Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.9 LAccepted-AOC 3 N K CHATTERJEE STREET KOLKATA 700 056 | KOLKATA | KOLKATA | WEST BENGAL | 700056 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹37.3 L+₹5.5 L (17.1%)Rejected-Finance 39 MAHESHMATI BANK COLONI MALDA WEST BENGAL | MALDA | MALDA | WEST BENGAL | 732101 | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹37.6 L+₹5.7 L (18.0%)Rejected-Finance 104 RASHTRAGURU AVENUE DUM DUM NAGERBAZAR KOLKATA 700028 | KOLKATA | HOOGHLY | WEST BENGAL | 700028 | L3 | Rejected-Finance 3rd lowest bidder |
Tender Value
Refer Docs
EMD Value
₹63,810
Closing Date
4 Aug 2021, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE_I, Kol. South Health El. Divn.,P.W.Dte.
75 D H Road Kidderpore Kol_23
Upgradation of capacity of Morgue with SITC of 2 nos 6 body mortuary cooler units at proposed G plus 1 storied building and renovation of existing morgue to cope up with upcoming 3rd wave of COVID pandemic at Sambhu Nath Pandit Hospital Kolkata.
2021_WBPWD_336451_1
WBPWD/KSHED/Q22/21-22
Open Tender
A/C ORG
Item Rate
30 days
Kolkata
Please refer Tender documents.
2 documents required · 2 mandatory
₹63,810
O/o Exe.Engr., Kol. South Health El. Divn., PWDte.
22 Nov 2021
14 Jul 2021
6 Aug 2021
14 Jul 2021
4 Aug 2021
24 Jul 2021
23 Jul 2021
120 days
Amount
Supply & Installation of 06 body mortuary chamber (Dimension-- L- 7'-6"ft x D-9'-6"ft x H-5-0’ft) costructed with well seasoned & treated wooden frame work, GI mesh wire net, anti-rat protection, 4mm. thick standard size glass tiles layer and 100mm thick thermocol insulative board on walls, ceiling & floor including finishing with cement plastering & suitable painting. Floor will be finished by 50mm thick cement concert casting including neat cement finish after thermal insulation. "U" Shaped drainage arrangement by glaze tiles including S & F siphon system drainage pipe will be in side walls.
Supply & Installation of 415V. 3Ph 50Hz 5 TR Capacity Air Cooled Condensing unit (1W+1S) with R-22 refrigerant complete with Sealed Unit compressor, heavy duty Copper Condenser coil, Blower Motor (18" Crompton Greaves), Receiver, Accumulator, Condenser Fan Motor, Service Valve, and LP/HP cut out Switch, Condenser Housing and Complete Angle Iron Unit base with brick foundation for both Stand by unit as well as working unit (as replacement of existing 2 nos. 2 x 8 Body Mortuary cooler)
Supply & Installation of 415V. 3Ph 50Hz 5 TR Capacity Air Cooled Condensing unit (1W+1S) with R-22 refrigerant complete with Sealed Unit compressor, heavy duty Copper Condenser coil, Blower Motor (18" Crompton Greaves), Receiver, Accumulator, Condenser Fan Motor, Service Valve, and LP/HP cut out Switch, Condenser Housing and Complete Angle Iron Unit base with brick foundation for both Stand by unit as well as working unit (for the new 2 nos. 2 x 6 Body Mortuary cooler)
Supply & Installation of 5 Ton Capacity low temperature cooling coil (Desired Temperature :- 40 ⁰F ± 2 ⁰F) made by heavy duty 5/8 " dia copper pipe with distributor, angle Iron frame with blower motor & base, fan blade and Vibration shock absorption rubber base complete set. (For new & existing units)
Supply & fixing new mortuary doors (Size 4" x 4" & 4" x 5") for the 6 body mortuary made of well seasoned & treated Sal wood including adequate 4" thick inner outer insulation against heat leakage, covering with 24 SWG Aluminum sheet & finished with paint, complete with door gasket, thickly chromium plated brass hinges, latches & locking arrangement fixed on the wooden frame work of mortuary chamber.
Replacement of damaged mortuary doors of 8 body chamber with Supply & fixing wooden doors of suitable Size as per site made of well seasoned & treated Sal wood including adequate 4" thick insulation against heat leakage covering with 24 SWG Aluminum sheet & finished with paint completed with door gasket, brass hinges & latches,& locking arrangement fixed on the wooden frame work of mortuary chamber.
Supply & fixing new cooling coil inspection doors with wooden frame (Size 4" x 4" & 4" x 5") at the back of the cooling coil made of well seasoned & treated Sal wood including adequate 4" thick inner outer insulation against heat leakage, covering with 24 SWG Aluminum sheet & finished with paint, complete with door gasket, thickly chromium plated brass hinges, latches & locking arrangement fixed on the wooden frame work of mortuary chamber.
Construction of cooling coil base by bricks, sand and cement with required necessary masonry work inside the cooling chamber including insulation of the same by 4" thermocol, wire mesh net, "U" hocks with plaster finish and neat cement at the top of the base to accommodate 2 no's cooling coil for each chamber.
Supply & Installation Complete arrangement of 3 track-2 tire self type structure of welded 3” x 3” x 3/8 “ angle iron with necessary cross sectional joint for accomodating the mortuary trays would be insulated inside of the morgue as per drawings. The structure will have two coats of red oxide and two coats of grey enameled paint.
Supply & Charging R –22Gas.
Supply & Delivery, fixing of Mortuary tray each having dimensions 24"x72" long & fabricated by 20 SWG SS Sheet & placed on requisite angle iron frame on (40mm x 40mm x 6mm) complete. With 4 Wheels MS pin and Handel including sliding arrangement on the frame for pulling the trays on wheels.
S & drawing refrigerant pipe lines for suction line, Discharge line, Condenser to receiver pipe line of with suitable sizes copper pipe including S& Fixing Thermostat Switch, Expansion Valve, Solenoid Valve, Hand Shutoff Valve, Drier, Dial type Thermometer, necessary brass flayer nut, suction line insulation complete in all respect as per direction of E.I.C
Cost of Thorough testing of the complete Installation of the Plant including High pressure dry Nitrogen gas pressure testing 48 hrs, with thorough system vacuum testing 48hrs,with testing the plant proper maintaining desired temperature.
Supply & Installation of wall mounting cubicle type 415 Volt, 50 Hz. electrical control panel fabricated from 40 x 40 x 5 mm MS angle and 40 x 5 mm MS flat & painting with 2 coats of Synthetic Enamel paint over 1 coat of RO primer & earthing attachment comprising with following electrical accessories & interconnection with suitable copper wire including wiring in between panel board to condensing unit & cooling unit motor with inter locking connection by suitable size of copper wire from condensing unit to control panel through PVC rigid pipe incl. proper earthing arrangement.
INCOMER: 415V, 63 amps TPN MCB (10 KA, C-Curve) (Make-Legrand/ABB/Schneider) - 1 no
OUTGOING: 440 V, 32 amps TPN MCB (Make-Legrand/ABB/Schneider) - 2nos
BUSBAR: 100 Amp capacity 99.9% - 99.5% electrolytic tinned copper 4 bar bus bar [size of flat 4 x 20 mm x 3 mm] mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification & all connection made with required size cu bars - 1set.
CONTROLLING: 415 V, DOL Starters with over load relay (relay rang 9-14 amps), ( Make-LT/LK MUG-10) -2 nos
METERING: 240 V, 10 A SPMCB (10 KA, C-Curve) 3 NOS, Voltmeter, Ammeter & 3 NOS CT coils of suitable specification & brand .
INDICATORS: 3 nos LED R, Y, B indicators (Siemens) with 3 nos 250V, 6A SPMCB (10 KA, C-Curve) (Make-Legrand/ABB/Schneider)
SAFETY: Single Phase Preventer & EI Danger board 1 no.
Cost of renovation of the existing 2 nos 8 body mortuary cooler units with repair & renovation of different spare parts such as hand shutt off valve, flair nut, Drier, Solenoid valve, Digital Temperature Meter, including refrigeration copper piping & insulation, thorough testing of the Plant with dry Nitrogen in high pressure & commissioning of the same after vacuuming & charging with refrigerant for desired temperature & satisfactory operation as per direction of EIC.
Terms and condition
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liability period 1 (One) Year
GITANJALI ELECTRONICS AND ELECTRICALS
SNOWLINE ENGINEERS
stage.html
html • 0.05 MB
technical_641880.pdf
PDF • 0.09 MB
techsummary_641880.pdf
PDF • 0.09 MB
finance_641880.pdf
PDF • 0.09 MB
BOQ Comparative Chart
xlsx • 0.01 MB
finsummary_641880.pdf
PDF • 0.09 MB
AOC.pdf
PDF • 0.37 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .