| Sl No | Description | Qty | Unit | Universal Cables Limited L4 | L S CABLE INDIA PVT LTD L1 | KEI Industries Limited L6 | KEC International Limited L7 | Kay Cee Energy and Infra Private Limited L2 | FINOLEX J-POWER SYSTEMS PVT. LTD. L3 | Polycab India Limited L5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00MATERIAL/ EQUIPMENT | ||||||||||
| 2.00Under ground cable section | ||||||||||
| 3.00 | 132kV, Single Core, 500mm2, XLPE Copper Cable | 57 | Km | 70,11,241.4 ₹40.0 Cr | 69,32,816.24 ₹39.5 Cr | 78,06,290 ₹44.5 Cr | 84,53,504.66 ₹48.2 Cr | 72,12,126.96 ₹41.1 Cr | 71,79,178.32 ₹40.9 Cr | 81,42,000 ₹46.4 Cr |
| 4.00 | 145kV rated Voltage Pre-moulded Straight Through Joint suitable for above cable | 78 | Nos. | 1,90,258.48 ₹1.5 Cr | 1,83,249.28 ₹1.4 Cr | 2,75,530 ₹2.1 Cr | 2,15,691.02 ₹1.7 Cr | 2,36,263.98 ₹1.8 Cr | 2,03,196.46 ₹1.6 Cr | 2,06,500 ₹1.6 Cr |
| 5.00 | 145kV rated Voltage Pre-moulded Straight Through Joint (with provision for sheath separation for cross bonding) suitable for above cable | 30 | Nos. | 2,09,211.64 ₹62.8 L | 1,89,398.26 ₹56.8 L | 2,75,530 ₹82.7 L | 2,26,875.06 ₹68.1 L | 2,36,263.98 ₹70.9 L | 2,12,194.11 ₹63.7 L | 2,20,660 ₹66.2 L |
| 6.00 | 145kV rated Voltage pre-moulded Outdoor end termination Kit complete with accessories suitable for above cable | 6 | Nos. | 3,97,224.58 ₹23.8 L | 2,02,926.96 ₹12.2 L | 4,36,021.8 ₹26.2 L | 2,95,577.02 ₹17.7 L | 2,72,767.48 ₹16.4 L | 2,81,391.53 ₹16.9 L | 2,47,800 ₹14.9 L |
| 7.00 | 145kV Plug in type pre moulded end termination kit complete with accessories suitable for above underground cable and suitable for termination in GIS type switchgear | 6 | Nos. | 3,10,782.5 ₹18.6 L | 2,02,926.96 ₹12.2 L | 3,87,954.5 ₹23.3 L | 2,20,644.66 ₹13.2 L | 2,72,767.48 ₹16.4 L | 2,16,386.37 ₹13.0 L | 2,53,700 ₹15.2 L |
| 8.00 | Galvanized steel supporting structures/ arrangement etc for suitable and safe termination of XLPE cable to GIS switchgear | 6 | Set | 36,469.08 ₹2.2 L | 45,505.52 ₹2.7 L | 44,055.3 ₹2.6 L | 39,943 ₹2.4 L | 97,567.42 ₹5.9 L | 10,55,678.34 ₹63.3 L | 69,443 ₹4.2 L |
| 9.00 | Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase | 12 | Nos. | 1,03,645.3 ₹12.4 L | 24,597.1 ₹3.0 L | 55,047 ₹6.6 L | 37,546.42 ₹4.5 L | 74,862.72 ₹9.0 L | 87,445.35 ₹10.5 L | 98,482.8 ₹11.8 L |
| 10.00 | Cross bonding Link box, Co-axial bonding cable with Sheath Voltage Limiters (SVL) complete with other associated accessories for each 3-phase circuit | 8 | Set | 3,28,248.86 ₹26.3 L | 1,04,538.56 ₹8.4 L | 3,15,384.5 ₹25.2 L | 1,19,030.14 ₹9.5 L | 1,63,677.56 ₹13.1 L | 3,94,234.28 ₹31.5 L | 1,70,451 ₹13.6 L |
Tender Value
₹52.1 Cr
EMD Value
₹1.0 Cr
Closing Date
16 Mar 2022, 4:00 pmClosed
SE (AUTOMATION, N/M, SP)
Vidyut Bhawan, Jyoti Nagar, Jaipur
DESIGN, MANUFACTURE, TESTING AT WORKS AND SUPPLY OF 132 KV SINGLE CORE XLPE CABLE FOR ESTABLISHING OF 132 KV DOUBLE CIRCUIT (500 SQ. MM) BETWEEN PROPOSED 132 KV LAXMAN DOONGRI SUBSTATION AND EXISTING 220 KV SUBSTATION KUNDA KI DHANI (JAIPUR) (APPROX
2022_RRVPN_256856_1
RVPN/EHV/ASP/TN-90
Open Tender
Electrical Works
365 days
JAIPUR
Please refer Tender documents.
4 documents required · 4 mandatory
₹23,600
SR AO (EA AND CASH) RVPN
₹1.0 Cr
JAIPUR
11 May 2022
1 Feb 2022
16 Mar 2022
1 Feb 2022
16 Mar 2022
20 Feb 2022
10 Feb 2022
MATERIAL/ EQUIPMENT
Under ground cable section
132kV, Single Core, 500mm2, XLPE Copper Cable
145kV rated Voltage Pre-moulded Straight Through Joint suitable for above cable
145kV rated Voltage Pre-moulded Straight Through Joint (with provision for sheath separation for cross bonding) suitable for above cable
145kV rated Voltage pre-moulded Outdoor end termination Kit complete with accessories suitable for above cable
145kV Plug in type pre moulded end termination kit complete with accessories suitable for above underground cable and suitable for termination in GIS type switchgear
Galvanized steel supporting structures/ arrangement etc for suitable and safe termination of XLPE cable to GIS switchgear
Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase
Cross bonding Link box, Co-axial bonding cable with Sheath Voltage Limiters (SVL) complete with other associated accessories for each 3-phase circuit
Cross bonding Link box, Co-axial bonding cable without Sheath Voltage Limiters (SVL) complete with other associated accessories for each 3-phase circuit
Galvanized Steel supporting structures along with clamps, connectors nuts-bolts, washers, foundation bolts etc. for Outdoor 132kV Cable end terminations (a composite structure for mounting link boxes and cable end terminations) for each phase
Galvanized Steel supporting structures/ arrangement, Gantry structures, Ladders etc. for suitable and safe terminations of XLPE cable from Terminal tower/ gantry maintenaing statutory clearances and safety as per IE rules
Galvanized Steel supporting structures/ arrangement as required for raising/ fixing of cable for vertical portion from main road to the proposed entry in GIS Building at Terminal Substation
Earthing Material including cast iron pipes with suitable clamps, charcol, common salt etc. (for each circuit)
Terminal connector suitable for ACSR Panther on the item No. 6 to connect cable end termination to Outdoor Switchyard Equipment.
Warning Tapes as per Specification
Optical Fiber Cable and associated accessories/items as per specification
132kV class of 120kV rating LA with grading ring, discharge counter with milli meter
Add: Any other item bidder may require to complete the cable system as per specification requirements
Description of Work / Item(s)
SERVICE PART
Under ground cable section
SURVEY
Surveying of cable route excavation of trial holes as per field requirement, prepartion of cable route profile, drawings for cable laying , final route alignment, marking lines & grades/prepartion of final cable route darwings after approval & preparing bill of materials for complete route shown in drawings i.e. between terminal sub stations.
Evalutions of thermal resistivity of soil along cable route (as per tecnical specifications)
Cable Installation:
Handling,Transportation to site & laying of 132 KV, single core, 500 Sq mm XLPE Copper cable as per foregoing specification requirements.
Establishing of 2 Ckts. each having 3 nos. 132kV single core, 500 sq. mm copper cable in trefoil formation alogwith pilot fiber cable, providing of Warning tape taging fixing, pipes for drain & gate crossing as per drawings and specifications in trench by pulling, drawing, etc. including cables, using standard cable installation equipments and as per directions of the engineer in charge and returning of unused items in Store. .
Handling & making of straight through joints for 132 KV, single core, 500 Sq mm power cable (XLPE copper cable) as per specification.
Handling and making of straight through joints (with provision for sheath separation for cross bonding) for 132 kV single core power cable as per specifcation.
Handling & making of outdoor type cable end termination for 132 KV, single core, 500 Sq mm power cable (XLPE copper cable) as per specification.
Handling & making of plug in type premoulded end termination for 132 KV, single core, 500 Sq mm power cable (XLPE copper cable) in GIS switchgear as per specification.
Installation of Galvenized Steel Structure/ arrangement, etc. for suitable and Safe Terminations of XLPE Cable to GIS switchgear
Installation of Galvanized Steel Supporting Structure alongwith clamps, connectors, nut-bolts, washers, foundation bolts etc. for Outdoor 132 kV Cable end terminations (a composite structure to mount link boxes and the cable end terminations) for each phase
Installation of Galvenized Steel Structure/ arrangement, Gantry structures, Ladders etc. for suitable and Safe Terminations of XLPE Cable from Terminal Tower/ gantry maintaining statutory clearances and safety as per IE Rules
Galvanized Steel supporting structures/ arrangement as required for raising/ fixing of cable for vertical portion from main road to the proposed entry in GIS Building at Terminal Substation
Installation of 132 kV class of 120 kV rating Surge Arrestors with grading ring, dicharge counter with Milli meter
Installation of solid bonding Link box with Link plates, bonding & grounding cable complete with other associated acessories for 1-phase.
Installation of Cross bonding Link box, Co-axial bonding cable, Sheath Voltage Limiters (SVL) complete with other associated acessories for each 3-phase circuit.
Installation of Cross bonding Link box, Co-axial bonding cable, without Sheath Voltage Limiters (SVL) complete with other associated acessories for each 3-phase circuit.
Installation of Earthing material including cast iron pipes with suitable clamps, charcol, common salts etc. complete set for each cable circuit (each having 3 core)
Installation of Terminal connector suitable for ACSR Panther conductor to connect cable end termination to outdoor switchyard equipments/ Surge Arrestors.
Installation of Underground Optical Fiber Cable and associated accessories/items as per specification alongwith XLPE cable at both ends at Substations.
CIVIL WORKS
Cutting Black Bitumen surface upto any depth including all layers of crust for laying Power Cables etc, staking of useful material and disposal of surplus debries including all leads including barricading, providing danger board/diversion board, lighting, reflectors etc.
Earth work in excavation for burried cable trenches/foundations including dressing of sides and ramming of bottoms, lift upto 2.5 mtr. including taking out the excavated soil & backfilling of jhiri with watering & ramming ,timbering & shoring ( wherever required ) disposal of surplus excavated soil as directed with all lead and lift including barricading, providing danger board/diversion board, lighting, reflectors etc. (Normal Soil)
Earth work in excavation for burried cable trenches/foundations including dressing of sides and ramming of bottoms, lift upto 2.5 mtr. including taking out the excavated soil & backfilling of jhiri with watering & ramming ,timbering & shoring ( wherever required ) disposal of surplus excavated soil as directed with all lead and lift including barricading, providing danger board/diversion board, lighting, reflectors etc. (Hard Rock)
Horizontal Direct Drilling (Trenchless Digging) method (with 250 mm HDPE pipe of minimum 6PN and strength complying to relevant ISS) wherever open cut method cannot be adopted. (If required) (for double circuit with 3 cable core in each circuit)
Poviding and laying of Cement concrete including curing, etc using stone aggregate 40 mm nominal size (crusher broken) in foundation plinth, excluding the cost of shuttering using 1 cement: 4 sand: 8 stone aggregate (For equipment foundation, junction box etc.)
P&L cement concrete in R.C.C. work in foundation,rafts,footings,strap beams, bases of columns etc.,'including curing ,compaction,finishing with rendering in cement sand mortar 1:3 (1cement :3 sand) and making good the joints, excl., the cost of centering and shuttering and reinforcement :M-20 grade mix 1:1.5:3 (1cement:1.5coarse sand : 3 graded stone aggregate 20 mm nominal size (For equipment foundation, junction box , culvert etc.)
Brick wall works, if required
Providing and fabricating steel reinforcement for R.C.C. work bending ,placing in position and binding complete including cost of binding wire in foundation ,raft footing ,strap beams base of column etc., up to plinth level hot rolled deformed (I.S.1139) cold twisted (I.S.1786)bars (For equipment foundation, junction box \ etc.)
Centering and shuttering with plywood or steel plates including strutting, propping bracing both ways with wooden members and removal of formwork for superstructure up to 4.5m height above plinth level for (For equipment foundation, junction box etc.)
Providing & Fixing of steel febrication made of angles, tees, square bars or other flats black pipe with hold fast and fittings complete as per design @ drawing including cutting welding & fabrication with priming coat of redoxide.
Providing,Laying & Jointing RCC class NP-2 Non Pressure pipes (IS:458 Mark) of approved make with collars, jointed with CM 1:2 or having Spigot & socket ends with flexible rubber rings joint including testing of joints etc. complete: 450 mm D.
Providing & Fixing of Reinforced Ferro Cement Cable Trench Covers designed for 'A' & 'AA' loading duly marked on cover with adequate reinforcement having thickness 75mm to 100 mm anti corrosive bitumen pained MS plate Rim & MS lifting hooks admixtures like plasticizer bond -improving compound, shrinkage resistance compound, abrasion resistant complete as per approved design ( For cable joint box) (For any span)
Providing & Laying HDPE pipe heavy duty of approved make jointed with solvent cement
(i) 250 mm dia. (for double circuit each circuit with 3 cable cores)
(ii) HDPE PLB Duct for Optical Fiber Cable
Supply and laying inter locking RCC cable covers as per approved drawing
Supply, spreading of clean river sand in the cable trench and cable joint pit as per specification.
Providing & Fixing Cable Route Marker along the route of cable at the spacing of 50 meter etc. as per drawing and site requirement.
RR Stone Masonry in F/P csm 1:4
Plastering 25 mm thickness csm 1:6
Providing & laying plane cement concrete M20 Grade
Charges of conducting pre commissioning tests as per specification & successful commissioning of circuit
Add: Any other item bidder may require to complete the cable system as per specification requirements
Maintenance Service [these charges shall be applicable after the completion of guaranteed performance period of cable system for 4 years excluding of item/ material/ equipment already covered for performance guarantee of 5 years. The charges shall be payable on actuals
Maintenance services per visit towards any breakdown of cable system which includes services of expert engineers, technicians alongwith necssary tools/ tackles, testing equipments, fault locating equipments to detect the faults and its subsequent ractification, re-testing and restoring the electric supply through cable system
Universal Cables Limited
Kay Cee Energy and Infra Private Limited
FINOLEX J-POWER SYSTEMS PVT. LTD.
KEI Industries Limited
Polycab India Limited
KEC International Limited
L S CABLE INDIA PVT LTD
Polycab India Limited
FINOLEX J-POWER SYSTEMS PVT. LTD.
Universal Cables Limited
KEI Industries Limited
KEC International Limited
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.07 MB
BIDTN90.pdf
Tender Documents • 5.96 MB
BOQ_458440.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid