Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.4 LAccepted-AOC | L1 | Accepted-AOC Lower amount quoted | |
| 2 | L2₹20.1 L+₹56,531.32 (2.89%)Rejected-Finance DHALIWAL | TARN TARAN | PUNJAB | 143107 | L2 | Rejected-Finance Higher amount quoted | |
| 3 | L3₹21.6 L+₹2.0 L (10.2%)Rejected-Finance HAMIRPUR ROAD NEAR BUS STAND UNA DISTT UNA HP | UNA | HIMACHAL PRADESH | 174301 | L3 | Rejected-Finance Higher amount quoted | |
| 4 | L4₹22.7 L+₹3.1 L (15.7%)Rejected-Finance | L4 | Rejected-Finance Higher amount quoted |
Tender Value
₹21.9 L
EMD Value
₹40,390
Closing Date
6 Apr 2022, 11:00 amClosed
Executive Engineer JSV Flood Prot. Division Gagret
Executive Engineer JSV Flood Prot. Division Gagret
Laying, Jointing and testing of GMS pipe in Rising Main, Supply and Errection of Pumping machinery including allied accessories
2022_HPIPH_58374_1
GGT-UNA01-752 No 11260-99 dt 21.03.2022
Open Tender
Civil Works
Item Rate
180 days
Gagret
As per NIT
6 documents required · 6 mandatory
₹400
Executive Engineer JSV Flood Prot. Division Gagret
₹40,390
Yes
3 Aug 2022
22 Mar 2022
6 Apr 2022
22 Mar 2022
6 Apr 2022
22 Mar 2022
22 Mar 2022 - 6 Apr 2022
Amount
Excavation in foundation trenches ( for pipes and pits ) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft / hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts including trimming and dressing of sides, levelling of beds to correct grade including, shoring, strutting, planking, timbering and dewatering, wherever required, stacking the useable and unuseable material/ soil separately and after laying, jointing and testing of pipes returing the useable soil in trenches in 15 cm ( Fifteen centimeter ) layers including consolidating of such deposited layer by ramming and watering and then disposing of all surplus excavated soil /un-useable materials as directed within all leads and lifts including restoration of un-metalled surface to its original condition and including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts complete in all respect to the entire satisfaction as per the directions of Engineer-in-Charge.
Laying, jointing and testing in trenches flanged GMS pipes (Medium grade/Heavy grade) confirming to ISI (1239-2004) specification including commissioning and cost of all fittings in respect of following diameters in Rising Main ( The earth work in trenches shall be measured and paid for separately ) including entire carriage of material in all leads and lifts as per the direction of the Engineer-in-Charge.
80 mm dia. (Medium grade) For Village Baneh di Hatti
100 mm dia. (Medium grade) for Village Shivpur
Providing, welding and fixing of MS flanges conforming to table as specified below of BIS code 6392-1971( Latest with upto date ammendments) welding of M.S. flanges on ( Two layers on inner face and one layer on outer face of each flange) with GMS pipes and bends on both ends. ( The GMS pipe to be measured and paid for separately. ) The welding of flanges should conforming to IS 816-1998 with electrodes as per IS 814-1997, Prov.& fixed with nuts, bolts of required size conforming to IS 1364, including providing & fixing 3 mm (Minimum) thick compressed asbestos fibre / synthetic rubber gasket conforming relevant BIS Code IS 2712-1965 in trenches complete in all respect and including entire carriage of materials in all leads and lifts as per the direct1on of the Engineer-in-Charge
80 mm dia Table-17 (RD 0 to RD 900)
80 mm dia Table-5 (RD 900 to 1860)
100 mm dia Table-17 (RD 0 to RD 1500)
100 mm dia Table-5 (RD 1500 to RD 2650)
Providing circumferential butt welded joints to GMS pipe of following dia with three layers on each end of welding using 3 mm and 4 mm dia electrodes after levelling the pipe ends according to relevent ISI specification within all leads and lifts and to entire satisfaction of the Engineer-in-Charge complete in all respect Butt welding joints
80 mm dia
100 mm dia
Supply of submersible pumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Groundfos/ LUBI /Hindustan/ Sabar/Seerex/Johnston / Amrut, confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ; 9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear. It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable, errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below.
Discharge = (Q) 9.72 LPS
Total Head = ( H) 82.07 Mts.
a) SWL in Tubewell = 0.00 Mtr. bgl.
c) R.L. point of discharge =102.50 Mtr.
d) Seasonal fluctuation + draught condition + bowl assembly. = 9.00 Mtrs.
e) Drawdown in Tubewell =67.10 Mtrs.
f) R.L of lowest point of pumpset installation = 26.90 Mtrs.
g) Static column lift = 75.60 Mtrs.
Rising main.
Length 10 Mtrs.
Dia meter. 100 mm
Class GMS Pipe (MG)
Column Pipe.
Length 83.10 Mtr.
Dia 100 mm
Class GMS. (M)
Pumping hours = 8.00 Hours
Altitude of installations above M.S.L. 350 Mtr.
Characteristic of water.
a) Temperature 20 Deg Cel.
b) Turbidity ________JTU.
c) Allkanity. ___________mg/ l Ca Co3
d) Size of solids ____________mm
e) others
Depth of T/well = 124.00Mtr.
Dia of T/ well assembly 300mm & 200 mm
Length of assembly pipe. 124.00 meter .
Dia of housing pipe 300 mm
Length of housing pipe. 76.00 meter
OPERATING CONDITIONS.
Type of Current :- A.C.Three Phase.
Frequency:- 50 Cycles /Sec.
Rated Voltage 415 +/- 15 % Volts.
System of earthing:- Double Loop earthing as per BIS 3843-1987 Latest.
Speed of Revolution ____________ RPM 2900
MOTOR.
Ref. to BIS code BIS 9283-1979 with upto date amendments.
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
Mechanical out put in H.P.
Class of insulation : Class B
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
Driver Type: Electric driven.
Operating Range: -15 % to+10 % of Total head at duty point.
Delivery size of Pump : ________( To be quoted by tenderer.)
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments. i) Make : ii) Type : iii) Capacity : 63 amp.
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. Panel/ Switch Board i) Drawing. ii) Layout Plan
MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. i) Make : ii) Type : iii) Range 63 amp. iv) Capacity
ELCB of recommended make L&T /Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63 Amp. iv) Capacity
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500.
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. 3 phase indicators i) Make : ii) Type : iii) Rating
Providing Hour run meter of recommended make of suitable capacity as per IS :722 (Latest edition) i) Type ii) Make iii) Range
Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452 (P- I&II ) with upto date amendments. 3 Phase indicators
Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range. 5 KVAR
Providing suitable starter of L&T/ Havell's /BHEL make as per IS :13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release, with or without 'initial oil filling as the case may be with Air Break. Type Star Delta with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : iii) Range.
Providing and fixing double flanged Cast iron Sluice valve of Leader / Kirloskar /LP/RG Brand make for the delivery line of pump and capable of withstanding the normal seat pressure and as per IS :- 780-1992 with latest ammendments i) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 100 mm dia
Providing and fixing double flanged swing type cast Iron Reflux valve of Leader/ Kirloskar/Kartar / LP/RG Brand make having Bye pass arrangement on the delivery line of the Pump and capable of 'withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendments i) Make : ii) Material : Cast Iron iii) Class PN-1.0 For for R/main 100 mm dia.
Providing and fixing pressure gauge of Prega / Precision make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements. i) Make :
Supply of PVC jointless, flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havells/ Finolex make suitable for the pumpsets offered from MCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe, solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor. The type, size and make shall be subject to approval of HPSEB authorities. i) Make : Finolex/ Havells ii) Size 3x 2.50 mm2 iii). type- IV capacity V Core-3
Lowering of GMS Column pipefor assembly 100 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No. 5.03 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 100 mm dia GMS pipe
Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 (P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply Side From meter of HPSEB to Bus Bar and Switch) i) Size 4.00 mm2 ii) Make Finolex/Havells. iii) Type iv) Capacity v) Core 3.
Providing and fixing double loop earthing with G.I. plate 600 mmx600mmx6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) G.I. wire 8 SWG upto 15 HP
Centrifugal Pumping Machinery alongwith allied accessories for village Baneh-di Hatti
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrangement ) Single /double /multi stage of Kirloskar / KSB/ Hindustan/ lubbi/ Groundfos Crupton KSB/Calama/BS/ make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.
Discharge (Q) = 3.45 LPS.
Total Head (H) = 103.83 Mtrs.
a)LWL In Sump well = 100.00 mtr
b)R.L. of shaft = 100.00 Mtrs.
c)R.L. of discharge Pt. = 175.50 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 0.00 Mtrs.
f) Static Head = 75.50 Mtrs.
Rising main.
Length = 1860 Mtrs.
Diameter = 80 mm. dia
Class GMS Tube(M)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =450 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 32 amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 32 Amp.
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 32 Amp
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 32 Amp.
Providing ICTP Switches with HRC fuses of L&T/ Havells make as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 32 amp.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 3 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing Hour run meter of recommended make of suitable capacity as per IS :722 (Latest edition) i) Type ii) Make iii) Range
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 80 mm dia suction pipe of the 65 mm dia for the suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.60
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make conforming IS 780-1992 with up to date ammendments of 80 mm dia for the delivery line of pump and capable with standing normal seat pressure as per BIS with upto date ammendments.For delivery pipe of pump i)Make Cast iron ii)Class PN1.00 iii). seat pressure (MPa).
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 80 mm dia for the delivery pipe of pump and capable with standing the normal Seat Pressure as per IS 5312-1984 part-1 class PN 1.60 upto date ammendments i)Make ii)Class PN 1.60 iii)Seat pressure(MPa) iv)Material Cast iron
Providing and fixing of Cast iron double flanged Swing type reflux valve of kirloskar/Leader / Kartar/Kilburn /BHEL /LP/RG Brand make IS 5312 Part 1 of 65 mm dia having by pass arrangement for the rising main of pump and capable of with standing the normal seat pressure as per BIS i)Make ii)Class PN 1.60 iii)Seat pressure(MPa) iv)Material Cast iron
Providing 80 mm dia circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.5.( GMS PIpe shall be issued by the department free of cost from Divisional store Badoh (Gagret) Una. The size of various components to be as under:-
i) Suction Pipe GMS Pipe 100 mm dia. (M)
ii) Delivery Pipe GMS 80 mm dia. (M)
iii) Common Header GMS 80 mm dia. (M)
and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 4.00 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 4.00 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with GI flat of suitable thickness electrode complete with material such as thimble, Nuts & Bolts, charcoal and common salt as per IS 3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the direction of the Engineer-in-Charge..i) GI Flat 25x3 mm
Centrifugal Pumping Machinery alongwith allied accessories for village Shivpur
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrangement ) Single /double /multi stage of Kirloskar / KSB/ Hindustan/ lubbi/ Groundfos Crupton KSB/Calama/BS/ make as per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.
Discharge (Q) = 6.27 LPS.
Total Head (H) = 109.51 Mtrs.
a)LWL In Sump well = 100.00 mtr
b)R.L. of shaft = 100.00 Mtrs.
c)R.L. of discharge Pt. = 169.85 Mtrs.
d)Suction lift. +ve mtrs.
e)Discharge Head = 0.00 Mtrs.
f) Static Head = 69.85 Mtrs.
Rising main.
Length = 2650 Mtrs.
Diameter = 100 mm. dia
Class GMS Tube(M)
Pumping hours. = 8 Hours.
Altitude of installations above M.S.L =450 mtrs.
Characteristic of Water
a)Temperature 20 Deg.Col.
b)Turbidity ________ JTU
c)Alloanity _________ mg/1 ca Co3
d)Size of solids __________ mm
e) Others.
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 63 amp.
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 63 Amp.
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 63 Amp
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 63 Amp.
Providing ICTP Switches with HRC fuses of L&T/ Havells make as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 63 amp.
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 5 KVR
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
Providing Hour run meter of recommended make of suitable capacity as per IS :722 (Latest edition) i) Type ii) Make iii) Range
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make as per IS 780-1992 with update ammendment for 125 mm dia suction pipe of the 125 mm dia for the suction line of pump and capable of with standing the normal seat pressure as per BIS with upto date ammendments i) Material Cast Iron ii).class PN1.60
Providing and fixing of double flanged Cast iron Sluice valve of kirloskar/Leader / Kartar/LP/RG Brand make conforming IS 780-1992 with up to date ammendments of 100 mm dia for the delivery line of pump and capable with standing normal seat pressure as per BIS with upto date ammendments.For delivery pipe of pump i)Make Cast iron ii)Class PN1.60 iii). seat pressure (MPa).
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 80 mm dia for the delivery pipe of pump and capable with standing the normal Seat Pressure as per IS 5312-1984 part-1 class PN 1.60 upto date ammendments i)Make ii)Class PN 1.60 iii)Seat pressure(MPa) iv)Material Cast iron
Providing and fixing of Cast iron double flanged Swing type reflux valve of kirloskar/Leader / Kartar/Kilburn /BHEL /LP/RG Brand make IS 5312 Part 1 of 100 mm dia having by pass arrangement for the rising main of pump and capable of with standing the normal seat pressure as per BIS i)Make ii)Class PN 1.60 iii)Seat pressure(MPa) iv)Material Cast iron
Providing 100 mm dia circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offered and common header as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.52.02.( GMS PIpe shall be issued by the department free of cost from Divisional store Badoh (Gagret) Una . The size of various components to be as under:-
i) Suction Pipe GMS Pipe 125 mm dia. (M)
ii) Delivery Pipe GMS 100 mm dia. (M)
iii) Common Header GMS 100 mm dia. (M)
and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 4.00 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 10.00 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
Providing and fixing double loop earthing with GI plate 600 mmx 600 mm x 6.30 mm thick electrode complete with material such as thimble, Nuts & Bolts, charcoal and common salt as per IS 3043-1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the direction of the Engineer-in-Charge..i) GI wire 4 SWG upto 30 HP.
SG Engineers and Consultants
SS ENGINEERING WORKS
Nirbhay Singh Jaswal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .