| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 CrAdmitted-Finance | ₹4.3 Cr | L1 | Admitted-Finance |
| 2 | L2₹5.2 Cr+₹92.2 L (21.4%)Admitted-Finance | ₹5.2 Cr+₹92.2 L (21.4%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | JK Electric Engineers Pvt. Ltd. L1 | Trade Linkers Associates L2 |
|---|---|---|---|---|---|
| 1.00Supply of material | |||||
| 1.01 | 50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and
other required accessories and fittings. Complete in all Respects including NCT and relays for pannel. | 1 | No | 3,39,06,400 ₹3,39,06,400 Lowest | 4,05,00,000 ₹4,05,00,000 |
| 2.00STRUCTURES | |||||
| 2.01 | Galvanised Structures | 6.7 | MT | 1,00,000 ₹6,70,000 Lowest | 1,30,000 ₹8,71,000 |
| 2.02 | Galvanised Nuts and Bolts | 0.4 | MT | 1,28,000 ₹51,200 Lowest | 1,40,000 ₹56,000 |
| 3.00POWER AND CONTROL CABLES | |||||
| 3.10 | 3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete | 200 | Mts | 945 ₹1,89,000 | 700 ₹1,40,000 Lowest |
| 3.20 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete | 600 | Mts | 465 ₹2,79,000 Lowest | 800 ₹4,80,000 |
| 3.30 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete | 600 | Mts | 545 ₹3,27,000 Lowest | 900 ₹5,40,000 |
| 4.00CONDUCTOR AND HARD WARE FITTINGS | |||||
Tender Value
₹4.3 Cr
EMD Value
₹8.5 L
Closing Date
19 Mar 2021, 4:00 pmClosed
Executive Engineer, TLMD-VIII, JKPTCL, Jammu
Office of the Executive Engineer, TLMD-VIII,JKPTCL, Ambedkar Chowk, Jammu
Augmentation of 132/33KV Grid Station Jourian from 20MVA to 50MVA by way of replacement of existing 20MVA Transformer with 50MVA Power Transformer
2021_PDD_118473_1
E NIt no TLMD-VIII/J/33 of 2020-21 dt- 26/02/2020
Open Tender
Electrical Works
Turn-key
180 days
Grid Station Jourian (kaleeth)
Please refer Tender documents.
3 documents required · 3 mandatory
₹10,000
Executive Engineer, TLMD-VIII, JKPTCL, Jammu
₹8.5 L
office of the Executive Engineer, TLMD-VIII, Jammu
29 Mar 2021
27 Feb 2021
23 Mar 2021
27 Feb 2021
19 Mar 2021
27 Feb 2021
6 Mar 2021
Amount
Supply of material
50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings. Complete in all Respects including NCT and relays for pannel.
STRUCTURES
Galvanised Structures
Galvanised Nuts and Bolts
POWER AND CONTROL CABLES
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Erection Testing and Commissioning
50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings. Complete in all Respects including relays for pannel.
STRUCTURES
Galvanised Structures
Galvanised Nuts and Bolts
POWER AND CONTROL CABLES
3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
CONDUCTOR AND HARD WARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Erection Charges of dismantled 33 KV LA's along with structure and all the allied acessories.
Errection Charges of dismantled 132 LA's along with structure and all the allied acessories.
Dismantling
Dismantling of galvanised Structure of transformer yard.
Dismantling of 33 KV LAs including structure and foundation
Dismantling of existing 20 MVA Transformer along with acessories
Dismantling of conductor and hardware fittings of transformer yard
Dismantling of 132 KV LAs including structure and foundation.
Loading unloading and carriage
Loading unloading and carriage of 20 MVA Transformer and allied acessories from Grid Station Jourian(Kaleeth) to Divisional Store Narwal( avg. distance 45 Kms)
CIVIL WORKS including material in all respect
Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing
Concreting of Transformer yard & Laying Of Gravel
Concreting of 33 KV yard & Laying Of Gravel
Concreting of 132 KV yard Laying Of Gravel
Rail Track
Fire protection Walls
Laying of Transformer foundations for Three phase 50 MVA Transformer (as per Drawing)
Construction of Oil sump & Tank for three phase 50 MVA Transformer (as per Drawing)
Laying of 132KV Column foundations (as per Drawing)
Laying of 33KV LA foundations (as per Drawing)
Laying of 132KV LA foundations (as per Drawing)
Trade Linkers Associates
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.74 MB
SBDNIT33.pdf
Tender Documents • 4.36 MB
BOQ_227678.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .