E.E. BCD Building Division No.-2, Ranchi
E.E. BCD Building Division No.-2, Ranchi
Supplying, Installing, Testing and Commissioning of a Power Distribution Units for Server Rack, Anti Static Flooring for Server Room, Fire Doors, Rodent Repllant System, Water Leakage Detection System, Gas Suppression System for UPS Room, Access Cont
2026_BCD_116750_1
BCD/Bld. Div.No.-02 Ranchi-06/2026-27
Open Tender
Civil Works - Buildings
Empanelment
30 days
Ranchi
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
11 Aug 2026
1 Aug 2026
10 Aug 2026
1 Aug 2026
8 Aug 2026
1 Aug 2026
Non Schedule Item
Supplying,Installation Testing & Commissioning Services for User Room, UPS Room, Server Room with 75 Inch Display Size & Type with Mutiple inputs display processors for (4 Input display) Screen Size: Minimum 75 inches (189 cm) Panel Type: Commercial-grade LED/LCD panel Resolution: 3840 × 2160 (4K UHD) Brightness: Minimum 500 nits Contrast Ratio: OEM standard for commercial signage panel Viewing Angle: 178° (H/V) or better Operation: 24×7 continuous duty cycle 2. Video & Picture Performance HDR support (HDR10 or equivalent) Anti-glare / haze treatment for professional use Landscape and portrait orientation support Color depth: 10-bit processing or higher 3. Processor & Smart Features Built-in signage SoC (System on Chip) Integrated media player without external PC Support for remote device management software Compatible with centralized display control system
4. Connectivity HDMI inputs: Minimum 3 DisplayPort input: Minimum 1 USB ports: Minimum 2 LAN (RJ-45): 1 Wi-Fi: Built-in Audio Out: Required RS-232C control port for professional integration 5. Mounting & Physical Requirements Slim industrial design suitable for control rooms / conference areas VESA wall-mount compatibility Necessary mounting brackets to be included Provision for cable management 6. Power & Environmental Conditions Power Supply: 100–240V AC, 50/60 Hz Low power standby mode Operating temperature suitable for Indian conditions (minimum 0–40°C) 7. Certification & Compliance BIS certified product Energy-efficient commercial display OEM warranty: 1 Year
Providing, Supplying, Installing, Testing and Commissioning of Main LT Power Distribution Panel and UPS Power Distribution Panel, fabricated from CRCA sheet steel, floor/wall mounted as required, dust and vermin proof, suitable for operation on 415V, 3 Phase, 4 Wire, 50 Hz AC supply system, complete with busbars of suitable current rating, MCCBs/MCBs, metering, indicating lamps, control wiring, cable alleys, earthing terminals, gland plates, danger notices, identification labels and all associated accessories, conforming to relevant IS/IEC standards and CPWD specifications, complete as required and as directed by the Engineer-in-Charge. Main LT Power Distribution Panel Supply, installation, testing and commissioning of Main LT Distribution Panel comprising the following: Incoming: 01 No. 400A, 4 Pole MCCB, draw-out type, with adequate breaking capacity corresponding to the prospective fault level of the system, complete with all standard accessories. Outgoing Feeders: 02 Nos. 250A, 4 Pole MCCBs for IT Load / UPS Input. 04 Nos. 63A, 4 Pole TPN MCBs for In-Row Cooling Units. 04 Nos. 32A, 4 Pole MCBs for small-capacity cooling units, control circuits, lighting and auxiliary loads. The panel shall be complete with suitably rated copper busbars, neutral and earth bars, interconnections, shrouding, internal wiring, engraved ferrules, terminal blocks, space heaters, ventilation arrangements and all accessories required for satisfactory operation. UPS Power Distribution Panel (UPS-PDB) for IT Load Supply, installation, testing and commissioning of UPS Power Distribution Panel suitable for feeding critical IT loads, complete with the following configuration: Incoming: 01 No. 250A, 4 Pole MCCB, draw-out type, having adequate rupturing capacity as per system fault level. Outgoing Feeders: 14 Nos. 32A, TPN MCB outgoing feeders for feeding IT Rack Power Distribution Units (PDUs). The panel shall be complete with copper busbars, neutral and earth bars, interconnections, control wiring, identification labels, metering provisions and all accessories required for complete operation. Power Cabling Providing, laying, dressing, clamping, glanding, terminating, testing and commissioning of the following FRLS/XLPE insulated, PVC sheathed, stranded copper conductor power cables of approved make, including cable trays, saddles, clamps, glands, lugs, ferruling, identification tags and all accessories required for complete installation: The scope shall include transportation, handling, installation, termination at both ends, insulation resistance testing, continuity testing, commissioning, submission of test reports and all incidental works required for completing the installation in a safe and workmanlike manner, complete in all respects and as approved by the Engineer-in-Charge.
Power Cabling
4C x 16 Sqmm CU Flexible Cable for Cooling Unit
1C X 120 Sqmm CU Flexible Cable for UPS Input
5C X 6 Sqmm CU Flex Cable for Power Rack PDU
4C X 4Sqmm CU Flexible cable
Supply, Installation, Testing and Commissioning of maintenance-free Chemical Earthing System specially designed for UPS, PAC Units, Server Racks, SRC Panels and other sensitive IT/Electrical equipment, comprising copper-bonded/GI earth electrode of approved make, earth enhancement compound, HDPE/PVC earth pit chamber with cover, watering arrangement, copper Strip/wire of required size, clamps, lugs, nuts, bolts, excavation, backfilling, interconnections and all other accessories complete.The item includes all labour, materials, tools, testing of earth resistance and commissioning complete in all respects as required at site.
Maintenance free earth electrode with chemical treatment 3mtr long with earth chamber, disconnection link etc complete.
50x6 mm GI Strip (Main Earth Grid Interconnection)
25x3 mm GI Strip (Equipment Bonding)
8 Sq.mm Green Copper Cable (Rack Earthing)
16 Sq.mm Green Copper Cable (UPS Earthing)
16 Sq.mm Copper Cable (Main Panel Earth)
Supply, Installation, Testing and Commissioning of Electronic Rodent Repellent System specially designed for Server Room/Data Centre environment, operating on ultrasonic and electromagnetic technology for effective deterrence of rodents without causing interference to IT, networking and communication equipment. The system shall comprise control unit(s), emitter/transmitter units, power supply arrangement, interconnecting cables, mounting accessories, fixtures and all necessary hardware required for complete installation. The item includes testing, commissioning, demonstration, warranty support and integration with existing electrical infrastructure, complete in all respects as per manufacturer's specifications and as required at site.(Server Room)
Transducers
Master Controller for the above Transduders-VHFO V2 -CONTROLLER
Fittings and Accessories
Rodent cable with PVC conduit
Supply, Installation, Testing and Commissioning of Water Leak Detection System specially designed for Data Centre Server Room applications, comprising microprocessor-based leak detection monitoring panel/controller, sensing cable/probe type leak detectors, zone monitoring modules, alarm annunciation, power supply unit, interface with BMS/DCIM/EMS through potential-free contacts, audio-visual alarm system, communication cabling, conduits, mounting accessories, terminations and all associated hardware. The system shall be capable of detecting water leakage beneath raised floors, around PAC units, chilled water pipelines, CRAC/CRAH units, server racks and other critical areas. The item includes laying and fixing of sensing cable, calibration, testing, integration, commissioning and demonstration of satisfactory performance complete in all respects as per manufacturer's specifications and site requirements.
Conventional Water Leak Detection Panel with Battery Backup
WLD cable
Fittings and Accessories
Electronic Hooter cum Flasher
Access Control System
Supply, Installation, Testing and Commissioning of Spectra Make RFID-Based Access Control System for 4 Doors, comprising intelligent network-based access control panel/controller, RFID card readers on both entry and exit sides of each door, electromagnetic locks (EM Locks)/electromechanical locking devices, door position sensors, exit devices, power supply units with battery backup, communication cabling, conduits, mounting accessories, interface modules, software licenses and all associated hardware required for complete operation of the system. The system shall provide secure access management through RFID smart cards only, with configurable access levels, time schedules and authorization rights for designated personnel. No biometric authentication shall be included in the system. The system shall be provided for the following locations: #Main Entrance Door #Server Room Door #User Room Door #UPS Room Door Each door shall be equipped with RFID card readers on both sides for controlled entry and exit, with centralized monitoring, event logging, user management and audit trail generation through the access control management software. The system shall support creation of individual user profiles, access groups, door-wise permissions, time-zone based access restrictions and reporting functions. The Access Control System shall be integrated with the Fire Alarm System such that, upon receipt of a fire alarm signal, all controlled doors shall automatically unlock/release to provide unrestricted emergency egress and comply with life safety requirements. Necessary interface modules, relay units and interconnecting cabling required for integration with the Fire Alarm System shall be included in the scope. Additionally, a dedicated remote door release/unlock switch shall be provided in the User Room for manual unlocking of the Main Entrance Door. The switch shall enable authorized personnel to release the lock of the Main Entrance Door remotely whenever required. The complete system shall include installation, wiring, programming, configuration, testing, integration, commissioning, user training and demonstration of satisfactory operation, complete in all respects as per Spectra manufacturer's specifications, approved drawings, statutory requirements and site conditions do all complete as required:-
Proximity card Reader
Egress Switch
Accees Card
Power Supply Unit
Electromagnetic Lock –600lbs
Access Software
6 Core x 0.75 Sq mm, multi strand, copper, sheilded,FRLS,Screened cable between the access controller and Card reader
CAT 6 cable with PVC conduit
2 Core x 1.5 Sq mm, multi strand, copper, FRLS,sheilded cable between the access controller and EM Lock/ door sensor /Push Button
Panic Bar
Networked Visual Security Architecture
Supply, Installation, Testing and Commissioning of IP-based Networked Visual Security Architecture comprising Honeywell make Network Video Recorder (NVR) with minimum 8-channel recording capability, integrated with 8 Nos. high-definition IP cameras, complete with minimum 2TB surveillance-grade hard disk storage, video management software, network switches (if required), power supplies, mounting brackets, junction boxes, communication cabling, conduits, connectors, terminations and all associated accessories. The system shall support continuous recording, motion detection, event-based recording, live monitoring, playback, remote viewing, user access management and video export functionalities. Cameras shall be suitable for indoor/outdoor installation as per site requirements and shall provide high-resolution day/night surveillance with infrared (IR) capability where applicable. The NVR shall support network-based video recording, storage, retrieval and monitoring of all connected cameras with provision for integration with Building Management System (BMS), Security Management System (SMS) or other monitoring platforms through standard network protocols, wherever required. The scope shall include laying and fixing of cables, configuration, programming, testing, commissioning, system integration, user training, demonstration of satisfactory performance and submission of all necessary documentation, complete in all respects as per Honeywell manufacturer's specifications, approved drawings and do complete as required at site.
2MP IP Dome cameras
16 Channel Network Video Recorder
8 TB Hard Disc
16 port POE Switch
24 inch Monitor
15 U rack
CAT 6 cable with PVC conduit
PDU Power Distribution Unit
Supply, Installation, Testing and Commissioning of UL Certified Schneider Electric APC NetShelter Metered Rack PDU, 0U vertical mounting type, 3-Phase, 11kW, 230V, 16A, complete with 36 Nos. IEC C13 outlets and 6 Nos. IEC C19 outlets, provided with IEC 309 (3P+N+PE) input plug and cord, suitable for installation in standard 19-inch server racks for distribution of power to servers, storage, networking and other critical IT equipment. The PDU shall be equipped with an integrated digital metering facility for real-time monitoring of electrical parameters including voltage, current, frequency, power consumption and load utilization, with local display indication for efficient power management and load balancing. The scope shall include supply of all mounting accessories, fixing hardware, power connections, terminations, labeling, testing, commissioning, operational verification and integration with rack infrastructure, complete with all associated components and accessories required for satisfactory operation. The item includes installation, configuration, testing, demonstration and handing over of the system complete in all respects as per Schneider Electric APC manufacturer’s specifications and site requirements.
Fire Doors
STEEL FIRE DOOR OF 120 MIN. FIRE RATING STABILITY & INTEGRITY Supply of Navair make uninsulated fire rated GI Sheet doors conforming to FD 120-UD classification of IS 3614 :2021 with fire rating of 120 minutes integrity. The factory manufactured door frame and shutter assembly shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 g/m2 coating as per IS: 277.The Door should be finished with powder coating in standard RAL shade finish having DFT of minimum 50 microns. The door should carry a minimum 500 Hrs of salt spray test. All accressesories like hardware, vision panel, fire & smoke seal etc to be supplied by Fire door manufacturer only as per the guidelines laid down in IS 3614:2021. The offered door must carry a prior valid test evidence of 5 years from NABL Accredited Lab. No fresh testing is required within the validity of test report from NABL Accredited Lab. TheThe Door frame shall be single rebate grooved profile to accomodate 10x4mm Fire Seal, Size of Frame to be minimum 100mm x 57mm made out of minimum 1.20mm thick galvanized steel sheet. Frames shall be butt / mitered joint and field assembeled with bolting system. The frame should also be provided with fire rated smoke seal as per IS: 3614:2021 or as per test evidence. It shall be pasted on surface and perimeter of main frame. All provisions should be mortised & provided with necessary inbuilt reinforcement to receieve appropriate hardware. Frames should be provided with back plate bracket for anchor fastner with 8-10 mm dia and minimum 80 mm long HDG fasteners, with Polyamide sleeves for installation of frame in finished plastered masonary wall opening. Rate are Excluding Grouting.Door leaf should be minimum 46mm thick fully flush double skin door. Door leaf must be manufactured from 1.2mm(18gauge) thick galvanised steel sheet. The infill material shall be Honeycomb. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For double leaf doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. The shutters shall be mounted to the frame with SS 304 grade ball bearing type hinges of size 100x75x3 mm alongwith all suitable hardware(Payable in extra item).Vision lite glass size 200mm x 300mm (max area upto 0.06sqm) wherever applicable should be provided with single layered clear fire rated glass panes as per guidelines laid down under IS 3614 : 2021 vide clause no. 7.2.7 table no. 2 with a clipon arrangement.The glass will be provided with fire rated ceramic tape of suitable size alround on either face. Every Glass pane must carry a permanent marking of SAINT GOBAIN. Door must be tested with vision panel- 6mm thick pyroswiss glass of Saint
1.Single rebated pressed steel frame of section 100x57mm finished with Powder Coating. 2. 46mm thick steel shutter finished with Powder coating. 3. SS Ball Bearing Hinges 100x75x3mm in of GEZE Make-04 Nos. Per Leaf. 4. Mortise Sash Lock With SS Lever Handle With 70mm Long Both Side Key Cylinder Of GEZE Make-01 No. Per Door. 5. SS Concealed Flush Bolt 300mm Long Of GEZE Make-01 No. Per Door. 6. SS Concealed Flush Bolt 600mm Long Of GEZE Make-01 No. Per Door. 7. Overhead Door Closer TS-1100 Of GEZE Make-01 No. Per Leaf 8. Vision Panel Of Size 200x300mm (Fitted With 6mm Thick 120 Min. Fire Rated Clear Toughened Glass PYROSWISS E120 Of SAINTGOBAIN Make)-01 No. Per Leaf
1200mm (W) X 2100mm (H)-Single Leaf
1200mm (W) X 2100mm (H)-Single Leaf with 30 Minutes Insulated
1000mm (W) X 2400mm (H)-
900mm (W) X 2100mm (H)-Single Leaf with 30 Min Insulated
Specially designed flooring for Anti Static Floor in Server Room
The panels are all-steel welded construction, 600x600 mm in size, with the hollow core injected with a lightweight, fire-retardant, non-combustible cementitious compound to ensure support of at least 90% of the top surface area. The panel is factory-laminated with a floor-grade HPL anti-static laminate (typically 1.2mm thick) to the steel surface, and the edges feature an integral trim. The Edge Support Rigid Grid (ESRG) system is used, featuring a continuous box-type stringer for enhanced lateral stability and rolling load performance. The pedestal assembly allows for easy level adjustment for a finish floor height (FFH) up to 300mm (the system can accommodate a range of 65mm - 2000mm). The system is engineered to provide a Uniformly Distributed Load (UDL) of 1350 kg/sq.m with a maximum permissible deflection of 1.52 mm.
Pedestal : the pedestal head assembly shall consist of a 75 x 75 mm x 3.5 mm embossed head mechanically riveted to a 100mm long 19 mm dia rolled formed stud and 2 check nuts for level adjustment and arresting vertical movement. the pedestal head shall consist of an anti-vibrational pvc cap, for panel and stringer location. the pedestal base assembly shall consist of 22.20 mm od pipe of thickness 1.6mm mechanically locked on a press for perpendicularity and then welded to a base plate of 100 x 100 x 2mm thick with stiffening folds. the sub structure assembly shall be suitably anchored to the floor with suitable adhesive or fastener as recommended by the manufacturer. all steel components shall be zinc electro plated.
Providing and fixing hot-dip galvanized steel stringers manufactured from cold-rolled steel construction, specially designed with ribs embossed on three sides to provide strength, lateral stability and improved rolling load performance. The stringers shall support panels on all four sides to ensure proper alignment and rigidity of the raised flooring system. Each stringer shall be provided with countersunk holes at both ends to accommodate bolting with M6 machine screws to the pedestal head assembly. The size of the stringer shall be 21 mm × 32 mm × 0.8 mm thickness and 570 mm in length, complete as per manufacturer’s standard specifications and installation requirements.”
The panels are size of 600 x 600mm
Supply of Tile puller
skirting to be included in Data center
2 to 3 mm anti-static epoxy flooring
Providing, fixing of Blanking Plate of Blanking Plates for UPS Panel Boards with complete as accessories
Suppyling, installation, testing and Commissioning of Monitoring of Temp Lamp Board for UPS near Main incomer of UPS from LT Panel with complete as reqired
Supply, Installation, Testing & Commissioning of Communication Card compatible with Liberty APM2.3 120 kVA, 3-Phase Modular UPS, complete with all necessary hardware, interface cables, mounting accessories, configuration, programming, integration with the UPS monitoring system/BMS (where applicable), testing, commissioning, and satisfactory demonstration of all communication and monitoring functions, as required for complete operation, in accordance with the manufacturer's specifications and as directed by the Engineer-in-Charge.
Supply, Installation, Testing & Commissioning of battery interlinking connectors for Connecting 2 UPS battery bank, comprising heavy-duty flexible copper interconnecting leads of suitable cross-sectional area with PVC/XLPE insulation, complete with tinned copper crimping lugs, nuts, bolts, spring washers, insulating sleeves, identification ferrules, heat-shrink sleeves and all other accessories required for interconnection of battery cells/monoblocks to form the complete battery bank, including termination, dressing, testing and commissioning, complete as required and as directed by the Engineer-in-Charge.
Supply, Installation, Testing & Commissioning of Nyvin make battery interconnecting cables of suitable cross-sectional area for UPS battery bank, comprising multi-strand copper conductor with PVC/XLPE insulation, complete with tinned copper crimping lugs, nuts, bolts, washers, insulating sleeves, ferrules and all accessories required for interconnection of battery cells/blocks, including laying, termination, testing and commissioning, complete as required and as directed by the Engineer-in-Charge.
Supply, Installation, Testing & Commissioning of ASPEN MAX HI-FLOW Condensate Drain Pump, specially designed and suitable for Vertiv SRC Precision Air Conditioning Units, complete with reservoir, float switch, anti-siphon device, power and control wiring, drain piping/tubing, fittings, clamps, supports, insulation, termination accessories, interconnections and all associated materials required for proper condensate drainage from the unit. The work shall include fixing of drain pump, laying and termination of drain line up to the designated discharge point, electrical wiring from source to pump, control integration with the Vertiv SRC unit, testing of automatic operation, leak testing, commissioning and satisfactory performance demonstration, complete in all respects as per manufacturer's recommendations and as directed by the Engineer-in-Charge.
Supply, Installation, Testing and Commissioning of Mitsubshi Heavy Duty 2 Ton Air Conditioner for NOC Room Supply, installation, testing, commissioning, and satisfactory operation of Mitsubshi Heavy Duty Split Air Conditioner, 2 Ton Capacity, suitable for continuous 24x7 operation in the Network Operations Center (NOC) Room, complete with all accessories, fittings, mounting arrangements, interconnecting refrigerant piping, electrical cabling, drainage piping, and associated works required for proper functioning. Technical Specifications 1. Type: High Wall Split Air Conditioner. 2. Make: Mitsubshi Heavy Duty or equivalent approved brand of equal or higher specifications. 3. Capacity: 2 Ton (Minimum 24,000 BTU/hr). 4. Operation: Suitable for uninterrupted 24x7 operation in mission-critical environments such as NOC/Data Center rooms. 5. Energy Efficiency: Minimum 3-Star Rating or latest applicable BEE rating. 6. Refrigerant: Environment-friendly refrigerant (R-32 or latest approved refrigerant). 7. Compressor: Inverter Rotary/Scroll Compressor with high reliability and low noise operation. 8. Cooling Performance: Capable of maintaining room temperature between 20°C to 24°C under design load conditions. 9. Power Supply: 230V ±10%, 50Hz, Single Phase. 10. Air Filtration: Equipped with washable and anti-bacterial air filters. 11. Condenser Coil: Copper condenser with anti-corrosion coating. 12. Evaporator Coil: Copper tube evaporator coil. 13. Noise Level: Low-noise operation suitable for NOC environment. 14. Remote Controller: Wireless remote controller with all standard operating functions. 15. Safety Features: High/Low voltage protection, overload protection, auto restart, and self-diagnostic features. Installation Requirements 1. Installation shall include indoor and outdoor unit mounting with suitable brackets/stands. 2. Copper refrigerant piping with insulation, control cable, power cable, and PVC condensate drain piping shall be included in the quoted rate. 3. All electrical and civil works necessary for complete installation shall be carried out by the contractor. 4. The unit shall be tested and commissioned in the presence of the department's authorized representative. 5. Necessary vibration isolation pads and weather protection arrangements for the outdoor unit shall be provided. Warranty 1. Minimum 1-year comprehensive onsite warranty for the complete unit. 2. Minimum 5-year warranty on compressor or as per OEM standard warranty policy, whichever is higher. 3. During the warranty period, all repairs, replacement of defective parts, and maintenance services shall be provided free of cost. Compliance The offered equipment shall be genuine OEM product, brand new, unused, and supplied with all relevant technical literature, warranty certificates, and test certificates. The bidder shall submit manufacturer authorization, product datasheets, and compliance statement against the tender specifications..
Supply, Installation, Testing and Commissioning (SITC) of Liebert RDU 501 Remote Monitoring and Management Unit complete with all accessories, communication interfaces, cabling, software configuration, integration with existing server room infrastructure, testing, documentation and commissioning at the Server Room of Jharkhand High Court, complete in all respects as per technical specifications and directions of the Engineer-in-Charge. Scope of Work: The contractor shall supply, install, test and commission one (01) number Liebert RDU 501 (or OEM-authorized equivalent model, if approved by the Engineer-in-Charge) for centralized monitoring and management of critical infrastructure installed in the Server Room of Jharkhand High Court. The scope shall include, but not be limited to, the following: 1. Supply of Liebert RDU 501 complete with all standard accessories, mounting hardware, communication modules, software licenses (if applicable), power adapters and interface cables required for successful operation. 2. Installation and integration of the RDU 501 with existing critical infrastructure equipment including UPS systems, precision air-conditioning units, environmental monitoring devices, power distribution units (PDUs), sensors and other compatible equipment available in the Server Room. 3. Provision and laying of all necessary communication cables, connectors, network patch cords, termination accessories, conduits/trunking and associated materials required for complete installation. 4. Configuration of the system for remote monitoring, alarm management, event logging, reporting and notification through web interface, e-mail and other supported communication methods. 5. Integration with the existing LAN/network infrastructure of Jharkhand High Court in coordination with the designated IT/Technical team. 6. Testing of all communication interfaces, monitoring parameters, alarms, event notifications and reporting functions to ensure satisfactory performance.
Supply, delivery, installation, testing, and commissioning of thermal insulation for the Server Room raised floor and ceiling using approved elastomeric insulation material. Technical Specification Providing and fixing thermal insulation using 19 mm thick / 16 mm thick K-FLEX or equivalent approved closed-cell elastomeric nitrile rubber insulation of Class 'O' fire performance, having low thermal conductivity, high resistance to water vapour diffusion, and suitable for HVAC and critical server room applications. The insulation shall be installed continuously below the raised access flooring and above the ceiling, complete in all respects as per the approved drawings and manufacturer's recommendations. All insulation joints, seams, edges, and terminations shall be properly aligned and sealed using the manufacturer's recommended adhesive to ensure a continuous vapour barrier and prevent air leakage, condensation, and thermal bridging. The finished installation shall be neat, uniform, and free from gaps, cracks, wrinkles, or damaged portions. The insulation material shall conform to the following minimum requirements: * Type: Closed-cell elastomeric nitrile rubber insulation. * Thickness: 19 mm for flooring and 16 mm for ceiling (or as indicated in the drawings/BOQ). * Fire Performance: Class 'O' as per applicable standards. * Thermal Conductivity: As per manufacturer's published data. * Water Vapour Diffusion Resistance: Suitable for condensation control in air-conditioned server room environments. * Installation: Complete with all accessories, adhesives, sealants, cutting, fitting, wastage, and finishing.
Total
Add GST @ 18 % in total of above all items.
Total with GST
Add Labour Cess @1%
Grand Total =
stage.html
html • 0.02 MB
finance_157855.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
NIQ-Rate-06.XLSX
Additional Documents • 0.03 MB
NIQ.pdf
Tender Documents • 0.41 MB
Corrigendum.pdf
PDF • 0.14 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .