| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for point wiring with single core FRLS-PVC insulated unsheathed 1100 volt grade cable with multi stranded copper conductor of size 1.5 sqmm (Nominal area) drawn through and including stove enamelled steel conduit medium grade ISI marked not less than 20 mm dia concealed in wall with cutting chasing and making good the disturbed surface of wall with all fittings including tee, junction boxes and continuous earth wire with and including FRLS PVC insulated unsheathed 1100 volts grade cable with multi stranded copper conductor of size 1.5 sqmm (Nominal area) connected to earth dolly complete for one light point control by one switch complete all as specified and as directed by Engr-in-Charge. | 10 | Per point | - | - |
| 2 | M&L for point wiring with single core FRLS-PVC insulated unsheathed 1100 volt grade cable with multi stranded copper conductor of size 2.5 sqmm (Nominal area) drawn through and including stove enamelled steel conduit medium grade ISI marked not less than 20 mm dia concealed in wall with cutting chasing and making good the disturbed surface of wall with all fittings including tee, junction boxes and continuous earth wire with and including FRLS PVC insulated unsheathed 1100 volts grade cable with multi stranded copper conductor of size 2.5 sqmm (Nominal area) connected to earth dolly complete for one light point control by one switch complete all as specified and as directed by Engr-in-Charge. | 5 | Per point | - | - |
| 3 | S&F in replacement Switch flame proof rotarytype with termination box inLM6, 16A, single pole 250V all as specified and directed by engr-in-charge. | 20 | Each | - | - |
| 4 | S&F in replacement Switch flame proof switch socket & plug combined in LM6 cable termination box in LM6 250 V , 16A,2P+earth all as specified and directed by engr-in-charge. | 10 | Each | - | - |
| 5 | Supply and fixing in replacement LED light fitting 2X16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver,holders, connector etc. Complete with all accessoriesprewired and including connecting up with threecore flexible copper conductor cable with suitable size all as specified and directed by engr-in-charge. | 10 | Each | - | - |
| 6 | Supply and fixing in replacement LED light fitting 1X16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass with LED tube light fixtures driver,holders, connector etc. Complete with all accessoriesprewired and including connecting up with threecore flexible copper conductor cable with suitable size all as specified and directed by engr-in-charge. | 10 | Each | - | - |
| 7 | Supply only PVC insulation tap in 25 mm width 25 Mtrs long suitable for upto 1.1 KV ISI marked complete | 30 | Roll | - | - |
| 8 | Supply and fixing in replacement LED Bulb 15 w including taking out to unsv old complete as directed. | 50 | Each | - | - |
| 9 | Supply and fixing Flame proof exhaust fan 305 MM sweep steel body heavy duty with louver mounting bracket ISI marked ,energy saving less noise capacitor type incl making hole in brick wall plastering colour coading and all site required work for disturbed surface matching with existing and making electric connection using three core copper cable drawn through in steel conduit pipe complete all as specified and directed. Note ; Old fan shall be deposited by contractor in MES Yard. | 5 | Each | - | - |
| 10 | Supply and fixing Flame proof wall mounting fan 24 inch sweep steel body heavy duty with energy saving less noise capacitor type incl making electric connection using three core copper cable drawn through in steel conduit pipe complete all as specified and directed.Note : Old fan shall be deposited by contractor in MES Yard. | 5 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.82 MB
BOQ_861505.xls
BOQ • 0.32 MB
TENDER30.pdf
Tender Documents • 1.24 MB
LISTOFMAKE30.pdf
Additional Documents • 0.67 MB
PS30.pdf
Additional Documents • 0.55 MB
Download all tender documents and submit your bid