccepted-AOC RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹31.0 L+₹71,416.89 (2.36%)Rejected-Finance RZ BH 4 STREET NO 5 MAIN SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹33.5 L+₹3.2 L (10.6%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹34.8 L+₹4.5 L (14.9%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹34.9 L+₹4.6 L (15.1%)Rejected-Finance NOT FOUND | L5 | Rejected-Finance Being L5 |
Tender Value
₹35.0 L
EMD Value
₹69,920
Closing Date
8 Dec 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Laxmisha Suvarna
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-10
PROVN OF THREE PHASE POWER SUPPLY FOR AUTOMATION CELL (UDAAN) AT AF STN RAJOKRI UNDER GE(AF) GURGAON
2023_MES_619813_2
CWE/GGN/GT-15/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF STN Rajokri
As per NIT
8 documents required · 8 mandatory
₹500
GE AF Gurgaon
₹69,920
Yes
3 Jan 2024
17 Nov 2023
11 Dec 2023
17 Nov 2023
8 Dec 2023
25 Nov 2023
17 Nov 2023 - 24 Nov 2023
Supply, installation, testing and commissioning of Servo controlled oil cooled Voltage stabilizer for automatic operation, copper wounded, three phase, naturally oil cooled, Outdoor type & designed for input variation between 340V to 460V with output voltage stabilized at 415 with accuracy + 1% and speed of correction not to be less than 8 volts per second and of capacity 300 KVA as per latest IS code complete all as specified and as directed. Note- The construction of platform for installation of servo voltage stabilizer 300 KVA as per recommendation of OEM including excavation and earth work at site are deemed to be included in the quoted rates complete.
Supply, installing, testing and commissioning disrtibution transformer step down of outdoor type,energy efficent level -III confirming to IS 1180 (Part-1) 2014, copper wounded capacity 315 KVA, 11/0.433 KV complete,AC , 3 phase 50 Hz , oil immersed, naturally cooled, delta connected on primary side (11 KV HV side ) and star connected on secondary side (433 LV) in accordance with vector symbol DYN -11 (vector Group) with neutral brought out on secondary side (LV side ) with tapping at + 2.5%,+ 5%+ 7.5% off load tap changer gear in steps of 2.5 % including initail oil filling to appropriate level having dielectric breakdown strength > 50 KV, and all standard fitting as per IS 1180 PArt I 2014, mounted on PCC platfoorm, With fencing steel gate as per zonal TD drg . The unit rate of transformer includes the following accessories/Fittings:
(a) Non Detachable rating & terminal marking plates. (b) Lifting lugs for main tank and top cover . (c) Earthing terminals with lugs -02 Nos (d) thermometer pocket with cap, alongwith dial type thermometer -01Nos (e) Externally hand operated off circuit tap charging device with locking arrangement (f) Oil conservator tank with oil filling hole & cap and oill level gauge. (g) Silica gel dehydrating breather with first charged silica gel. (h) Top filter Valve with plug. (j) Drain cum bottom filter valve with plug. (k) Air vent, Explosion vent, Fings etc. (l) unidirectional reversible roller -04 Nos (m) HV bushing -03 Nos (n) LV bushing -04 Nos (o) First fill oil. (p) Base channel 100x50xmm, 460 mm Long with hole to make them suitable for fixing on a platform or plinth including making locking arrangement. (q) First fill of fresh oil confirming to relevent IS and tested upto 50KV dielectric strength. (r) Extra bushing for neutral outside the L.T cable box for providing independent earthing for neutral. (s) Provision of 2 Nos danger boards 250x200 mm size made out of 1.6 mm thick M.S. plate, Vitreous enamelled white, with letters figure of voltage and conventional skull and bones in signal red colour, one at HT side and other on LT side. (t) Any other fitting /accessories so as to confirm the whole transformer to IS 1180 : 2014.
Note:(i) Before installatonation of Transformer factory inspection should be carried. (ii) SEI inspection arrangement shall be made by the contractor. (iii) Transportaion charge deemed to be included in the quoted rate.
Supply, installation, testing and commissioning of 11 KV, 630 Amps having short circuit capacity 21kA for 3 Sec, Outdoor (IP54), RMU (Ring main unit) 3 way, comprising of 01 Nos motorized operated Load Break Switch and 02 Nos 630 Amp fixed type motorized spring charging VCB eletrolytic grade copper busbars all inside single, SF6 gas filled, robotically welded stainless steel 304 (non ferrite Non Megnetic Grade) tank with minimum thickness 3.15 mm, IP 67 Degree of Protection, internal-arc classified 21 KA for 1sec, on site repairable with site replacable bushing/ coupling /mechanism, gas refilling etc. The enclosure shall have pad lockable double door access with anti-theft higes, fully covering the front facia and cable boxes to ensure fail -safe anti theft protection. The unit alonwith accessories and fittings as required at site.
(A) 01 Nos. Incoming Load Break Switch module each consisting of following accessories:- (i) Each switching-unit is designed as a three positions switch. This three function switch combines the functions of switch disconnector and earthing switch. (II) 11kV, 630 Amps Load Break Switch with interlocking line-earthing scheme both short circuit current 21kA for 3 Sec, Making Capacity-50 kAp - 01 No (III) Auxiliary contacts -1 No +1 NC - 01 No (iv) Spring-assisted snap-action motorized mechanism with un-inhibited operating shaft for emergency manual operation with intergrated eathing switch - 01 No (v) Cable terminal (site replacable cable bushing situated not beyond 300mm or as per OEM tested design from cable -cover to allow ease of access for installation /testing /replacement purpose) with double - door arrangement for enhanced safety (IP4+IP3X) interlocked to prevent access upto 11kv, 120-185 Sqmm, 3 Core, XLPE Aluminium cable termination in live -condition/and kit. Each Set of 03 (vi) Right angle boots (push on type) - Each set of 03 (vii) Arc proof cable covers having cable entry from bottom, front with Interlocking mechanism including earth switch - 01 No (viii) Capacitive voltage indication fixed type system as per IEC-61243 with LED - 01 Set of 3 (ix) Fault passage indicator - It is to be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault -01 No (x) ON, OFF, EARTH mechanical indication on the front mimic of the panel -01 No cable cover standard - 01
(B) 02 Nos Outgoing VCB Module - Each consisting of following accessories: - (i) Each function – unit consists of a vacuum – circuit breaker in combination with a three position – switch. The three-position switch fulfils the operation of the disconnector and earthing function. (ii) 11 KV, 630 Amps Fixed type VCB module with series disconnector cum earthing switch of short circuit breaking current / withstand, 21 KA for 3 Sec Making Capacity – 50 kAp - 01 No (iii) Auxiliary contacts – 1 NO + 1 NC- 01 No. (iv) Stored – energy motorized high – endurance spring charging mechanism (M1+), with inbuilt spring charging lever and mechanically latched ON/OFF push -buttons to allow handle less and un-inhabited operation – 01 No. (v) Cable terminals cable bushing situated not beyond 300 mm or as per OEM tested design from cable cover to allow ease of access for installation/testing) with door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access up to 11 KV, 120 Sq mm, 3 Core, along with XLPE AL cable termination Each set of 3 (vi) Right angle boots (push on type) Each set of 3 (vii) 3 O/C + 1 E/F self-powered numerical protection relay with low and high set for over current and Earth Fault. Relay should have facilities to display the maximum loaded phase current also. Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol – 01 No/per VCB outgoing. (viii) Auxiliary Relay for OTI / WTI – transformer protection – 01 No
ix) Associated ring Core cast- resin insulated CT Ratio 30/15/1-1 as per site reqmt (for metering and protection) 2.5 VA, 10 P 10 Protection – Each set of 3 (x) Arc proof cable covers having cable entry from bottom, front with interlocking mechanism including earth switch – 01 No. (xi) Capacitive voltage indication fixed type system as per IEC 6123 with LED – 01 Set (xii) ON, OFF, Earth mechanical indication on the front mimic of the panel – 01 No (xiii) Emergency trip push button – 01 No. (xiv) CB mechanical operation should be min 10000 Nos without any maintenance. (xv) Vacuum Interrupter and VCB must be RMU manufacturer’s own make for better life cycle optimization. (xvi) CB operating sequence should be O-0.3sec-CO-3min_CO
(C) Bus connected, fixed type Potential and Auxiliary transformer with floor mounted compartment of matching height and depth, positioned alongside RMU to provide required aux. supply for spring charging motor and metering, consisting of following accessories:- (i) 1-Ph 11 KV/110V, class 0.5 potential transformer – 03 Nos for metering. (ii) 1-Ph (11 KV/rt3), 230 VAC, 250/500 VA Auxiliary transformer – 01 No for battery charging. (iii) 11 KV Tri vector Energy Meter of Class 0.5 accuracy with RS 485 Communication – 01 No per VCB o/g (iv) 2x12 Volt DC battery – 01 Set (v) 230 VAC/24 VDC Battery charger – 01 No, with indication of status of functioning (vi) HRC fuse links for primary side isolation and AC/DC MCBs for secondary isolation – 01 Set (vii) Digital Voltmeter & RYB LED indications to confirm AC/DC supply availability – 01 Set (viii) Anti condensation space heater with thermostat – 01 No (ix) LED lamp for illumination and 3 pin socket with switch – 01 No
(D) Standard mano meter -01 for each tank, Operating handle - 02, cable clamping provision (standard)-01/for every cable entry, Operation and maintenance manual - 01, installation and commissioning manual - 01, RMU Foundation as per OEM Recommendation (Earth Work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted. Height of plinth should not be less than 0.45 mtrs from ground level. NOTE:- (i) The above module consisting of Load break Switches and VCBs shall be aligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on platform as recommended by OEM. (ii) The OEM should provide 2 years manufacturing warranty including service support at site without any cost from the date of commissioning of RMU at site. Certificate for the same to be submitted by OEM at the time of delivery. The rate quoted by the bidder shall include the service cost of RMUs and no extra claim shall be entertained at later stage.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified and as directed.
Supply, laying, jointing and testing XLPE LT insulated, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 400 Sqmm and laid in trenches/ducts/pipe or on poles including aluminium thimble/gland of suitable size complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 95 Sqmm and laid in trenches/ducts/pipe or on poles including aluminium thimble/gland of suitable size complete all as specified and directed.
Supply, laying, jointing and testing XLPE LT insulated, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5core x 50 Sqmm and laid in trenches/ducts/pipe or on poles including aluminium thimble/gland of suitable size complete all as specified and directed.
M&L for excavation in trenches not exceeding 1.5 m wide and and not exceeding 1.5 m depth in loose/soft soil and getting out soil all as specified and directed.
M&L for returning, filling in, with excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed.
M&L for removal of surplus soil to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete as specified and directed.
Supply and filling river sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted. Note : Punned down thickness shall be measured and paid .
Supply and laying un-reinforced precast concrete LV cable cover class Type I with 250 x 150 x 40 mm, as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type-1 with peak, size 300mm x 180mm x 40mm all as specified and directed by Engineer-in-charge. Note- Type-I test certificate to submitted by the contrator.
Supply and fix GI pipe light grade of sizes 100mm for cable protection in trenches and cable entry at bldg/block end,all as per specified and directed.
M&L for earthing complete with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI strip 32x6mm mm Dia as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision 20 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed . NOTE: (i) The concrete pit shall be PCC 1:3:6 type C-140 mm thick pre cast cover slab of RCC(1:2:4) type B-1 using 20 mm graded stone aggregate reinforced with 8 mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cost iron cover shown in the electrical plate No.3 of MES SSR Part -1 (ii) item includes the cost of 7.5 m GI pipe for protection of earth strip. (iii) PCC pits extra cost of addtional length of watering pipe,bends elbows etc.shall be deemed to be included in the quioted rate. (iv) Item includes the cost of 7.5 mtr length Galvised earth strip 32x6 mm.
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6mm galvanised iron or steel wire complete all as specified and directed
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 sqmm to 95 sqmm
S&F in replacement Gang Operated Device triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level including MS pipe 32mm with handle, for 11000V, current rating upto 200 Amps vertically operated etc complete all as specified and directed.
Supply and fixing LT HRC fuse unit 03 pole with neutral, 400Amp, 440V, 50 Hz with sheet metal enclosure 3.15mm thick stainless steel IP-54 and grouting with wall/LT pole complete all as specified and as directed.
Material and labour for brick masonry platform (suitable for 315 KVA transformer) having size 3.0 mtr x 3.0 mtr and total height 1.6 M (0.45 M below ground level including excavation and earth work, 1.15M above ground level including RCC slab 150 mm on top and refilling of sand/soil), PCC 1:4:8 type D-2 in foundation, sub class 'B' brick work in CM 1:4, 15mm thick rendering in CM 1:6 on all sides of platform upto 150 mm below ground level, supply and fixing of 02 Nos MS channels of suitable size for balancing of transformer, embedded in PCC 1:2:4 type B-1 up to 150mm thick RCC slab, including provn of stair case on one side complete all as specified and directed.
M&L for danger notice plate of 1.6mm thick mild steel sheet vitreous enamelled white with letter figures and conventional skull and bones in signal red colour and fixed with MS clamp, bolt and nuts of approved size for LT 20x15cm complete all as specified and as directed
All as per item No 21 herein before but HT of size 25x20cm complete all as specified and as directed.
Excavating in post holes (or similar holes) each not exceding 0.5 cum ,geeting out, returning filling in and ramming earth or broken rubble mixed with earth around , in layesrs not excceding 25cm soft/loose soil complete all as specified as directed
M&L for cement concrete type B-1,1:2:4 (40mm graded stone aggregate) as in foundations, filling and mass concrete complete alla s specified as directed.
Fixing only chain link fencing including line wires,any mesh,size and type of any type of standards, rails,straining bolts etc including provision of binding wire.
Supplying only Chain link MS galvanised fencing,any size,any type (weight not exc 4kg/sqm) complete all as specifed as directed.
S&F 11 to 15 mm dia of shank mild steel screw bolts (machine made) with haxagonal or square heads at one end and screwed the other end, or screw both end,each scrwed and to fitted with washer and one haxagonal or square nut bolt but length exc 5cm and not exc 10cm long all as specified and directed
M& L for mild steel round bar 10mm dia and over,cut tolength,bent to shape rquired,including cranking,bending spirally for hopping columns,hooping ends with binding with and including mild steel wire (annealed) not less then 09mm dia or securing with clips for Gd-I,Fe-432 (part-I) complete all as specifeid and directed.
M&L for prepration of new steel surfaces of any description over 10cm width or girth and applying two coat of synthetic enamel paint over a coat of red oxide complete all as specified and directed.
S&F Hand rails,half round or other steel section or core for wooden hand rail straight portion,drilled and countersunk for balusters running bars for doors balusters,nosing to steps including embeding in concrete and screwing etc.Wind ties for roof including securing bolts posts and struts in fencing including cutting tops to shape as directed ,drilling holes ,notching for wire ,etc flat iron fillets(for securing wire mesh etc) including all neccesary drilling ,bolting or riveting etc and similar work confirming to Fe-290 Grade E-165 complete all as specified and directed.
M/s ELECTROSHINE ENGINEERS
Commercial Traders
M/S Anand Enterprises
shiv shanker enterprises
RAVINDRA BROTHERS
Shrikanth Solutions
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .