THE EXECUTIVE ENGINEER
THE EXECUTIVE ENGINEER NITPY KARAIKAL
ANNUAL MAINTENANCE OF 11KV/433V SUBSTATION 1 EQUIPMENT
2024_NITPY_799151_2
NITPY/P D-E/2024/006
Open Tender
Electrical Works
Works
30 days
NIT PUDUCHERRY
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹12,500
Yes
10 Jul 2024
7 Jun 2024
28 Jun 2024
7 Jun 2024
27 Jun 2024
7 Jun 2024
7 Jun 2024 - 27 Jun 2024
Amount
Service charges for service and testing of 11kv 3 panel VCB MAKE: KIRLOSKAR a) visual for damage b) cleaning, lubricate & oil moving parts c) resistance value of spring charge motor, closing coil & trip coil d) insulation resistance measurement e) contact resistance measurement f) timing test g) bus bar chamber inside painting works
Supply and Replacement of rubber beadings for 3 VCB's
Supply and Replacement of GI bolt nut (as required) including bus bar bolt nut. (*The quantity is mentioned as approximately)
Supply and Replacement of Pole housing with drive Insulator for 1 VCB (if required) *
Supply and Replacement of Vacuum interrupter 11 kV CG WL-34599 M3+S (if required) *
Supply and installation of 250V/110V DC/100VA powerpack for VCB panel (Make: INUTECK or SPZ)
Supply and Installation of L&T change over TNC switch
Supply and Installation of Mechanical counter for VCB
Testing and calibration of over current and earth fault relay
Testing of trip circuit supervision relay
Testing and service of master trip and auxiliary relays
Testing and calibrations of volt meter, ammeter and annunciator
Testing and calibrations of HT energy meter
Testing and calibrations of space heater
Testing and calibrations of thermostat
Testing and calibrations of powerpack units
Testing and calibration of CT, PT a) insulations resistance test b) secondary winding resistance test c) ratio test
Servicing and testing of 630kva, 11kv/433V Transformer with OLTC a) visual checking for oil leakages b) transformer oil filtrations (including filling of transformer oil and transport charges ) c) BDV and Acidity test d) insulation resistance test e) ratio test f) winding resistance test in all TAP of HT &LV windings g) magnetic balance test h) magnetizing current test i) vector group test j) oil and winding temperature meter along with sensor conditions check k) Bucholz relay test
Leakage arrest in Buchholz relay side
Leakage arrest in HV side (if required) *
Leakage arrest in LV side (if required) *
Testing of breather - including supply of Silica Gel
Testing of RTCC panel along with OLTC
Service charges for service and testing of 415V ACB (Make: ABB & L&T) a) visual checking for damage b) cleaning, lubrications of moving parts c) resistance value of spring charge motor and trip coil & closing coil d) insulation resistance test e) contact resistance test f) protection trip test
Testing and calibrations of conserve make MFM meter a) current checking b) voltage checking c) power factor checking d) energy calibration test with three phase injection kit
Servicing and testing of change over switches (including supply and changing of bolt nuts as required)
Servicing and testing of earth electrode (Including supply & replace of SS bolt nuts. as required)
Servicing of all panel board door locks as required
Purchase of Spares
Supply of 11kv Epoxy busbar supporting insulator with bolt nuts
Supply of 9KV lightning arrestor
Supply of transformer oil
Supply of 110V DC trip coil for Kirloskar VCB (110v, R=39Ohm, 636439 No: 92205)
Supply of 250V/110V DC/100VA powerpack for VCB panel (Make: INUTECK or SPZ)
Supply of 8NO and 8NC AUXLERY SWITCH for Kirlosker VCB (SPC 25P 8169/V77 25A/660V AC/DC)
Supply of Earth resistance tester (Analog) Make: CIE
Supply HT gloves (working potential 11kv tested potential 33 kv above molded type)
Supply HT insulation Tape
WINTECH ENGINEERING SERVICES
GRENEL POWERS PVT.LTD.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .