Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹1.5 Cr
EMD Value
₹3.1 L
Closing Date
3 Dec 2026, 4:00 pm7d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
EXECUTIVE ENGINEER
MECHANICAL DIVISION BHEP CHANDERKOTE
Upgradation of Fire Fighting System Which Includes Detection System and Fire Panels/ Control Panels and Allied Accessories Installed at PH-I BHEP
2026_SPDC_330988_1
E NIT NO. 21-MECH OF 2026-27 DATED 12.11.2026 DUE ON 03.12.2026
Open Tender
Machineries/ Mechanical Engg Items
Lump-sum
120 days
BHEP CHANDERKOTE
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
CHIEF PAY AND ACCOUNTS OFFICER BHEP CHANDERKOTE
₹3.1 L
BHEP CHANDERKOTE
12 Nov 2026
12 Nov 2026
4 Dec 2026
12 Nov 2026
3 Dec 2026
21 Nov 2026
12 Nov 2026 - 3 Dec 2026
17 Nov 2026
180 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing, and commissioning of an Intelligent Microprocessor-based Addressable Fire Alarm Control Panel, The panel is 1 built-in SLC loop expandable up to 32 loops, supporting up to 256 addressable devices per loop for Class A, and 512 addressable devices per loop for Class B networkable with up to peer-to peer 128 panels via RS485 or Fiber Optic cable. The panel has a minimum 36-zone LED display to indicate Fire, Fault, and Disable conditions. The panel has an inbuilt 24VDC, 3A auxiliary power supply for external device powering. It has a minimum 7 inches touch-sensitive LCD screen with feather -touch buttons for fire/fault indication and multiple LED indicators for clear visual status of fire, fault, disable, and system operation. with address and analog values, support Class A and B wiring, and feature 2 programmable sounder outputs, 6 programmable equipment outputs, 24V DC/3A auxiliary output, and battery backup of 30 mins at fault condition and 24 hours for normal condition. The panel shall be modular and support optional features including FPE monitoring, alarm counter, output delays, and address disablement. The panel has provision for BMS/SCADA integration via MODBUS/BACnet protocol. The panel has built-in programmable relays for alarm and fault events. The panel has provision for graphic software interface to monitor and control the system graphically. The panel shall have an event history log capable of storing a minimum of 10,000 events. The panel has an inbuilt real-time clock for event stamping. The panel shall support a loop length of not less than 1.4 kilometers per loop. The panel shall have an IP rating of IP30 or higher. Each loop can be expanding upto 2000 meter extra by using loop expender module. (System Should be: UL/FM/VDS/LPCB / STQC /LPCB /EN-54 certified.) | 1 | no | 100 | ₹100 |
| 2 | Supply, installation, testing and commissioning of Addressable Multi Detector with embedded MCU, drift compensation, every detector is microprocessor based with 360° LED indication and electronically settable addresses and should not have DIP/rotary addressing and only store the address on memory and dirty detector notification, four programmable sensitivity levels, and two-wire non-polarized loop connection with operating voltage between 16–28 V DC (Modulated-pulse) and provides minimum obscuration ratio - 0.113 to 0.203 dB/m, Heat sensitivity 54° C ~ 65° C and standby Current: ≤ 0.5 m with alarm current: ≤ 1.0 mA having minimum relative humidity: ≤ 95% RH (non-condensing at 40°C ±2°C) . The detector shall have red LED for alarm indication and provide red flashing for LED polling indication The detector is having digital filter for dust discrimination with nuisance alarm indication. It provides minimum Protection Rating: IP32. (System Should be: UL/FM/VDS/LPCB / STQC /LPCB/ EN-54 certified.) | 155 | nos | 100 | ₹15,500 |
| 3 | Supply, installation, testing and commissioning of Addressable Manual Call Point, suitable for indoor use, dual -action hammerless resettable type (operated by special key), and transparent protective cover for accidental activation protection with LED status indication Red alarm LED (steady ON during alarm) Red polling LED (flashing during normal communication) , manual addressing capability, two-wire non-polarized loop connection, operating voltage 16–28V DC, IP43 protection rating, complete with mounting box and accessories and fully compatible with Fire detection alarm panel. (System Should be: UL/FM/LPCB approved and STQC/LPCB/ EN-54 certified.) | 25 | nos | 100 | ₹2,500 |
| 4 | Supply, installation, testing and commissioning of Addressable Sounder cum Strobe (Sounder Beacon), suitable for indoor use, with 16 selectable tones, adjustable sound output up to 4 levels, high-intensity LED for visual alarm, loop-powered operation (no external 24V required for standard use), manual addressing capability, two-wire non-polarized connection, operating voltage 16–28V DC, IP43 protection rating, complete with base and accessories. (System Should be: UL/FM/VDS/LPCB / STQC /LPCB/EN-54 certified.) | 25 | nos | 100 | ₹2,500 |
| 5 | Supply, Installation, Testing and Commissioning of dual IR powered flame detection system designed for critical infrastructure and harsh outdoor environments. The device shall have minimum dual sensors including a 5MP progressive scan super low lux CMOS sensor and an IR flame sensor using 4.3 µm main detection with a 5.0 µm comparative band, and the device shall have a fixed F1.6 4 mm 5MP lens with horizontal field of view of 90° and vertical field of view of 48°. The device is capable of distinguishing radiation spectrum differences produced by sunlight, light and combustion, using two pyroelectric infrared detectors in different bands to ensure high sensitivity detection and very low false alarm rates. The device shall have a minimum built-in mechanism to confirm and filter flame detection results directly at the device side, and the details shall have full-color night view capability with WDR support and selectable 3D DNR levels (disable/ low/middle/high). The device is dual video streams with main stream resolutions up to 2880×1620 @ 25 fps, 2560×1440 @ 25 fps, 1920×1080 @ 25 fps or 1280×720 @ 25 fps and sub stream resolutions selectable down to 640×360 @ 15 fps, with H.265 and H.264 compression, configurable CBR or VBR bitrates, and G.711A or AAC audio compression at 64 kbps. The device has support for TCP/IP (IPv4 and IPv6), HTTP, DHCP, RTSP, NTP, P2P and SIP protocols, and shall have ONVIF and WebRTC interface support with SDK for integration, supporting simultaneous preview of not less than 10 channels. The detector should have minimum built in 2G DTR watchdog for continuous monitoring of the healthiness of the system. The device has built-in 64 GB MicroSD/SDHC/SDXC card local storage, expandable to 128 GB or 256 GB, with support for alarm picture and video push and linkage. The device can integrate hooter to emit sound alerts when smoke or flame is detected, and shall have hardware reset, tamper detection, image quality control, activity monitoring, motion detection with configurable areas and multiple sensitivity levels, and shelter alarm with event linkage for snapshot and recording. The detector should have motion detection, intrusion alert, shelter alarm, flame detection, image quality control incorporated. The detection range should be minimum at 1.5m distance for 30x30 pixel to of at least 30 meters for a 30 cm × 30 cm flame, with a full-screen detection area and self-defined arming schedule, and shall be capable of installation indoors at heights above 2.5 m or outdoors at heights above 3.5 m. The device shall have white LEDs with maximum white light range of 30 m, and shall support operating temperature from –20 °C to +60 °C with ≤90 % relative humidity non-condensing. The device shall have an IP67 ingress protection rating for outdoor weatherproof installation, shall support OSD with title, time, date and up to seven user-defined OSD lines, and shall support firmware upgrades via tool upgrade. The detector shall provide Inbuilt relay(24V@1A) for 3rd party integration with alarm input dry contact and dedicated reset switch. The detector shall have the provision to operate through both DC adaptor or POE switch. The detector shall also have built-in LED alarm indication for normal and alarm condition along with LED flash. (System Should be: UL/FM/ VDS/LPCB / STQC /LPCB / EN-54 certified.) | 60 | nos | 100 | ₹6,000 |
| 6 | Supply, installation, testing and commissioning of Addressable Monitor Module, for monitoring external fire protection devices with EOL supervision, LED indication, two-wire loop connection, 16–28V DC operation, complete with base and accessories. The module has 2 LEDs, Operating indication LED flashing and action LED emitting on signal input with minimum IP32 rating. (System Should be: UL/FM/LPCB approved and STQC/LPCB certified.) | 140 | nos | 100 | ₹14,000 |
| 7 | Supply, installation, testing and commissioning of Addressable Isolator Module, EN54-17 compliant, loop powered, dual isolation with LED indication, 18–28V DC operation, complete with base. Each isolator module shall be equipped with two independent directional LED indicators (Left LED and Right LED) that display the exact zone or loop segment where the short-circuit has occurred. In the event of a short circuit before the isolator, the Left LED shall illuminate. In the event of a short circuit after the isolator, the Right LED shall illuminate. (System Should be: UL/FM/LPCB approved and STQC/LPCB/EN-54 certified.) | 22 | nos | 100 | ₹2,200 |
| 8 | Supply of 10 gram Dosage, Non Corrosive, Non Toxic, DIN Rail mounted two wired, Solid state Automatic Fire Detection and extinguishing capacity minimum 0.1 cum Hot Aerosol Fire Extinguishing device activates by the thermal influence, the vaporized metal ions and cations in the aerosol engage in affinity reactions with active radicals in the combustion process, repeatedly consuming large quantities of active species and efficiently absorbing free radicals in the flame, resulting in chemical inhibition activates at 170℃ temperature and discharge within 6 seconds, suitable to protect enclosure volume of ≤0.1m3, having operating 50~+90℃ . Equipment installation method inside the enclosure on Standard rail mounting. Extinguishing agent contact 50%~58% (for both) of Oxidizer Content / Barium Nitrate Content/ Potassium Nitrate. Shelf Life - 10 years.
Technical Standards:
- XF 499.1-2010 Aerosol Fire Extinguishing System - Part 1: Hot Aerosol Fire Extinguishing Device
- Q/JAD 002-2018 Fast-Response Hot Aerosol Fire Extinguishing Device
- EN 15276-1:2019 International Standard
EN 15276-2:2019 International Standard Product Certification:
= AZT: CERTIFICATE OF CONFORMITY
= ECM & GTS (System Should be: UL/FM/LPCB /ECM/EN 15276-1:2019/ EN 15276-2:2019/EN 15004-1:2024 STANDRED) & MSDS certificated. | 4 | nos | 100 | ₹400 |
| 9 | Supply of 20 gram Dosage, Non Corrosive, Non Toxic, DIN Rail mounted two wired, Solid state Automatic Fire Detection and Hot Aerosol Fire Extinguishing device activates by the thermal influence, the vaporized metal ions and cations in the aerosol engage in affinity reactions with active radicals in the combustion process, repeatedly consuming large quantities of active species and efficiently absorbing free radicals in the flame, resulting in chemical inhibition activates at 170℃ temperature and discharge within 6 seconds, suitable to protect enclosure volume of ≤0.2m3, having operating 50~+90℃ . Equipment installation method inside the enclosure on Standard rail mounting. Extinguishing agent contact 50%~58% (for both) of Oxidizer Content / Barium Nitrate Content/ Potassium Nitrate. Shelf Life - 10 years.
Technical Standards:
- XF 499.1-2010 Aerosol Fire Extinguishing System - Part 1: Hot Aerosol Fire Extinguishing Device
- Q/JAD 002-2018 Fast-Response Hot Aerosol Fire Extinguishing Device
- EN 15276-1:2019 International Standard
EN 15276-2:2019 International Standard Product Certification:
= AZT: CERTIFICATE OF CONFORMITY
= ECM & GTS (System Should be: UL/FM/LPCB /ECM/EN 15276-1:2019/ EN 15276-2:2019/EN 15004-1:2024 STANDRED) & MSDS certificated | 11 | nos | 100 | ₹1,100 |
| 10 | Supply of 30 gram Dosage, On Corrosive, Non Toxic, DIN Rail mounted two wired sensor, Solid state Automatic Fire Detection having extinguishing capacity minimum 0.3 cum and Hot Aerosol Fire Extinguishing device activates by the thermal influence, the vaporized metal ions and cations in the aerosol engage in affinity reactions with active radicals in the combustion process, repeatedly consuming large quantities of active species and efficiently absorbing free radicals in the flame, resulting in chemical inhibition activates at 170℃ temperature and discharge within 6 seconds, suitable to protect enclosure volume of ≤0.3m3, having operating 50~+90℃ . Equipment installation method inside the enclosure on Standard rail mounting. Extinguishing agent contact 50%~58% (for both) of Oxidizer Content / Barium Nitrate Content/ Potassium Nitrate. Shelf Life - 10 years.
Technical Standards:
- XF 499.1-2010 Aerosol Fire Extinguishing System - Part 1: Hot Aerosol Fire Extinguishing Device
- Q/JAD 002-2018 Fast-Response Hot Aerosol Fire Extinguishing Device
- EN 15276-1:2019 International Standard
EN 15276-2:2019 International Standard Product Certification:
= AZT: CERTIFICATE OF CONFORMITY
= ECM & GTS (System Should be: UL/FM/LPCB /ECM/EN 15276-1:2019/ EN 15276-2:2019/EN 15004-1:2024 STANDRED) & MSDS certificated | 6 | nos | 100 | ₹600 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.44 MB
SBD.pdf
Tender Documents • 1.43 MB
BOQ_1123452.xls
BOQ • 0.37 MB
GeneralTendercorrigendum26112026.pdf
PDF • 0.57 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .