REPAIR AND MAINT OF 33 11 KV SUB STN POWER TRANSFORMER INCLUDING SERVICING OF VCBs CAPACITOR BANK AND ALLIED WORKS AT RMS
2026_MES_778870_2
8153/E8
Open Tender
Civil Works
Item Rate
180 days
DIMAPUR
As per Tender Document
6 documents required · 6 mandatory
₹500
Yes
GE 868 EWS
₹80,000
Yes
29 Aug 2026
8 Aug 2026
5 Sept 2026
8 Aug 2026
29 Aug 2026
15 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material and labour for servicing /testing of transformer circuit breaker, control panel including outdoor CT, PT and relays in control panel of outdoor SF 6 Gas Circuit Breaker of capacity 1250/800 Amps and rating 36 KV complete as details mentioned as under:-
(a) Details of servicing of breaker :-
(i) Checking of Closing/Tripping coil assembly
(ii) Adjustment of mechanism if required.
(iii) Clean the circuit breaker to remove dust and dirt.
(iv) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(v) Visual check for rusted,wear/tear parts.
(vi) Checking of spring charge mechanism
(vii) Visual check for rust and deformation.
(viii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(ix) Check for loosened connections, rust, damaged lead wires.
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & triping coil.
(xii) Replacement of Dashpot/shock absorbers .
(xiii) Replacement of carbon brush of spring charging motor
(xiv) Cleaning of porcelain bushing
(xv) Checking of limit switch etc
(b) The following test shall be carried out:-
(i) Primary Injection Test of outdoor CT / PT
(ii) Closing & Opening Timing Test for all three poles. | 2 | Each job | - | - |
| 1.01 | (iii) IR Test with megger in open and closed condition.
(iv) Contact resistance test for all three poles
(v) Closing coil resistance
(vi) Tripping coil resistance.
(c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :-
(i) Over current and earth fault Relay
(ii) Transformer diffrential relay
(d) Testing of followig Aux relay
(i) DC supply supervision relay.
(ii) CB SF 6 gas pressure low.
(iii) Master trip relay
(iv) Main Buchholz trip
(v) Buchholz OLTC Trip
(vi) SPR & PRV trip.
(vii) Winding temp high trip
(viii) Oil temp high trip.
(ix) Main Buchholz alarm
(x) Winding temp High alarm
(xi) Low Oil level alarm
(xii) Oil temp high alarm
Note:- (i) Certification of testing and calebration from OEM will be provided by the contranctor.
(ii) New spare parts will be replaced by Genuine spare parts only as per OEM authorised/consultation.
(iii) Servicing shall be carried by Rep/Tech of OEM.
(iv) The spare parts reqd for repair/replacement shall be measured and paid as supply only under relavant items and fixing of the same is deemed to be inclusive in this Item. | - | - | - | - |
| 2 | Material and labour for servicing /testing of breaker/control panel including CT, PT and relays in control panel of VCB of capacity 630/400 Amps and rating 11 KV complete as details mentioned as under:-
(a) Details of servicing of breaker :-
(i) Adjustment of mechanism if required.
(ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth.
(iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(iv) Visual check for rusted,wear/tear parts.
(v) Check Spring Tension and pitting of the Cluster Contacts.
(vi) Visual check for rust and deformation.
(vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(viii) Check for loosened connections, rust, damaged lead wires.
(ix) Check whether the contacts are damaged by arcing.
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil.
(xii) Checking of Jaw Contacts Conditions and repair/adjust.
(xiii) Replace the jaw contacts,If required.
(xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish.
(xv) Replacement of Dashpot/shock absorbers . | 10 | Each Job | - | - |
| 2.01 | (xvi) Replacement of carbon brush of spring charging motor
(xvii) Checking, cleaning, tightening , testing the busbars incl bus chambers, CT/PT
(xviii) Checking, cleaning, tightening , testing of support insulator, Spouts etc
(b) The following test shall be carried out:-
(i) Primary Injection Test of CT / PT
(ii) Closing & Opening Timing Test for all three poles.
(iii) IR Test with megger in open and closed condition.
(iv) Contact resistance test for all three poles
(v) Closing coil resistance
(vi) Tripping coil resistance.
(c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :-
(i) Over current and earth fault relay
(d) Testing of followig Aux relay
(i) DC Supply supervision relay.
(ii) Master trip relay
Notes:- (i) Certification of testing and calebration from OEM will be provided by the contranctor.
(ii) New spare parts will be replaced by Genuine spare parts only as per OEM authorised/consultation.
(iii) Servicing shall be carried by Rep/Tech of OEM.
(iv) The spare parts reqd for repair/replacement shall be measured and paid as supply only under relavant items and fixing of the same is deemed to be inclusive in this Item. | - | - | - | - |
| 3 | Supply only big and small gear assembly with handle and bracket suitable for 11 KV HT VCB complete all as specified and as directed. | 2 | Each Set | - | - |
| 4 | Supply only Anti pumping device suitable for 11 KV HT VCB complete all as specified and as directed. | 2 | Each Set | - | - |
| 5 | Supply only Worm wheel with work shaft suitable for 11 KV HT VCB complete all as specified and as directed. | 2 | Each Set | - | - |
| 6 | Supply only HRC fuse of existing sample suitable for 11 KV HT VCB complete all as specified and as directed. | 5 | Each Set | - | - |
| 7 | Supply only voltmeter PT operated suitable for 11 KV HT VCB complete all as specified and as directed. | 2 | Each Set | - | - |
| 8 | Supply only Ammeter CT operated suitable for 11 KV HT VCB complete all as specified and as directed. | 3 | Each Set | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
8153Tenderdoc.pdf
Tender Documents • 1.58 MB
BOQ_877748.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].