Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.41Accepted-Finance | L1 | Accepted-Finance _ | |
| 2 | L2₹16.99+₹0.58 (3.53%)Accepted-Finance | L2 | Accepted-Finance _ | |
| 3 | L3₹22.13+₹5.72 (34.9%)Accepted-Finance | L3 | Accepted-Finance _ | |
| 4 | _₹22.15Accepted-Finance | _ | Accepted-Finance _ | |
| 5 | _₹23.21Accepted-Finance | _ | Accepted-Finance _ |
Tender Value
Refer Docs
EMD Value
₹53,000
Closing Date
18 Aug 2021, 1:00 pmClosed
Executive Engineer, ED Budgam, KPDCL
Office of the Executive Engineer, ED Budgam, KPDCL
HT/LT network improvement by way of replacement of worn-out conductor and rotten/damaged/undersized/tree posts poles and insertion in longer spans in various feeders under the jurisdiction of ED Budgam, KPDCL.
2021_PDD_131639_1
EDB_33_of_2021_22
Open Tender
Electrical and Maintenance Works
Turn-key
10 days
ED Budgam
As per SBD
7 documents required · 7 mandatory
₹1,000
Executive Engineer, ED Budgam, KPDCL
₹53,000
25 Aug 2021
24 Jul 2021
19 Aug 2021
24 Jul 2021
18 Aug 2021
27 Jul 2021
24 Jul 2021 - 27 Jul 2021
Amount
Work items identified for HT/LT network improvement
Carraige from store upto site, Erection,testing and commisioning of 9mtr long Steel Tubular Poles complete with base plate(300x300x5mm), top cap, including digging of pit (1/6th of pole height) positioning etc, complete in all respect as per REC Standard.
Carraige from store upto site, Erection,testing and commisioning of 8 mtr long Steel Tubular Poles complete with base plate(300x300x5mm), top cap, including digging of pit (1/6th of pole height) positioning etc, complete in all respect as per REC Standard.
Carraige from store upto site, laying, stringing, tensioning, binding of 50 Sqmm ACSR Conductor of sizes complete in all respects as per standards
Carraige from store upto site, laying, stringing, tensioning, binding of 30 Sqmm ACSR Conductor of sizes complete in all respects as per standards
Supply,Carraige upto site and fixing of GI V Cross arm & GI F Top with clamps duly fabricated as per site requirement including clamps(50x6 mm), GI Nuts & Bolts,washers etc complete in all respects as per REC standards.
Supply,Carraige upto site,Installation,testing and Commissioning of 11 KV Polymer composite Pin Insulators 12 kv.5KN, Lighting impulse 75 Kv positive and 80 Kv negative, Creepage distance 320mm complete in all respects as per REC standards
Supply,Carraige upto site and installation of GI Mukhi Clamp for Shackle insulators
Supply,Carraige upto site and installation of 16KN Polymer Shackle insulators
Cement bottoming of S T poles in 1:2:4 mix,up to 1/6th plantation depth of pole below ground, 9" above ground,circular with radius 6" around the pole girth/surface ,top surface tappered outwards 0.5 cum/pole as per the diagram given in technical specifications.
Earthing of steel tubular poles complete by GI pipe 40mm or GI rod 20mm 2.5mtr long through GI strip.
Painting of Poles with one coat of Red Oxide (1ltr/pole) and two coats of alimunium paint (1ltr/pole).
NOTE: 1.The rates quoted by the bidder for all the line items shall be inclusive of GST/freight/insurance/storage/installation/testing and any other charges FOR various sites in the identified feeders for HT/LT network improvement under the jurisdiction of Electric Division Budgam
M/S SYED YAQOOB CONSTRUCTIONS
M/S G E C ELECTRICALS
M/S NEW AL MUSTAFA ELECTRICALS
A One Engineers
AL HASSAN ASSOCIATES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .