Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 CrAdmitted-Finance | ₹2.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.1 Cr+₹10.3 L (5.05%)Admitted-Finance | ₹2.1 Cr+₹10.3 L (5.05%) | L2 | Admitted-Finance |
| 3 | L3₹2.2 Cr+₹20.9 L (10.3%)Admitted-Finance | ₹2.2 Cr+₹20.9 L (10.3%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | CIVICTRA ENGINEERING AND CONSTRUCTIONS L2 | M AND COMPANY ENGINEERS AND CONTRACTORS PRIVATE LIMITED L3 | Marib Constructions L1 |
|---|---|---|---|---|---|---|
| 1.00 | 3 Pole, SF6 gas filled, Outdoor Circuit Breaker, including all accessories, auxiliaries and Marshalling Boxes/Kiosks, (145KV, 1250 Amps of 3 phase, 50 c/s and 31.5KA for 1 second). | 2 | No. | 9,22,000 ₹18,44,000 | 11,13,750 ₹22,27,500 | 8,18,515 ₹16,37,030 Lowest |
| 2.00 | 145kV, 50c/s, 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades | 4 | Set | 3,25,000 ₹13,00,000 | 3,46,005 ₹13,84,020 | 3,15,515 ₹12,62,060 Lowest |
| 3.00 | 145kV, 50c/s, 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with One Earthing Blades | 2 | Set | 3,43,000 ₹6,86,000 | 3,95,010 ₹7,90,020 | 3,25,515 ₹6,51,030 Lowest |
| 4.00 | 145kV, 50c/s, 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing Blades | 2 | Set | 3,72,000 ₹7,44,000 | 4,44,015 ₹8,88,030 | 3,30,515 ₹6,61,030 Lowest |
| 5.00 | Single phase, 50 c/s 145KV Current Transformers (1200-600-300/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA | 6 | No. | 2,87,000 ₹17,22,000 | 2,15,325 ₹12,91,950 Lowest | 2,15,515 ₹12,93,090 |
| 6.00 | Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries. | 6 | No. | 43,000 ₹2,58,000 Lowest | 61,182 ₹3,67,092 | 65,515 ₹3,93,090 |
| 7.00 | Loading unloading and tranasportation of 132KV Control and Relay Panel(Douplex Type} for Line/Feeder completely wired including Substation automation supporting IEDS/numerical relays inlcuding Distance Recorder from TLMD-IV Pampore to Grid station Budgam.Including its testing and commissioning. | 2 | set | 9,58,000 ₹19,16,000 | 54,000 ₹1,08,000 | 45,515 ₹91,030 Lowest |
| 8.00 | Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/V3) KV/ (110/V3)V, One min power freq withstand 275KVrms | 6 | No. | 2,87,000 ₹17,22,000 Lowest | 3,23,730 ₹19,42,380 | 2,91,515 ₹17,49,090 |
| 9.00 | 132KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP) | 12 | No. | 11,000 ₹1,32,000 Lowest | 24,057 ₹2,88,684 | 12,515 ₹1,50,180 |
| 10.00 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns. | 4 | No. | 1,23,000 ₹4,92,000 | 81,000 ₹3,24,000 | 80,515 ₹3,22,060 Lowest |
Tender Value
₹1.9 Cr
EMD Value
₹3.9 L
Closing Date
22 Dec 2022, 4:00 pmClosed
Executive ENGINEER TLMD 7
TLMD-7,JKPTCL,BEMINA,SRINAGAR
SITC of Electrical Equipment and Related Accessories including Supply and Erection of Columns and Supporting Structures for 2 Number 132kV Line Bays for 132 33kV Grid Sub Station Nowbug, Chadura at GS BUDGAM
2022_PDD_197099_1
TLMD-7/TS/ 09 of 2022 DATED 22-11-2022
Open Tender
Electrical Works
Lump-sum
92 days
kashmir
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,000
CD A/C No. 0367010200000182
₹3.9 L
Yes
office of SE,O AND M CIRCLE 2ND , jkptcl, kmr
9 Jan 2023
23 Nov 2022
23 Dec 2022
23 Nov 2022
22 Dec 2022
23 Nov 2022
23 Nov 2022 - 15 Dec 2022
12 Dec 2022
Amount
3 Pole, SF6 gas filled, Outdoor Circuit Breaker, including all accessories, auxiliaries and Marshalling Boxes/Kiosks, (145KV, 1250 Amps of 3 phase, 50 c/s and 31.5KA for 1 second).
145kV, 50c/s, 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades
145kV, 50c/s, 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3pole Isolators with One Earthing Blades
145kV, 50c/s, 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Two Earthing Blades
Single phase, 50 c/s 145KV Current Transformers (1200-600-300/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA
Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries.
Loading unloading and tranasportation of 132KV Control and Relay Panel(Douplex Type} for Line/Feeder completely wired including Substation automation supporting IEDS/numerical relays inlcuding Distance Recorder from TLMD-IV Pampore to Grid station Budgam.Including its testing and commissioning.
Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/V3) KV/ (110/V3)V, One min power freq withstand 275KVrms
132KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP)
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
POWER AND CONTROL CABLES
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
7 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
14 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
27 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
4 Core, 16 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete
CONDUCTOR AND HARDWARE FITTINGS
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter -31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Double Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping 5 strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
T Clamps Twin 500mm2/ Twin 500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
PI Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
PG Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Earth Wire 7/3.15mm
Earthwire Tension Clamps comprise of compression type tension clamp with two 'D' shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
CABLE TRAYS/CABLE RACKS/ACCESSORIES
Cable Trays of size 400mm x 3000mm made of M.S angles 40x40x6mm,40x6 Flat.
Cable Trays of size 300mm x 2500mm made of M.S angles 40x40x6mm,40x6 Flat.
Lugs, Ferrules, Welding Material, Cotton Waste etc
HDPE pipes for cables
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area
GALVANISED STRUCTURES, INCLUDING GALVANISED NTUTS, BOLTS(lattice Type)As per Design Drawings
GALVANISED STRUCTURES, INCLUDING GALVANISED NTUTS, BOLTS( Pipe Type)As per Design Drawings
CIVICTRA ENGINEERING AND CONSTRUCTIONS
M AND COMPANY ENGINEERS AND CONTRACTORS PRIVATE LIMITED
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.23 MB
sbd.pdf
Tender Documents • 3.88 MB
BOQ_523798.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .