Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.4 LAccepted-AOC 13 29 304 IIIRD FLOOR EAST PATEL NAGAR OPP HOTEL SIDDARATHA NEW DELHI 110008 | WEST | DELHI | 110008 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹13.7 L+₹31,778 (2.37%)Rejected-Finance NOT FOUND | L2 | Rejected-Finance Being not lowest | |
| 3 | L3₹14.4 L+₹1.0 L (7.82%)Rejected-Finance | L3 | Rejected-Finance Being not lowest | |
| 4 | L4₹14.6 L+₹1.2 L (8.79%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | L4 | Rejected-Finance Being not lowest | |
| 5 | L5₹14.7 L+₹1.3 L (9.76%)Rejected-Finance | L5 | Rejected-Finance Being not lowest |
Tender Value
₹17.3 L
EMD Value
₹34,500
Closing Date
5 Apr 2021, 6:00 pmClosed
CWE (AF) Gurgaon
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-110010
PROVN OF 100 KVA DG SET AND OTHER ALLIED WORKS SERVICES FOR SMC AT VSV GURUGRAM UNDER GE (AF) GURGAON
2021_MES_430638_1
CA NO CWE/GGN/G-58/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Gurgaon
As per NIT
9 documents required · 9 mandatory
₹500
GE (AF) Gurgaon
₹34,500
Yes
22 Jul 2021
15 Mar 2021
7 Apr 2021
15 Mar 2021
5 Apr 2021
29 Mar 2021
Amount
Supply, Installation, Testing and commissioning of silent DG set 100 KVA/80 KW 415 Volts, 3 phase, 4 wire, engine and alternator compete with AMF panel having meters and sound proof canopy founadtion including anti vibration Pads etc of capacity 100 KVA. Specifications are as below: -
Engine: Greaves Power Direct injection, water cooled, four cyllinder, 4 stroke rated at 1500 RPM, confirming to ISO:3046/BS 5514 with the following: (i) Radiator cooling (ii) Mechanical Governer (iii) Exhaust manifold with SS exhaust flexible bellow (iv) Fly wheel and fly wheel housing (v) Dry type air cleaner (vi) Starter motor, Battery Charger
Alternator: Meccalte/ Crompton Greaves/ Stamford Voltage (3P) , Frquency 50HZ, current-139.12Amps, type 4P, rotatin field, volatge regulator solid state, volt regulation (1/1)- ± 1%, insulation class-H, tamp rise 125º C, Bearing (qty/type)-1/sealed, coupling flex dise, one step load acceptance 100% of rating, unbalnced load capability 25% of rated amps
Accousting Enclosure: Powder coated wheather proof canopy, Engine and alternator mounted on AV mounts with silencer and SS exhaust bellow optimised to meet stringent MDEF/CPCB norms for sound and emmission Baserail with drawout type fuel tank, drain Plug, Inlet and Outlet connections, airvent, level gauge
Control Panel: Fabricated with CRCA sheet and powder coated with RAL 9003 with the following: (i)Suitable circuit breaker (ii)Controller with multi teature display (iii) Load on and Set running indication lamps (iv) Copper conductor cables between alternator and control panel
Literature: (i) Operation and spare parts manual in CD format (ii) Installation and general maintenance guidelines (iii) Foundation drawing (iv) Alternator and control panel wiring drawings (v) Test certificate Note: Specific fuel consumption is based on HSD complying to IS:460 and tolerances with respect to ISO 3046
Genset Specification: Greaves Cotton Genset rating prime, output(KVA/KWE) 100/80, gross engine power 93, Aspiration/cooling TCAC, 4 cyllinders Inline, displacement 4.87, Bore X stroke (mm) - 108X133. cpmression ratio 17.2, Rated RPM 1500, overspeed trip (RPM) 1650, Governer type Mech class G2, Frequency ratio Isochronous, air cleaner (type/qty) dry/01, Genset model GPWII-PII-100E, Engine Model 4G11TAG25
Exhaust Sytem: Max allowable backpressure (kPa) 4.5, Exhaust temperature (deg C) 500, silencer type residential
Engine Electrical System: Charging alternator (VDC/Amps) 12V/35A, starter motor rated volatge 12 DC, battery volatge (DC)/ Capacity (AH) 12V/88AH
Fuel System: Recommended fuel IS:1460, HSD, fuel tank capacity 350 litres
Fuel consumption @ % load (LPH): (i) 100%- 23.6 (ii) 75% - 17.4
Lubricating Oil system: Lube oil sump capacity 10litres,lube oil changed period 500 HRS, lube oil consumption < 0.2 % of SFC, lube oil filter (type/qty) Spin on/1, recommended lube oil grade 15W40, API CI4, recommended lube oil Greaves Maxtherm
Cooling System: Max ambient capacity 50°C, Coolant capacity (Eng+Rad) - 25 litres
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 120 Sqmm. complete all as directed. Note : Provision of suitable double crimpped lugs and glands shall deemed to be included in quoted rates.
Complete all as per Srl item No. 2.00 here-in-before but 3.5 coreX50 Sqmm
Complete all as per Srl item No. 2.00 here-in-before but 4 core 35 Sqmm
Complete all as per Srl item No. 2.00 here-in-before but 4 core 25 Sqmm
M & L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using galvanised iron strip 32×6mm as earthing strip by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI light grade with funnel, wire mesh and 40 mm dia GI protection pipe medium grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified.
Supply, installing, testing and commissioning factory made and tested LT Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 300 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and made out of 3.15 mm thick CRCA mild steel sheet and mild steel & Angle iron frame work made out of 50 mm x 50 mm X 6 mm ), front opening type with aprons for cable entry, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey RAL- 7035 shade. The scope of work also comprising of the following:- ( LOCATION :- ) Make of Panel: Adlec/ Schneider / Universal Switch Gear Control/ Tricolite.
The panel manufacturer should have following Govt. Approved Certificates: 1. CPRI Certification Degree of Protection IP-54 (should have IEC:60439-1 test) 2. CPRI Short Circuit withstand strenght should be 50kArms for 1.0 Sec with intial peak of 105kA 3. CPRI Certification Rated current for short circuit not less than 4000 A with rated insulation voltage 660V 4. ISO 9001 CERTIFIED
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 80mm bore for protection of UG cables complete all as specified and as directed.
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and filling river sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted. Note : Punned down thickness shall be measured and paid .
M&L for sub class ‘B’ bricks old size laid flat dry in trenches over cable, across the direction of cable complete all as specified & directed .
M&L for Boring of holes under road, pavement,hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 70 to 150 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 25 to 50 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
shiv shanker enterprises
Garg Engineers
Commercial Traders
PARKASH ENTERPRISES
national engineering
Ridhi engineers and builders
MONA GENERATOR SEVICES PVT. LTD.
D P ENTERPRISES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .