| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical All documents found in order |
| 2 | Accepted-Technical | Accepted-Technical All documents found in order |
Tender Value
₹4.1 L
EMD Value
₹8,151
Closing Date
16 Jan 2026, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AC_ELECT
SHQ BSF JAMMU
Improvement of FIDAR control room in ADM block at BOP Chhawani of 120 Bn BSF under SHQ Jammu SH Providing electrical installation Fans Air conditioners and service connection
2026_BSF_893398_1
09/AE(Elect)/NIT/SHQ JAMMU/Engg/2025-26
Open Tender
Electrical Works
Works
90 days
IN AOR OF 120 BN
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹8,151
12 Feb 2026
10 Jan 2026
19 Jan 2026
10 Jan 2026
16 Jan 2026
10 Jan 2026
10 Jan 2026 - 16 Jan 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Group A)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (i) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (i) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire.
Supplying and fixing suitable size GI box with modularplate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 Pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing PVC batten/ angle holder including connections etc. as required.
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing 5/6 A switch modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supplying and fixing 3 pin 5/6 A socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Supplying and fixing 12 way, Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCb/Isolator)
Supplying and fixing 8 way, Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCb/Isolator)
Suppying and fixing 5 A to 32 A rating, Single pole, 240/ 415 V, 10 KA,"C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (i) Single Pole
Suppying and fixing 5 A to 32 A rating, double pole, 240/ 415 V, 10 KA,"C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (ii) Double Pole
Earthing with GI earth 50 mm X 2000 mm including accessories with ground enrichment compound (AIO4SiOHO), crstalline conductive mixture conforming IS 3043:1987 as required
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thickG.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies,shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. (i) 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum)
LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hourswith 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), DCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sqmm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) (i) 18 -22 watt
Supplying and fixing energy efficient 09 watt LED bulb suitable for PVC batten/ angle holder etc. as required. Make Havells/ crompton/ Bajaj/ Halonix
Supplying and installation of fresh air fan with louvers shutter 250 mm sweep including making the hole by cutting the wall to suit the size of the above fan and making good the damage same, connection, testing , commissioning etc as required. (Havells make Thrill Air DX White with self opening louvers or with similar specifications of C&G / Orient / Usha / Almonard)
Suppyling and fixing square type, 25 Ltrs capacity electric storage water heater (Geyser), ABS outer body & SS tank on the existing wall including 450 mm long braded hose with two nos. 15 mm nuts & rubber washers and making connections etc. ISI marked as required, make Usha/ Crompton/ Havells/ bajaj and equivalenet to make Havells Model No GLAZER STORAGE PLASTIC (GSWCBNTWB25)
Supplying, Installation, testing & commissioning of 10 watt LED Surface Mirror Light, decorative ultra slim round profile LeD lighting fixture with extruded polycarbonate, environmental friendly, energy efficient etc. as required. Make :- Philips / Bajaj/ CG/ Havells/ SYSKA /Wipro / C&S / Orient/ Helonix or equivalent to Make : Havells - Model-No LED PRIDE PLUS NEO.
LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm) (i) 36 watt
Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). (i) 1.5 TR with 5 Star BEE Rating
Supplying and fixing 5 KVA stablizer having following technical specification, copper winding, input voltage - 90 volt to 300 volt, digital display meter etc as required. (make V-guard/ Luminous/ Mircotek/ Voltas
Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 3.5 x 35 sq.mm size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. make Havells/ poly cab/ Finolex/ R R kable.
Supplying and making end termination with brass compression gland and aluminium lugs for 3.5 x 35 (22mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. (i) 3½ X 35 sq. mm (32mm)
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required i) 50 mm dia
Supplying and fixing Bus-Bar chamber with 63 Amps, 415 volts, 4 way 4 nos. copper bus bars, Complete with connections, earthing the body etc. as required. Havells Make Item Code IHBC006304 or other equivalent Anchor, Crompton, Phillips, Legrand.
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.82 MB
BOQ_939044.xls
BOQ • 0.67 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .