Loading…
Loading…
Tender Value
₹48.0 L
EMD Value
₹96,000
Closing Date
30 Jul 2026, 3:00 pm5d left
1)Electrical (General) work in connection with "Construction of new LHS in lieu of LC Gate No. 16/C/E in B.K section under AEN/KWAE". 2) Electrical (General) work in connection with "Construction of new LHS in lieu of LC Gate No. 3/C/E in A.K section under AEN/KWAE" 3) Electrical (General) work in connection with "Construction of new LHS in lieu of LC Gate No. 21/C/E in B.K section under AEN/KWAE". 4)Electrical (General) work in connection with "Construction of new LHS in lieu of LC Gate No. 24/02 by Railway's relieving girder under AEN/KWAE" 5) - Electrical (General) work in connection with "Construction of Limited Height Subway in lieu of L.C. No. 18/6/C/E at Km 89/21-23 & 89/24-22 (DN) in between Station PTAE-AGAE in BB Loop under AEN/KWAE"
EL-HWH-25-21-3579
EL-HWH-25-21-3579
Open
Works - General
180 Days
Jalgaon, Maharashtra
₹0
₹96,000
7 Jul 2026
7 Jul 2026
16 Jul 2026
A-Electrical (General) work in connection with "Construction of new LHS
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 1 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral 2 in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 4 nos. single core HRFR / FRLS 3 grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for three phases and one neutral in GI conduit of 25mm dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Supply of Submersible Sewage Pump-Motor set of discharge capacity 92 Cubic metre per hour and discahrge head 9 Mtrs. (approx.) suitable for operation on 415V, 50 Hz, 3Ph / 240V, 50 4 Hz, 1 Ph supply system complete with one fully automatic starter control panel with all protection and float switch alongwith 10 Mtrs. long multicore copper flexible cable of suitable size for motor operation, 5 mtr. Lifting Iron Chain, GI clamps, steel wire rope with double pulley, PVC flexible pipe of suitable size and length including installation and commissioning. ( Make of pump-motor set - KSB / Texmo / CRI / Kirloskar / Crompton / Calama ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Trenching and laying of cable under ground by soil cutting with covering of cable by sand and bricks / through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN- 10 or higher) without bricks alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) Above/
Supply of GI ( minimum coating thickness 65 microns ) conical / octagonal ( minimum sheet thickness - 3mm ) Pole of overall length 5 M with single / double arm bracket, top cover, base plate including hinged door-inbuilt Junction box complete with copper bar, insulator, Hylam sheet for cable termination and fuse kit-kat / MCB ( Make - Utkarsh / B.P. Projects / Crompton / Bajaj / Surya ) Above/
RCC foundation, erection and commissioning of above GI pole with construction of 11 cement concrete muffing ( Cement : Stone : Sand = 1 : 2 : 4 ) with foundation accessories including earthing of pole with 1 no. of 50 mm dia, 3 M long GI pipe ( Make - TATA / Jindal / Bansal ) with necessary earth connection from pipe to pole by GI Strip / GI wire Above/
Wiring of light point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 12 conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral through pole from inbuilt pole Junction Box's porcelain fuse kit-kat / MCB to light fitting along with 1 no. single core HRFR / FRLS grade, PVC insulated copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Dismantling / Cutting of existing pole and make good of surface including transportation from site to stores Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 14 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 15 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition Above/
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition Above/
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) Above/
Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall ( LED Street light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of out door LED Flood light / Street Light fitting on High Mast Tower / Pole / Structure with suitable arrangement. ( LED outdoor light fitting will be supplied by Railway ) Above/
Installation, connection and commissioning of Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Wall Bracket Fan will be supplied by Railway ) Above/
Supply of SPN DB ( Metal Enclosure with Metal Door ), 8 way, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of MCCB with Thermal - Magnetic Release of breaking capacity 36 kA at 415V AC, 50Hz of capacity 25-32A / 32-40A / 40-50A, 4 Pole complete with metal enclosure with spreader terminals including fixing, connection, testing and commissioning. ( Make - LK(L&T) /Siemens / ABB / Hager / Legrand / Schneider / C&S ) Above/
Supply of Sheet Moulded Compound ( SMC ) JB box, fire retardant of size 250 x 250 x 27 155 mm ( IP-55 ) / equivalent size heavy duty, outdoor type, UV ray protected, self fire- extinguishing, shock resistance IK08 or above and IP65 degree of protection grade transparent polycarbonate DB box including fitment with suitable size and shape Mild Steel ( MS ) bracket by replacing existing damage box and accessories with testing and commissioning. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of Dust and vermin proof metal Busbar Chamber made of 16 SWG ( 1.6mm ) 28 MS sheet duly powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 100 Amp, 4 way, suitable for 415V, 50Hz supply system including all accessories alongwith fixing, connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. ( Make - Havells / Standard / HPL / C&S / LK (L&T) / Indoasian ) Above/
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 25-63 ) Amp, 4 Pole - 1 no. b) MCB, 4 Pole, 32Amp, 415V, 50Hz, 10kA ( C-curve ) - 2 nos. c) MCB, 2 Pole, 10Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. d) Power Contactor, 3 Pole, 12A, 415V, 50Hz - 2 nos. e) Astronomical Timer Switch - 2 nos. f) Tinned Copper Busbar ( 4 Bar ) each of capacity 100 Amps., 415V, 50 Hz - 1 set g) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. h) CT of suitable ratio for MFM - 3 nos. i) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 6 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) Above/
Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Above/
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed )
B- Electrical (General) work in connection with "Construction of new LHS
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 32 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 33 grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 4 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for three phases and 34 one neutral in GI conduit of 25mm dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Supply of Submersible Sewage Pump-Motor set of discharge capacity 92 Cubic metre per hour and discahrge head 9 Mtrs. (approx.) suitable for operation on 415V, 50 Hz, 3Ph / 240V, 50 35 Hz, 1 Ph supply system complete with one fully automatic starter control panel with all protection and float switch alongwith 10 Mtrs. long multicore copper flexible cable of suitable size for motor operation, 5 mtr. Lifting Iron Chain, GI clamps, steel wire rope with double pulley, PVC flexible pipe of suitable size and length including installation and commissioning. ( Make of pump-motor set - KSB / Texmo / CRI / Kirloskar / Crompton / Calama ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Trenching and laying of cable under ground by soil cutting with covering of cable by sand and bricks / through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN- 10 or higher) without bricks alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) Above/
Supply of GI ( minimum coating thickness 65 microns ) conical / octagonal ( minimum sheet thickness - 3mm ) Pole of overall length 5 M with single / double arm bracket, top cover, base plate including hinged door-inbuilt Junction box complete with copper bar, insulator, Hylam sheet for cable termination and fuse kit-kat / MCB ( Make - Utkarsh / B.P. Projects / Crompton / Bajaj / Surya ) Above/
RCC foundation, erection and commissioning of above GI pole with construction of cement concrete muffing ( Cement : Stone : Sand = 1 : 2 : 4 ) with foundation accessories including earthing of pole with 1 no. of 50 mm dia, 3 M long GI pipe ( Make - TATA / Jindal / Bansal ) with necessary earth connection from pipe to pole by GI Strip / GI wire Above/
Wiring of light point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral through pole from inbuilt pole 43 Junction Box's porcelain fuse kit-kat / MCB to light fitting along with 1 no. single core HRFR / FRLS grade, PVC insulated copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Dismantling / Cutting of existing pole and make good of surface including transportation from site to stores Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 45 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 46 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition Above/
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition Above/
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) Above/
Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall ( LED Street light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of out door LED Flood light / Street Light fitting 53 on High Mast Tower / Pole / Structure with suitable arrangement. ( LED outdoor light fitting will be supplied by Railway ) Above/
Installation, connection and commissioning of Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Wall Bracket Fan will be supplied by Railway ) Above/
Supply of SPN DB ( Metal Enclosure with Metal Door ), 8 way, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of MCCB with Thermal - Magnetic Release of breaking capacity 36 kA at 415V AC, 50Hz of capacity 25-32A / 32-40A / 40-50A, 4 Pole complete with metal enclosure with spreader terminals including fixing, connection, testing and commissioning. ( Make - LK(L&T) /Siemens / ABB / Hager / Legrand / Schneider / C&S ) Above/
Supply of Sheet Moulded Compound ( SMC ) JB box, fire retardant of size 250 x 250 x 58 155 mm ( IP-55 ) / equivalent size heavy duty, outdoor type, UV ray protected, self fire- extinguishing, shock resistance IK08 or above and IP65 degree of protection grade transparent polycarbonate DB box including fitment with suitable size and shape Mild Steel ( MS ) bracket by replacing existing damage box and accessories with testing and commissioning. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of Dust and vermin proof metal Busbar Chamber made of 16 SWG ( 1.6mm ) 59 MS sheet duly powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 100 Amp, 4 way, suitable for 415V, 50Hz supply system including all accessories alongwith fixing, connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. ( Make - Havells / Standard / HPL / C&S / LK (L&T) / Indoasian ) Above/
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 25-63 ) Amp, 4 Pole - 1 no. b) MCB, 4 Pole, 32Amp, 415V, 50Hz, 10kA ( C-curve ) - 2 nos. c) MCB, 2 Pole, 10Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. d) Power Contactor, 3 Pole, 12A, 415V, 50Hz - 2 nos. e) Astronomical Timer Switch - 2 nos. f) Tinned Copper Busbar ( 4 Bar ) each of capacity 100 Amps., 415V, 50 Hz - 1 set g) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. h) CT of suitable ratio for MFM - 3 nos.i) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 6 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) Above/
Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Above/
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed )
C-Electrical (General) work in connection with "Construction of new LHS
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 63 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 64 grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 4 nos. single core HRFR / FRLS 65 grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for three phases and one neutral in GI conduit of 25mm dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Supply of Submersible Sewage Pump-Motor set of discharge capacity 92 Cubic metre per hour and discahrge head 9 Mtrs. (approx.) suitable for operation on 415V, 50 Hz, 3Ph / 240V, 50 66 Hz, 1 Ph supply system complete with one fully automatic starter control panel with all protection and float switch alongwith 10 Mtrs. long multicore copper flexible cable of suitable size for motor operation, 5 mtr. Lifting Iron Chain, GI clamps, steel wire rope with double pulley, PVC flexible pipe of suitable size and length including installation and commissioning. ( Make of pump-motor set - KSB / Texmo / CRI / Kirloskar / Crompton / Calama ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Trenching and laying of cable under ground by soil cutting with covering of cable by 67 sand and bricks / through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN- 10 or higher) without bricks alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) Above/
Supply of GI ( minimum coating thickness 65 microns ) conical / octagonal ( minimum sheet thickness - 3mm ) Pole of overall length 5 M with single / double arm bracket, top cover, base plate including hinged door-inbuilt Junction box complete with copper bar, insulator, Hylam sheet for cable termination and fuse kit-kat / MCB ( Make - Utkarsh / B.P. Projects / Crompton / Bajaj / Surya ) Above/
RCC foundation, erection and commissioning of above GI pole with construction of cement concrete muffing ( Cement : Stone : Sand = 1 : 2 : 4 ) with foundation accessories including earthing of pole with 1 no. of 50 mm dia, 3 M long GI pipe ( Make - TATA / Jindal / Bansal ) with necessary earth connection from pipe to pole by GI Strip / GI wire Above/
Wiring of light point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 74 conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral through pole from inbuilt pole Junction Box's porcelain fuse kit-kat / MCB to light fitting along with 1 no. single core HRFR / FRLS grade, PVC insulated copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Dismantling / Cutting of existing pole and make good of surface including transportation from site to stores Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 76 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition Above/
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition Above/
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) Above/
Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall ( LED Street light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of out door LED Flood light / Street Light fitting on High Mast Tower / Pole / Structure with suitable arrangement. ( LED outdoor light fitting will be supplied by Railway ) Above/
Installation, connection and commissioning of Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Wall Bracket Fan will be supplied by Railway ) Above/
Supply of SPN DB ( Metal Enclosure with Metal Door ), 8 way, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of MCCB with Thermal - Magnetic Release of breaking capacity 36 kA at 415V AC, 50Hz of capacity 25-32A / 32-40A / 40-50A, 4 Pole complete with metal enclosure with spreader terminals including fixing, connection, testing and commissioning. ( Make - LK(L&T) /Siemens / ABB / Hager / Legrand / Schneider / C&S ) Above/
Supply of Sheet Moulded Compound ( SMC ) JB box, fire retardant of size 250 x 250 x 89 155 mm ( IP-55 ) / equivalent size heavy duty, outdoor type, UV ray protected, self fire- extinguishing, shock resistance IK08 or above and IP65 degree of protection grade transparent polycarbonate DB box including fitment with suitable size and shape Mild Steel ( MS ) bracket by replacing existing damage box and accessories with testing and commissioning. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of Dust and vermin proof metal Busbar Chamber made of 16 SWG ( 1.6mm ) 90 MS sheet duly powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 100 Amp, 4 way, suitable for 415V, 50Hz supply system including all accessories alongwith fixing, connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. ( Make - Havells / Standard / HPL / C&S / LK (L&T) / Indoasian ) Above/
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 25-63 ) Amp, 4 Pole - 1 no. b) MCB, 4 Pole, 32Amp, 415V, 91 50Hz, 10kA ( C-curve ) - 2 nos. c) MCB, 2 Pole, 10Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. d) Power Contactor, 3 Pole, 12A, 415V, 50Hz - 2 nos. e) Astronomical Timer Switch - 2 nos. f) Tinned Copper Busbar ( 4 Bar ) each of capacity 100 Amps., 415V, 50 Hz - 1 set g) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. h) CT of suitable ratio for MFM - 3 nos. i) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 6 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) Above/
Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Above/
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed )
D- Electrical (General) work in connection with "Construction of new LHS
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 94 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 95 grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 4 nos. single core HRFR / FRLS 96 grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for three phases and one neutral in GI conduit of 25mm dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Supply of Submersible Sewage Pump-Motor set of discharge capacity 92 Cubic metre per hour and discahrge head 9 Mtrs. (approx.) suitable for operation on 415V, 50 Hz, 3Ph / 240V, 50 97 Hz, 1 Ph supply system complete with one fully automatic starter control panel with all protection and float switch alongwith 10 Mtrs. long multicore copper flexible cable of suitable size for motor operation, 5 mtr. Lifting Iron Chain, GI clamps, steel wire rope with double pulley, PVC flexible pipe of suitable size and length including installation and commissioning. ( Make of pump-motor set - KSB / Texmo / CRI / Kirloskar / Crompton / Calama ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Trenching and laying of cable under ground by soil cutting with covering of cable by sand and bricks / through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN- 10 or higher) without bricks alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) Above/
Supply of GI ( minimum coating thickness 65 microns ) conical / octagonal ( minimum sheet thickness - 3mm ) Pole of overall length 5 M with single / double arm bracket, top cover, base plate including hinged door-inbuilt Junction box complete with copper bar, insulator, Hylam sheet for cable termination and fuse kit-kat / MCB ( Make - Utkarsh / B.P. Projects / Crompton / Bajaj / Surya ) Above/
RCC foundation, erection and commissioning of above GI pole with construction of cement concrete muffing ( Cement : Stone : Sand = 1 : 2 : 4 ) with foundation accessories including earthing of pole with 1 no. of 50 mm dia, 3 M long GI pipe ( Make - TATA / Jindal / Bansal ) with necessary earth connection from pipe to pole by GI Strip / GI wire Above/
Wiring of light point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 105 conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral through pole from inbuilt pole Junction Box's porcelain fuse kit-kat / MCB to light fitting along with 1 no. single core HRFR / FRLS grade, PVC insulated copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Dismantling / Cutting of existing pole and make good of surface including transportation from site to stores Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 107 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 108 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition Above/
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition Above/
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) Above/
Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall ( LED Street light fitting will be supplied by Railway ) Above/
Fixing, connection and commissioning of out door LED Flood light / Street Light fitting on High Mast Tower / Pole / Structure with suitable arrangement. ( LED outdoor light fitting will be supplied by Railway ) Above/
Installation, connection and commissioning of Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Wall Bracket Fan will be supplied by Railway ) Above/
Supply of SPN DB ( Metal Enclosure with Metal Door ), 8 way, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of MCCB with Thermal - Magnetic Release of breaking capacity 36 kA at 415V AC, 50Hz of capacity 25-32A / 32-40A / 40-50A, 4 Pole complete with metal enclosure with spreader terminals including fixing, connection, testing and commissioning. ( Make -LK(L&T)/Siemens / ABB / Hager / Legrand / Schneider / C&S ) Above/
Supply of Sheet Moulded Compound ( SMC ) JB box, fire retardant of size 250 x 250 x 120 155 mm ( IP-55 ) / equivalent size heavy duty, outdoor type, UV ray protected, self fire- extinguishing, shock resistance IK08 or above and IP65 degree of protection grade transparent polycarbonate DB box including fitment with suitable size and shape Mild Steel ( MS ) bracket by replacing existing damage box and accessories with testing and commissioning. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of Dust and vermin proof metal Busbar Chamber made of 16 SWG ( 1.6mm ) MS sheet duly powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 100 Amp, 4 way, suitable for 415V, 50Hz supply system including all accessories alongwith fixing, connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. ( Make - Havells / Standard / HPL / C&S / LK (L&T) / Indoasian ) Above/
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 25-63 ) Amp, 4 Pole - 1 no. b) MCB, 4 Pole, 32Amp, 415V, 122 50Hz, 10kA ( C-curve ) - 2 nos. c) MCB, 2 Pole, 10Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. d) Power Contactor, 3 Pole, 12A, 415V, 50Hz - 2 nos. e) Astronomical Timer Switch - 2 nos. f) Tinned Copper Busbar ( 4 Bar ) each of capacity 100 Amps., 415V, 50 Hz - 1 set g) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. h) CT of suitable ratio for MFM - 3 nos.i) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 6 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) Above/
Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Above/
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed )
E-Electrical (General) work in connection with "Construction of Limited
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 125 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for phase and neutral 126 in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 4 nos. single core HRFR / FRLS 127 grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for three phases and one neutral in GI conduit of suitable dia along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Supply of Submersible Sewage Pump-Motor set of discharge capacity 92 Cubic metre per hour and discahrge head 9 Mtrs. (approx.) suitable for operation on 415V, 50 Hz, 3Ph / 240V, 50 128 Hz, 1 Ph supply system complete with one fully automatic starter control panel with all protection and float switch alongwith 10 Mtrs. long multicore copper flexible cable of suitable size for motor operation, 5 mtr. Lifting Iron Chain, GI clamps, steel wire rope with double pulley, PVC flexible pipe of suitable size and length including installation and commissioning. ( Make of pump-motor set - KSB / Texmo / CRI / Kirloskar / Crompton / Calama ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Trenching and laying of cable under ground by soil cutting with covering of cable by sand and bricks / through suitable dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN- 10 or higher) without bricks alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway ) Above/
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway ) Above/
Trenching, laying under road / track through 50 mm dia GI pipe ( medium gauge ) including supply of GI pipe and commi- ssioning of cable including back filling of trench with excavated soil after laying of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway ) Above/
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway ) Above/
Supply of GI ( minimum coating thickness 65 microns ) conical / octagonal ( minimum sheet thickness - 3mm ) Pole of overall length 7 M with single / double arm bracket, top cover, base plate including hinged door-inbuilt Junction box complete with copper bar, insulator, Hylam sheet for cable termination and fuse kit-kat / MCB ( Make - Utkarsh / B.P. Projects / Crompton / Bajaj / Surya ) Above/
RCC foundation, erection and commissioning of above GI pole with construction of 135 cement concrete muffing ( Cement : Stone : Sand = 1 : 2 : 4 ) with foundation accessories including earthing of pole with 1 no. of 50 mm dia, 3 M long GI pipe ( Make - TATA / Jindal / Bansal ) with necessary earth connection from pipe to pole by GI Strip / GI wire Above/
Wiring of light point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 136 conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral through pole from inbuilt pole Junction Box's porcelain fuse kit-kat / MCB to light fitting along with 1 no. single core HRFR / FRLS grade, PVC insulated copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Dismantling / Cutting of existing pole and make good of surface including transportation from site to stores Above/
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS 138 grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 139 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab / V-MARC ) Above/
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition Above/
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition Above/
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) ) Above/
Designing of mounting layout, supply, installation, connection and commissioning of 20-22W LED batten (Type of LED - Surface Mounting Device ) tube with industrial grade constant current Driver ( Efficiency - Greater than 85% ) with short circuit protection, extruded aluminium housing and milky polycarbonate diffuser ( LED chip make - Nichia, Osram, Seoul, Philips, Lumileds, Everlight, Avago, Cree, Lednium, APT Electronics & BridgeLux ), LED luminaire system efficacy - Greater than 120 Lumens per Watt @ 350mA drive current, Colour Temperature - 6500K (Cool white), CRI>80, SDCM<5, Driver Operating Voltage - 140-270 Volt AC, Surge Protection minimum 4KV, THD<10%, Driver HV Cut off @ 325V/440V (P2P) protection for 8 hrs., Life span of LED chip Greater than 50000 burning hours, The Luminaire & Driver both should be of same make / brand and indivi- dually BIS approved with 60 months warranty including fixing with GI clamps made of GI flat of suitable size & GI nut-bolts. ( Make : Philips (Signify) / Havells / Bajaj / Panasonic / Crompton / Jaquar / Lighting Technologies / Halonix ) Above/
Designing of mounting layout, supply, installation, connection and commissioning of Street light 90 Watt LED (Type of LED - Surface Mounting Device ) luminaire, pressure die cast housing with Ingress Protection - IP66 or higher ( LED chip make - Nichia, Osram, Seoul, Philips, 145 Lumileds, Everlight, Avago, Cree, Lednium, APT Electronics & BridgeLux ), complete with all accessories, LED luminaire system Efficacy minimum - 130 Lumens per Watt @ 350mA drive current, Impact resistance IK-05 or higher, Colour Temperature - 5700K, Driver Surge Protection minimum 4KV, Life span of LED chip Greater than 50000 burning hours, The Luminaire & Driver both should be of same make / brand and individually BIS approved with 60 months warranty including fixing with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall. ( Make : Philips (Signify) / Havells / Bajaj / Panasonic / Crompton / Jaquar / Lighting Technologies / Halonix ) Above/
Designing of mounting layout, supply, installation, connection and commissioning of Street light 90 Watt LED (Type of LED - Surface Mounting Device ) luminaire, pressure die cast housing with Ingress Protection - IP66 or higher ( LED chip make - Nichia, Osram, Seoul, Philips, 146 Lumileds, Everlight, Avago, Cree, Lednium, APT Electronics & BridgeLux ), complete with all accessories, LED luminaire system Efficacy minimum - 130 Lumens per Watt @ 350mA drive current, Impact resistance IK-05 or higher, Colour Temperature - 5700K, Driver Surge Protection minimum 4KV, Life span of LED chip Greater than 50000 burning hours, The Luminaire & Driver both should be of same make / brand and individually BIS approved with 60 months warranty including fixing, connection and commissioning of outdoor Flood light / Street light fitting on High Mast Tower / Pole / Structure with suitable arrangement. ( Make : Philips (Signify) / Havells / Bajaj / Panasonic / Crompton / Jaquar / Lighting Technologies / Halonix ) Above/
Designing of mounting layout, supply, installation, connection and commissioning of Flood light 80 Watt LED (Type of LED - Surface Mounting Device ) luminaire, pressure die cast aluminium housing with Ingress Protection - IP66 or higher ( LED chip make - Nichia, Osram, Seoul, 147 Philips, Lumileds, Everlight, Avago, Cree, Lednium, APT Electronics & BridgeLux ), complete with all accessories, LED luminaire system Efficacy minimum - 100 Lumens per Watt @ 350mA drive current, Impact resistance IK-05 or higher, Colour Temperature - 5700K, Driver Surge Protection minimum 4KV, Life span of LED chip Greater than 50000 burning hours, The Luminaire & Driver both should be of same make / brand and individually BIS approved with 60 months warranty including fixing of outdoor LED Flood light / Street Light fitting on High Mast Tower/Pole/Structure with suitable arrangement. ( Make : Philips (Signify) / Havells / Bajaj / Panasonic / Crompton / Jaquar / Lighting Technologies / Halonix ) Above/
Supply of AC Wall Bracket Fan 400 mm sweep suitable for operation on 1Ph, 220- 240V, 50 Hz supply system including fixing, connection and commissioning with GI clamps made of GI flat of suitable size and GI Nut-Bolts on wall / structure. ( Make : Havells / Usha / Orient / Halonix / Atomberg / Crompton / Bajaj ) Above/
Supply of SPN DB ( Metal Enclosure with Metal Door ), 8 way, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of TPN MCB DB ( Metal Enclosure with Metal Door - IP 43 ), 3Ph, 4 way per phase, 415V, 50Hz, complete with 4 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz per phase as per requirement of load and 1 no. FP RCBO, of current rating 63A, 300mA, 10kA, 415V, 50Hz. ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) Above/
Fixing, connection and commissioning of above TPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement. Above/
Supply of MCCB with Thermal - Magnetic Release of breaking capacity 36 kA at 415V AC, 50Hz of capacity 25-32A / 32-40A / 40-50A, 4 Pole complete with metal enclosure with spreader terminals including fixing, connection, testing and commissioning. ( Make - LK(L&T) /Siemens / ABB / Hager / Legrand / Schneider / C&S ) Above/
Supply of Sheet Moulded Compound ( SMC ) JB box, fire retardant of size 250 x 250 x 154 155 mm ( IP-55 ) / equivalent size heavy duty, outdoor type, UV ray protected, self fire- extinguishing, shock resistance IK08 or above and IP65 degree of protection grade transparent polycarbonate DB box including fitment with suitable size and shape Mild Steel ( MS ) bracket by replacing existing damage box and accessories with testing and commissioning. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of Sheet Moulded Compound ( SMC ) JB box, fire retardant of size 700 x 480 x 155 210 mm ( IP-55 ) / equivalent size heavy duty, outdoor type, UV ray protected, self fire- extinguishing, shock resistance IK08 or above and IP65 degree of protection grade transparent polycarbonate DB box including fitment with suitable size and shape Mild Steel ( MS ) bracket by replacing existing damage box and accessories with testing and commissioning. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of Thermoplastic Polycarbonate Busbar Chamber of dimen- sion 450mm x 300mm x 210mm consisting with 4 nos. tinned copper busbar of each bar of capacity 100 Amp, 4 way, suitable for 415V, 50Hz supply system and 4 nos. Cable glands with Ingress protection : IP65 or 156 higher as per IEC-60529 ( weather proof), rust, dust, moisture and shock proof, anti corrosive, halogen free acid resistant, light weight, impact resistant IK 08/09 as per IEC- 60068-2-72, fire returdant, insulated, UV stabilised as per EN ISO 4892, should withstand glow wire test at 960 degree C as per IS 11000-2-1,IEC-60695-2-10 and fire rated UL94V-0 complete with hinged door with locking arrangement including fixing, connection and commissioning of above Junction Box on pole/structure with mounting clamp. ( Make : Hensel / Sintex / OBO Bettermann / RMC / Grasp / ABB / Legrand / Spelsberg / EPP Composites ) Above/
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) 157 Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 25-63 ) Amp, 4 Pole - 1 no. b) MCB, 4 Pole, 32Amp, 415V, 50Hz, 10kA ( C-curve ) - 2 nos. c) MCB, 2 Pole, 10Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. d) Power Contactor, 3 Pole, 12A, 415V, 50Hz - 2 nos. e) Astronomical Timer Switch - 2 nos. f) Tinned Copper Busbar ( 4 Bar ) each of capacity 100 Amps., 415V, 50 Hz - 1 set g) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. h) CT of suitable ratio for MFM - 3 nos. i) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 6 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S ) Above/
Fixing, connection, testing and commissioning of above panel including all incoming and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Above/
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed )
F-Schedule () G-GST as applicable ( At present @ 18% )( For Schedule A
Goods & Services Tax ( at present @ 18% )
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
3579Clause_2.pdf
ATTACHMENT
TenderBooklet.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
TenderFormandAnnexuresnew.pdf Tender form and annexure
ATTACHMENT
GCC_April-2022.pdf
ATTACHMENT
HTLTstandardspecification.pdf
ATTACHMENT
Advancecorrectionslipsupto11.pdf Advance Correction Slip
ATTACHMENT
TenderFormandAnnexuresnew.pdf
ATTACHMENT
Advancecorrectionslipsupto11.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].