Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.4 LAccepted-AOC | L1 | Accepted-AOC Being reasonable and Lowest L1 | |
| 2 | L2₹14.6 L+₹1.1 L (8.56%)Rejected-Finance GF AKRITI TOWER 19 B VIDHAN SABHA MARG LUCKNOW PIN 226001 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226001 | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹14.8 L+₹1.4 L (10.5%)Rejected-Finance | L3 | Rejected-Finance Being other than L1 | |
| 4 | L4₹14.9 L+₹1.5 L (11.3%)Rejected-Finance N A | L4 | Rejected-Finance Being other than L1 | |
| 5 | L5₹15.1 L+₹1.6 L (12.3%)Rejected-Finance R 233 6 SIR SYED ROAD 3 JOGABAI EXT OKHLA NEW DELHI DELHI 110025 | SOUTH EAST DELHI | DELHI | 110025 | L5 | Rejected-Finance Being other than L1 |
Tender Value
Refer Docs
EMD Value
₹44,000
Closing Date
26 Nov 2020, 6:00 pmClosed
Col SS Bose
HQ CWE (AF) Chakeri Kanpur 208008
PROVN OF FIRE DETECTION AND ALARM SYSTEM IN ICU SCU AND HDU AT 7 AFH KANPUR CANTT
2020_MES_373455_1
82134/E8
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
CHAKERI KANPUR
Class E cat c (vi)
8 documents required · 8 mandatory
₹500
GE (AF) B/R CHAKERI
₹44,000
28 Dec 2020
31 Aug 2020
3 Dec 2020
31 Aug 2020
26 Nov 2020
7 Oct 2020
Amount
Supply, installation, commissioning and testing of Single Loop Analogue Addressable Fire Alarm Control Panel, with a single loop driver card, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 240 addressable devices one each loop via fully digital communication protocol, equipped with a white backlit display (240x64 pixel resolution) graphical LCD Display with atleast 6 lines of information, 200 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software, dedicated USB and RS-232 serial port for direct or PC connection. 5500 events storage, loop current 500 mA, panel shall be equipped with in-built multi-meter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, can be networked to compatible addressable panels and repeater panels by adding a network card, features battery charger status and temperature, supports programmable cause / effect on outputs, panel housing meets IP30 ingress protection classification finished in RAL 7035, 1 Year Warranty, Independently certified as complying with requirements of BS EN 54 Part 2, 4, and 13. Approved by: British Standards Institute (BSI) and Vertrauen durch Sicherheit (VdS) complete all as specified and directed. Make- Ceasefire/LST/Advanced/Tyco/Bosch/UL series/Morley
Supply, installation, commissioning and testing of Intelligent Analogue Multi-Criteria (combination of smoke and heat) Detector including Isolator modules for short circuit isolation of signalling line cuircuit (SLC) with special algorithms to utilise information from both smoke and heat sensing elements to ensure high level of immunity to false alarms without compromising genuine alarm sensing performance, programmable multiple smoke senstivity level and 9 modes of operation, bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360 degree view of status, auto- addressable/ electronically addressed, utilises fully digital communication addressable protocol with high noise rejection. Approved by LPCB for EN 54-5, EN 54-7, & EN 54-17 standard complete all as specified and directed. Make:- Ceasefire/LST/Advanced/Tyco/Bosch/UL series/Morley
Supply, installation, commissioning and testing of Intelligent Analogue Manual Call Point with resettable operating element, with in-built bi-directional short circuit isolator. Bi-Colour LED for local indication of device status, single action operation, reset to normal condition using special reset key, clearly visible alarm flag in the activated state. Approved by LCPB for EN 54-11 standard complete all as specified and directed. Make:- Ceasefire/LST/Advanced/Tyco/Bosch/UL series/Morley
Supply, installation & commissioning of Standard Mounting Box for Modules all as per site requirement complete all as specified and directed. Make:- Ceasefire/LST/Advanced/Tyco/Bosch/UL series/Morley
Supply, installation & commissioning of Intelligent Sounder Interface Module allows to connect conventional Sounder or Sounder Beacon to addressable loop, with in-built short circuit isolator, allows for two stage alarm capability, addressed through auto and manual options. Approved by LPCB for EN 54-17 & EN 54-18 standard.complete all as specified and directed. Make:- Ceasefire/LST/Advanced/Tyco/Bosch/UL series/Morley
Supply, fixing & laying of 1.5 Sqmm x 2 core PVC insulated copper conductor armoured cable including jointing materials complete all as specified and directed. Make:- Polycab/Havells/Finolex/Pragon/KEI.
Supply & fixing and installation of response Indicator to provide the indication of alarm activated condition of detector installed in a concealed enclosure or not visible directly. complete all as specified and directed. Make:- Ceasefire/LST/Advanced/Tyco/Bosch/UL series/Morley
Prime Technology
M/s R.V. Constructions
SKYLIGHT INNOVATIONS
APEX INFRANET Pvt.Ltd.
shanti enterprises
SANJEEV ENTERPRISES
Continental Engineers and contractors
Ceasefire Industries Pvt. Ltd.
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .