Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.0 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹11.9 L+₹20,630.49 (1.76%)Rejected-Finance FLAT NO 703 7TH FLOOR PARVATI ENCLAVE PLOT NO 180 SECTOR 2 TOLOJA PANCHANANDTAL TALOJA MAJKUR DISTT RAIGAD MAHARASHTRA 410208 | RAIGAD | MAHARASHTRA | 410208 | L2 | Rejected-Finance NOT L1 | |
| 3 | L3₹16.6 L+₹4.9 L (41.4%)Rejected-Finance 1101 A WING SACHDEV COMPLEX JANGAL MANGAL RAOD BHANDUP W MUMBAI 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | L3 | Rejected-Finance NOT L1 |
Tender Value
₹11 L
EMD Value
₹22,000
Closing Date
16 Oct 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
COL VIKAS KESARWANI
CWE AF LOHEGAON, PUNE - 411032
REPAIR, MAINTENANCE OF HIGH TENSION DISTRIBUTION SYSTEM AND HT EQUIPMENTS AT SITE P AND R UNDER GE (AF) THANE
2023_MES_615222_2
82649/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF THANE
As per NIT
6 documents required · 6 mandatory
₹500
Yes
GE AF THANE
₹22,000
Yes
4 Nov 2023
26 Sept 2023
23 Oct 2023
26 Sept 2023
16 Oct 2023
3 Oct 2023
Amount
Supply , jointing & testing end terminal cable jointing kit for 22 KV (Earthed) grade cable for outdoor termination Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm etc complete all as specified and directed by Engineer.in.Charge.
Supply , jointing & testing end terminal cable jointing kit for 22 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm etc complete all as specified and directed by Engineer.in.Charge.
Supply , jointing & testing cable jointing kit for 22KV (Earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 3 C x 95 Sqmm etc complete all as specified and directed by Engineer in Charge.
Dehydration/ filtration of transformer oil filled in transformer installed at different locations,testing of oil after dehydration to achieve dielectric strength not less than 40 KV for 1 minute in 2.5 mm electrode gap as per relevant IS and to bring the acidity with the permissible limit complete all as specified and directed by Engg.in.Charge.
Supply and filling fresh tansformer oil confiming to IS 335 having die electric strenght up to 50 KV with oil testing kit 2 mm thick top up transformer complete all as specified and as directed by Engr In Charge.
Disconnecting of incoming & outgoing cable from both side of transformer indoor/ outdoor type including all accessories, loading unloading and transportation from site to work shop as per site requirement and back to site after carried out repairs & assembling , including connection for the capacity 160 KVA to 250 KVA and commissioning and testing complete all as specified and directed by Engr In Charge.Note: Gasket set,LT/HT Side ceramic bushing,spindle for HT/LT side, rewinding, dehydration of oil shall be measured and paid separately in respective items.
Taking out defective HT winding and M& L for rewinding of HT coil with super enameled best quality copper wire of existing gauge with superior quality insulation material for transformer of capacity 160 to 250 KVA complete all as specified and directed by Engr In Charge.
M& L for rewinding of LT coil with super enameled best quality copper wire of existing gauge with superior quality insulation material for transformer of capacity 160 to 250 KVA complete all as specified and directed by Engr In Charge.
Assembling of HV and LV coils including necessary insulation with paper boards and varnishing, making internal connections, drying, removal of moisture from core and coils, heating the complete and carried out all necessary tests for transformer capacity 160 KVA to 250 KVA complete all as specified and directed by Engr In Charge.
M& L for improvement of insulation resistance value for core & coil winding by cleaning complete, applying varnishing & necessary insulation material and baking in oven terminal connection inside the transformer complete all as specified and directed by Engr in Charge.
Disconnecting the HT termination,Supply and fixing HT Boot cover at cable end and VCB as directed by Engineer-in-Charge
Disconnecting all incoming and outgoing connection of HT 22KV under ground cable,detecting fault by applying surge current 1.5 times the rated current & finding exact location of fault with PICO equipment and repair the same immediately complete all as specified and as directed by the Eng.in.Charge.Note: Necessary Jointing kit to be measured and paid separately in respective items.
M&L for Servicing/testing the following equipment of distribution Transformer 22/0.44kv: (a) IR Value of winding (b) De carbonizing all cable connection.(c) Earth Resistance Checking (d) Replacement of Silica gel Complete all as specified and as directed by Eng.in.Charge
Painting of transformer after cleaning the body surface of transformer by rubbing with emery paper to remove oil stains,dust etc and applying one coat of synthetic enamel paint by spray paint incl writing SM No./MES No. of capacity 160/250 KVA Transformer completeall as specified and directed by Eng.in.Charge.
Supply only assembly of approved make filled with silica gel suitable for transformer of capacity 160/250 KVA distribution transformer complete all as specified and as directed by Eng.in.Charge.
Supply and fix brass spindle for terminal on HT side threaded complete with nut,washer etc of suitable dia for transformer of capacity 160KVA to 250KVA complete all as specified and directed by Engg.in.Charge.
Supply and fix brass spindle for terminal on LT side threaded complete with nut,washer etc of suitable dia for transformer of capacity 160KVA to 250KVA complete all as specified and directed by Engg.in.Charge.
Supply and fix ceramic bushing and gasket on LT side of transformer of capacity 160 to 250 KVA 22000/433 Volt distribution transformer complete all as spd and directed by Engg.in.Charge
Supply and fixing in replacement of complete gasket(Cork sheet) 6mm thick with and incl conical rubber bush complete all as spd and directed by Engg.in.Charge.
M&L for Servicing/ Testing HT 22KV VCB Panel rupturing capacity 26/3 MVA, 1250 Amps one incoming- three out going panel including checking of contacts, lubrication of mechanism, cleaning, tighting, insulation Ressistance Test for exsiting rated HT breaker. Tightening of all control wiring panel, repair to manual/ electrical closing/ tripping. Opening of panel back covers, removing of Bus bar, removing of PT, removing of CTs, cleaning of all bus bar, CT chamber and heating up chamber to remove moisture pressure test with pressure test kit. complete testing of breaker, checking mechanism of fixed and moving contracts and removing carbon deposits and overhauling of spring charged mechanism and operation of indicators and correctly showing of ON/OFF and spring charged/ discharged system, cleaning the surface of insluators, fasten the bolts fixed in interruption units, mechanism linkages, replacing all unserviceable parts like CT, PT, vaccum interrupter, fuses/ any mechanism etc. Lubricating and greasing the mechanism of moving parts and repairing of trip push button assembly including testing and calibration of protection relays and reconnecting back the VCB and testing complete all as specified and directed Note:-The quoted rates shall also be deemed to include for submission of test reports for testing as specified above
Supply only Voltage indicator lamp(Red,Yellow and Orange) 220 V,AC for servecing/replacement the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
Supply only Control Fuse,HRC,2/4/6 Amp for servecing/repairing the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
Supply only HT Tape for servecing/repairing the HT 22KV VCB Complete all as specified and directed by Engg.in.Charge
Supply only high voltageover current protection relay for servicing/repairing the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
Supply only Earth fault relay for servicing/repairing the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
Supply only Auxillary contacts for servicing /repairing the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
Supply only SPACE heater alongwith thermostat for HT VCB Panel including electric connection complete all as specified and directed by Engg.in.Charge.
Supply only master trip relay suitable for HT 22 KV VCB Panel complete all as specified and directed by Engineer-in-Chrage.
Supply only contact arm suitable for HT 22 KV VCB Panel complete all as specified and directed by Engineer-in-Chrage.
Supply only shunt release coil on, 110 V, DC suitable for HT 22 KV VCB Panel complete all as specified and directed by Engineer-in-Chrage.
Supply only shunt release coil off, 110 V, DC suitable for HT 22 KV VCB Panel complete all as specified and directed by Engineer-in-Chrage.
Supply only key locks for servicing /repairing the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
Supply only Switch operating Assembly servicing /repairing the HT 22KV VCB complete all as specified and directed by Engg.in.Charge.
M&L for taking down carefully existing serviceable switch air break, gang operated outdoor, any type of capacity upto 22 KV, servicing to the operating mechanism, greasing etc of all joints for smooth operation, with & including replacement of burnt male/female contact where required, re-fixing the switch air break, gang operated outdoor, testing, complete all as specified and as directed.
Taking down Unserviceable GOD of any capacity and supply and installation HT 22KV/200Amps outdoor type GOD including dropout fuse assembly complete all required at site etc complete all as specifed and directed by Engineer in charge.
Supply & fixing Dropout Fuse 23 SWG complete all as specified and directed by Engg.in.Charge.
S&F in replacement Copper strip of size 32x 6mm with saddles and fixing screws etc. for roof conductors and down conductors above ground Complete all as specified and directed by Engg.in.Charge
S&F Copper strip of size 20x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground Complete all as specified and directed by Engg.in.Charge
S&F in replacement Single phase SMPS based battery backed power pack for Supply Back-up for trip Coil,Protection Relay,Indication,& other Load in HT Panels, working input voltage 90 to 300 Volt AC, output 110 Volts DC with backup for 15-20 min, complete all as specified and as directed. Make-Gogate or in equivalent
S&F Lightening arresters HT 22 KV 65 kilo Amp Non linear expulsion type transmission class with standard fittings confirming to IS-3070 (Part-I) 1985, including dismantling & taking down old unserviceable lightning arresters, complete all as specified & as directed.
S&F Disc type insulator, porcelain, vitreous, 145mm high and 255mm dia ball and socket type, white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 22000 Volts, including dismantling & taking down old unserviceable insulator, complete all as specified & as directed.
Supply & laying XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric power cable with aluminum conductor, 22000 V grade, cross sectional area of 3 core 95 Sqmm in trenches all as specified and directed by Engr In Charge.
Supply & laying un reinforced precast cement concrete cable cover class HV type 1, flat, size 300mm x 180mm x 40mm all as specified & directed by Eng.in .Charge
M&L for earthing complete with Copper earth plate electrode 600x 600x 3 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal gound level and connected to earth test point by means of copper Strip of size 20x3 mm all as specified and shown in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site and all as directed. Note: (i). 7.5 RM Copper strip in deemed to be included in quoted rates beyond 7.5 RM strip shall be measured and paid separately. (ii). Earth resistance of earth pit should be less than 2 Ohms. On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. (iii) Rate quoted by the tenderer is deemed to include salt & Charcoal upto & above 450 mm top of Copper plate. (iv) Soil registance test if required shall be the responsbility of contractor without any extra cost.
Excavation in trenches , n exc 1.5 m wide and n, exc 1.5 m in depth for foundation, etc. or for shafts, wells cesspits, manholes, peir holes. Etc 1.5 m n exc 10 sqm on plan and n exc, 1.5 m in depth and getting out complete as specified & directed
Returning, filling including spreading, leveling, watering and well ramming in layers not exc 25cm in soft/soil complete all as specified and directed
Removing excavated soil not exc 50m depositing where directed at a level not exc 1.5m above the starting point complete all as directed and specified & directed.
M&L Sand cushioning for UG cable protection/ducts, consolidated sand compacted with clean dry sand all as directed and specified.
Boring for road crossing in any kind of soil/rock strata all as specified and directed by Engineer-in-Charge.
Supply & laying GI pipe light graded of size 80mm dia in trenches and fixing on wall/Poles with help of suitable size MS clamp for cable protection all as directed.
Supply, fixing & stretcing aluminium conductor steel reinforced (ACSR) of any type and size fixed on existing steel tubular/ PCC HT/LT pole fixed on insulators and binding with & including 2 mm binding wire complete all as specified and directed by Engineer-in-Charge. Notes :- i) The ACSR conductors shall be conforming to IS- 398 (part-II) and as specified in SSR part-I . ii) The unit rate quoted shall also be deemed to include for supply and fixing of binding wire, aluminium tapes etc which shall not be included in the weight of conductors for payment. iii) Weight of conductors shall be determined by measuring the horizontal distance between centres of two adjacent poles and compounding the weight of conductors of that size multiplied by lenght of span and 3 % extra shall be added for sag, jointing, jumpers etc. iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.
M&L Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape inclusive of one primer coat, one under coat and one finishing coat of paint complete all as spd and directed by Engg.in.Charge.
M&L in replacement for electrical rubber hand glove 22 KV complete ass as specifed and directed by Engr-in-Charge
Supply & fixing in replacement of ceramic HV/LV bushing with gun metal bushing stud, nuts and washers for transformer of capacities 315/400 KVA etc complete all as specified and directed by Engineer.in.Charge.
M&L for Servicing/testing of HT 22KV RMU SF-6 including calibration,troble shooting,repairing, replacement of unserviceable spare parts and adjustment/servicing phase concordance unit,protection relay test,Voltage indicator lamp,short circuit indicator,switch operating mechanism,circuit breaker operating mechanism,auxiliary contacts,opening release,key locks on network switches on transformer feeders of over current relay,earth fault relay,checking of vaccum of interupter including connected accessories cleaning of fixed and moving contacts,testing of electrical wiring system,by qualified technical person etc complete all as specified and as directed by Engineer.in.charge.Note: Necessary spare parts need to replace will be paid in respective item.
Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earthpit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to & including galvanised GI earth Strip of size 25X 4 mm by means of GI bolts, nuts, washers, and connected to other end to main board duly protected by 15 mm bore GI light grade pipe from earth plate. Earth plate shall be surrounded by packed layer of coal dust 300mm and common salt 15 cm thick all around bottom and top. Watering pipe 20 mm bore of GI medium grade pipe and including funnel, wire mesh, CI cover & frame, PCC (1:3:6) type C2 (using 40 mm graded stone aggregate) as in earthing pit including necessary excavation & earth work, all as specified & shown in electrical plate No. 5 of SSR Part – I. Note : PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner.etc complete all as specified and as directed by Engineer.in.charge.
DWARKESH STRUCT-CON
sapana enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .