Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.1 LAccepted-AOC KALIKAPUR MATHPARA BOLPUR BIRBHUM | BOLPUR | BIRBHUM | WEST BENGAL | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹23.4 L+₹1.4 L (6.15%)Rejected-AOC | L2 | Rejected-AOC Being L2 Bidder | |
| 3 | L3₹24.5 L+₹2.4 L (10.8%)Rejected-Finance | L3 | Rejected-Finance Being L3 Bidder |
Tender Value
Refer Docs
EMD Value
₹49,436
Closing Date
3 Mar 2025, 1:00 pmClosed
Executive Engineer, Birbhum Electrical DivisionPWD
Office of The EXECUTIVE ENGINEER P.W.DTE. Birbhum Electrical Division P.O. Suri,Dist Birbhum, Pin 731101
Thorough Repair and Renovation work of the electrical wiring at Aministrative building at Labpur R.H ,Birbhum.
2025_WBPWD_812890_1
BIRED/149/e-NIQ(1st call) of 2024-2025
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Bolpur
Please refer Tender documents.
4 documents required · 4 mandatory
₹49,436
Executive Engineer, Birbhum Electrical DivisionPWD
2 Apr 2025
7 Feb 2025
5 Mar 2025
7 Feb 2025
3 Mar 2025
10 Feb 2025
10 Feb 2025
Amount
Dismantling the existing Electrical Installation(OLD LT panel& other fittings &fixtures) ,withdrawing old batten wiring etc by own tools & tackles and mending good the damages, as directed by EIC.
Supplying and fixing 415V, 125A TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating(L&T)
Supplying & fixing double door Vertical TPN MCB Distribution board [Enclosure (607914)] for MCCB incomer with IP-42/43 protection, on angle iron frame embedded in wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.(8-Way) INCOMING-160 A FP MCCB -1 No.OUTGOING-6-32A SPMCB-15 Nos.,63A TPMCB-2Nos,32A TPMCB-1 NO. [Make - Legrand]
S&F 415 V, Horizontal type, TPN MCB DB (6-way) with SS enclosure double-door[Enclosure (607716)] with IP-42/43 protection, with Four Pole Isolators as incomer and SPMCBs ('C' Curve, 10 KA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS.INCOMING-63 A FP Isolator -1 No.OUTGOING-6-32A SPMCB-18 Nos. [Make - Legrand]
Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc HPL make 63A
S&F 250V, SPN MCBDB (2+12) way with SS enclosure double-door (Ivory White with IP-42/43 protection with DP Isolators as incomer and SPMCBs ('C' Curve, 10kA) as outgoing, flushed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS. INCOMING-40 A DP Isolator OUTGOING-12 Nos. 6-10A SPMCB [Make - Legrand]
S&F 250V, SPN MCBDB (2+6) way with SS enclosure[ Enclosure (8GB32102RC08)] double-door (Ivory White with IP-42/43 protection with DP Isolators as incomer & SPMCBs ('C' Curve, 10 kA) as utgoing, flushed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment as per GS.Incoming-32A DP IsolatorOUTGOING-6Nos. 6-10A SPMCB [Make-Legrand]
Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm dia, 3 mm thick Polythene pipe, without earth continuity wire, by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles, as per GS.
S&F sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works, incl. S&F bakelite / perspex top cover by Brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required, as per GS. i) 100 mm x 100 mm x 65 mm
ii) 150 mm x 100 mm x 65 mm
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required as per GS. [Make-Havells/Polycab/ RR KABEL ] i) 4x16sqmm + 2x10sqmm [From meter loop to VTPNDB via Main Switch]
ii) 4x10sqmm + 2x6sqmm [VTPNDB to HTPNDB]
iii) 2x6sqmm + 1x4sqmm [HTPNDB to SPNDB]
iv) 2x4sqmm + 1x2.5sqmm
v) 2x2.5sqmm + 1x1.5sqmm [for Power plug, Comp. board]
vi) 3x1.5sqmm
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board/PVC board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed], as per GS.[Average run 8 mtr]
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC. i) On Board
ii) Average run 6 mtr
Supplying & Fixing GI Modular /PVC Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works i) 2 Row 18 Module
ii) 2 Row 12 Module
iii) 1 Row 8 Module
iv) 1Row 6 Module
Supplying & Fixing 6A modular type switch(Brand approved by EIC) on existing modular swich board with necy.interconnection by 1.5 sq.mm copper wire
Supplying & Fixing 6A modular type 5 pin socket(Brand approved by EIC) on existing modular swich board with necy.interconnection by 1.5 sq.mm copper wire
S&F 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approved by EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI /PVC(As per choice of EIC)Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc., as per GS.
Supply and fixing of Single Phase 250V Timer DB (equivalent to 10 way SPNDB in size) with double acrylic door sheet steel enclosure, neutral bar, din rail for controlling AC machines made following accessories with IP-43 protection with front door locking arrangement as per instruction of EIC. (Make Legrand ). S&F following electrical accessories & front door locking arrangement with all interconnections by 2x4 & 1X2.5 sq.mm copper wire (FRLSH) & all control circuit wiring would be made by 1.5 sqmm stranded cu wire (FRLSH) suitable length maintaining colour code with proper socketing by crimping method, taping, ferrule marking to complete the job as per direction of EIC & earthing attachment.The box should be painted by powder coated paint. incl connections maintaining recommended clearance as per IS.The box should be fixed on wall with suitable size of flush nut and necy. connection. i) 32 A DPMCB (C-curve 10ka) ( Make :Legrand)- 1 No. ii) 6A SP MCB--- 1no. iii) 24Hr x 7days programmable Digital timer (L&T make Cat no 67DDT0) -- 1no- 1 No. iv) 3-pole power contactor (ABB makeAX 09) with 240V operating coil -- 1 no. v) 32A Auto- 0ff- Bipass SPDT toggle switch (Approved/ reputed make or approved by EIC ) --- 1 No. vi) 2-Modular AC motor starter (Legrand/Myrius Cat no 673031) -- 1 no vii)2-module plate with cover (Make Legrand /Myrius) -- 1no viii) LED indication lamp (approved reputed make) -- 1 No. ix) Outgoing bakelite connector 32A (Reputed make as approved by EIC) - 4 nos.
Supplying & Fixing of PVC water proof type Loop box (Make-Sintex GSJB2520 /Hensel) of size [250X200X100]mm having hinged PVC top cover & 4 mm thick with rubber gasket lining,railway type mechanical locking arrangement, DIN rail & 4pole terminal stud on MS structure as per direction of EIC.Suitable for interconnection by 6 sq.mm copper wire among 240V, 15A TP MCB (L&T) -1NO, 6A SP MCB -1no 22A TP Power Contactor with 220V coil voltage, -NO,(L&T, Cat No. MNX22-2P, CS90Astronomical time switch (GIC Model: T2DDT7) incl.S&F the individual items. (For roof top LED light control & 3phase AC)
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.
S&F 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board, as per GS.
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl.S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 2 nos. 6 A, 5 pin Modular type plug socket with 2 nos. 6A Modular type switch (Brand approved by EIC), and on 6 Module GI Modular type switch board with one modulat indicator and a blanking plate 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply and installation of minipole of 1.5mt (5”ft) long made by 80mm dia pipe complete with M.S. base plate welded with tie system arrangement at the bottom of the pole / pipe placed at lighting arrangement at the roof providing C.C. foundation (6:3:1) as per GS. Having 600mm x 600mm x 250mm thick C.C. with hard jhama metal by net cemented finish (3mm) thick and properly curing by with water treatment arrangement for the muffing incl. earthing attachment as per G.S,
Supplying and fixing projected single arm bracket with 1.5 mtrs long 40mm dia M.S pipe and 20" long 80mm dia M.S sleev with flange fabrica-ted with pole cap, bolted with pole top for fixing the street light fitting . With two coats of Aluminium paint over two coats of red lead primer after preparation of surface.As per direction of EIC.
S & F 240V, 120 Watt LED Luminaire of Luminous Flux - 16800 lm (Make-Philips, Urban Edge Plus LED Street Light Cat. Ref. -BRP503 LED 168 CW R 3C PSU-S1 /Crompton/Havells/ Bajaj with similar specifications)
S & D 240V, 50 Watt LED Luminaire of Luminous Flux min.-6000 lm (Make-Philips,IP-66protection, city star LED Street Light Cat. Ref. -BRP331 LED 54 CW R5N PC PSU-S1 V1 /Crompton/Havells/ Bajaj with similar specifications)
Wiring by 3x 1.5 sqmm single core PVC insulated copper wire through polythene pipe from loop box to fitting as per GS [Make-Havells/Polycab/KEI]
Supply & Delivery of 1.1 kv grade 2Cx6 sqmm XLPE-armoured AL. cable, as directed by EIC. [Make - Polycab/Havells/RR Kabel/KEI] ( for Compound light)
Supply & Delivery of 1.1 kv grade 4Cx4 sqmm PVC-Copper. cable, as directed by EIC.[Make - Polycab/Havells/RR Kabel/KEI] ( For 3 Ph AC)
Laying of one No. cable upto 35 sqmm in underground trench 460mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed
Laying only Cable upto 50 sqmm through existing RCC/Hume/ GI Pipe/open masonary trench for single, 2, 3, 3½ & 4 core
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required-25mm dia.
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
S&F compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of 2Cx6 sqmm XLPE/PVC armoured cable, as per GS.
Finishing the end of 2Cx6 sqmm XLPE/PVC armoured cable by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials, as per GS.
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 16 sq.mm
Supply of Single industrial box (thick ness of box should not be less than 22 SWG) type luminaire with CRCA body (Make :- Philips -TMC 502 1xT-LED22W Crompton/wipro having similar specification). incl S&D 1x 18watts 4 ft LED tubewith 2100 lumen out put (Make:- Philips, Cat - Mas LED tube 1200 mm 18W865 T8 with heat sink / Crompton /wipro having similar specification) [N/S]
Supply of Twin industrial box (thick ness of box should not be less than 22 SWG) type luminaire with CRCA body (Make :- Philips -TMC 502 2xT-LED22W Crompton/wipro having similar specification). incl S&D 2x 18 watts 4 ft LED tubewith 2100 lumen out put (Make:- Philips, Cat - Mas LED tube 1200 mm 18W865 T8 with heat sink/ Crompton /wipro having similar specification) [N/S]
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length, as per GS.
Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling with HW block and ceiling plates, nipples etc. as required
Supply and fixing 4 ft LED tubewith 2100 lumen out put (Make:- Philips, Cat - Mas LED tube 1200 mm 18W865 T8 with metal heat sink/ Crompton /wipro having similar specification) [N/S]
Supply and delivery of 230V 1200mm sweep ceiling fan (28Watt or less BLDC fan, class of insulation -'B', SERVICE VALUE (CMM/W minimum 6.85, R.P.M. 350(min), THD <10%, supplied with out remote control P.F. not less than 0.9, bult-in 2.5KV SPD with complete accessories. [Make: Crompton /Orients/ RR]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire, as per GS.
Supply and delivery of 230V 450mm sweep 4 blade,1420 RPM,85W,Wall-fan,full metal Body as directed by EIC.[Make: EPC ]
Fixing only above wall-fan on wall by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length, as per GS.
Supply and delivery of 230V 300mm (12") Exhaust fan with all necessary accessories, as directed by EIC. [Make: EPC Heavy Duty, ]
Supply and delivery of 230V 230mm (9") Exhaust fan with all necessary accessories, as directed by EIC. [Make: EPC Heavy Duty, ]
Fixing only 12" exhaust fan after making holes in wall as per GS
Fixing only 9" exhaust fan after making holes in wall as per GS
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) for 30 cm Exhaust fan (12")/ 230mm Exhaust fan (9")
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc., as per GS.
Supply & Fixing of batten holder (CONA make) on existing circular box.
Supply & Fixing of 12 W LED lamp of 100lm/ watt luminious efficiency. [PHILIPS/ Havells/Crompton/SYSKA]
Excavation of soil for installation of Earth Electrode and filling & ramming as per GS For Morum Soil
Connecting the equipments body to earth busbar including S &F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm diax 80 mm long GI bolts, double nuts, double washers incl. S &F 15 mm dia GI pipe protection (1 Mts. long) to be filled withbitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: (ISI Medium)
Supplying & Fixing GI/PVC Modular Switch Board of the following sizes complete with top cover plate flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.2 Module
Supply & Fixing 240 V 6 A Modular type switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required
Supplying & Fixing of PVC water proof type Loop box (Make-Sintex GSJB2520 /Hensel) of size [150X100X50]mm having hinged PVC top cover & 4 mm thick with rubber gasket lining,railway type mechanical locking arrangement, DIN rail & 4pole terminal stud on MS structure as per direction of EIC.Suitable for interconnection by 1.5 sq.mm copper wire among 240V,10/ 6ASP MCB (L&T) -1NO, incl.S&F the individual items incl. the charge of welding the clamp of the loop box with the bar of the pole
Supply &fixing of LED Bulk Head [[Make- Surya/Cat No. Carvinio LED, SLEBH 10W) / Make- Jaquar Cat No. CWLL01v109xx along with 12 W Led Lamp)/Crompton or Equivalent make as per choice of EIC
Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint up to 9 mtr pole One coat of red lead/Zinc chromate priming
1st coat of aluminium paint over 1 coat of RO priming
2nd coat of aluminium paint over 1st coat
Supply, installation, testing and commissioning of LED illuminated sign board made of 1” x1” Iron hollow square bar with sufficient support bar in between the structure and fitted in wall with L channel and angle iron at the front side of the building. Thickness of the board in four sides are 150mm. Back side of the board should be covered 24swg aluminum sheet to resist unwanted water seepage. 3 mm thick ACP sheet fixed at front & four sides with corners are finished by router cutting.The encrypted matter will be printed in front of ACP sheet by laser cutting and the letters of same matters are made by 3mm thick good quality milky white acrylic sheet & pasted in front of laser cuts of ACP sheet. The boards should be fixed on wall by necessary MS angel/ flats. There will be provision for easy opening of the bord during maintenance work. The cost including scaffolding charges(for 2 storied building) and painting with 2 coat of RO primer and one coat of synthetic enamel paint.
Supplying & fixing 18W,2100 lumen Master LED tube with metal heat sink (Philips) with necessary holder for connection incl necessary tie bar arrangement to hold the tubes horizontally.
Supply ,Installation ,Testing & Commissioning of Split type AC machine having colling capacity range (6.6KW-7.0KW),With variable speed Twin rotary compressor ,refrigerant gas R32 BBE star rating-3(EER range 4.24),Air flow range CFM(780-850), P2 capcitor, Indoor and outdoor coils made of copper tube connecting chord with plug top confirming to IS 1391(Part-i &Part-II)with all amendments(Make:-O General(Model No:ASGG24CPAA-B)/Mitsubishi Heavy duty/)
Supply ,Installation ,Testing & Commissioning of Split type AC machine having colling capacity range (5.2KW-5.3KW),With variable speed rotary compressor ,refrigerant gas R32/R410 BBE star rating-3(EER range 3.83),Air flow range CFM(560-600), P2 capcitor, Indoor and outdoor coils made of copper tube connecting chord with plug top confirming to IS 1391(Part-i &Part-II)with all amendments(Make:-O General(Model No:ASGG18CPAA-B)/Mitsubishi Heavy duty/)
S/L of 4 core 2.5 sq.mm 1.1 KV grade unsheathed FR Cu cable with gas line as per direction of EIC for Indoor to Outdoor Communication for Split type AC m/c.(Make:- Polycab/ Havells/ KEI/RR Kable)
Supply & layingSoft Drawn braided hose PVC Pipe 19mm dia for water drain with proper supports & brackets as per direction EIC. (Make: Suprime/Oriplast as per approved by EIC)
S&D of minimum 13KW nominal cooling capacity ceiling suspended [ concealed] Split Air Conditioner with R410A / R407C / R-32 Refrigerant, with single Scroll Compressor / Swing compressor in inverter machine, suitable for operation on 415V,+_ 5% , 50Hz, 3Ph AC Supply. with precharged refrigerant, Wired/ Wireless remote & all other accessories (Make : DAIKIN model FDMF140BRV16/ RZMF140BRV16 / Mitsubishi heavy industries model FDUM125CSV-S6/FDC125CSV-S6 / O General model ARG60F/AOG60F).
Installation testing & commissioning of above AC machines grouted into the wall by fixing the indoor with two number 1 mt long MS equal angle of sizes 40mmX40mmX 6mm to fixed by welding in both end to the existing joist on wall. The indoor unit suspended from this angle support with 4 nos 10mm full threaded suspender bolt with double nut & spring washer. Out door unit will be fixed on wall with two number 1.2mt long MS "C" channel of sizes 80mmX40mmX 6mm by one side grouted into the wall as per direction of EIC.
Supply & Laying of Refrigerant Copper pipe of following diameter for connecting of Indoor to Outdoor unit, along with drip resistant nitrile rubber insulation with double insulating wrapping tape to avoid dripping of condensate water:- Discharge Line 6.35mm dia, min. thickness 0.8m with 9mm thick nitrile insulation. (Make : Rajco / Royku).
Discharge Line 9.5mm dia, min. thickness 0.8mm with 9mm thick nitrile insulation. (Make : Rajco / Royku).
Suction Line 15.88mm dia, min. thickness 0.99mm with 9mm thick nitrile insulation. (Make : Rajco / Royku).
Suction Line 19.05mm dia, min. thickness 0.99mm with 9mm thick nitrile insulation. (Make : Rajco / Royku).
Wrapping the copper pipe with insulation & electric cable by S/F 26SWG Aluminimum sheet to make it weather & vermin proff. 6.35 / 9.5mm dia with 9mm thick nitrile insulation, 15.88/ 19.05mm dia with 9mm thick nitrile insulation & 6core 2.5Sqmm Copper cable.
Supply & laying drain Water piping work with 25 mm dia Schedule 40 PVC/ UPVC hard pipes (Finolex / Ashirbad / Supreme) incl. fitting , accessories bends, elbows, tees, flanges, tapings, etc. insulated with 9mm. thick nitrile rubber tube insulation.
S&F flexible canvas connection for indoor to duct/ air terminal for 13KW indoor
SITC of Powder Coated Al. Grill without VCD suitable size (Make:Systemair / Primier)
S & providing drop ceiling to cover the indoor units & supply air duct including the cost of 3mm thick ACP sheet as per manufacturer's specification on the frame work fabricated from Aluminium hollow rectangular section of size 50mm x 25mm (2mm thick) & duly suspended by Aluminium hollow rectangular section of size 50mm x 38mm (2mm thick) and silicon sealent complete in all respect including making trap door arrangement as per direction of EIC. (Make:Aludecor/Pratapbond)
Supplying, fabrication & fixing M.S U-channel of 6 mm thick of size (80mm x 40mm x 40mm) for making platform for installation of outdoor unit of 4 TR Concealed split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1.5:3) etc. fabricated with horizontal angle of 20mm x 20mm x 6mm including supporting angle 40mm x 40mm x 6mm in each platform in outer edge for transmitting the load centrally through 2 Nos. (40mm x 40mm x 6 mm) Angle inserted into the existing wall. Area of the platform is 2.5Mtr. x 1.2Mtr. or as per direction of EIC.
Dismantling of the existing split type AC machine (1.5/2.0 Ton) along with the outer cover carefully by skilled labour from its position for necy. Servicing /overhauling incl cleaning the dust ete. due to dismantling operation and also uninstalled & removing of unused old damaged windows AC unit from wall and covered the vacant space by ACP board with necessary dimension with good mending and damages as per direction of EIC as per direction of E.I.C.
Re-installation of the dismantelled AC units at suitable location after making holes in wall by expert labour also mending good after complete the work. Connecting the pipe line testing the leak by gas pressure (minimum 400 PSI ) and vacuuming the unit properly (Minimum -30 PSI), hold the vacuum up to 48 hours, after release the gas testing the Split type Room Air conditioner incl. gas charging as per requirement and replacement of existing capacitor with metal body P2 capacitor with supply & fitting adjustable powder coated painted heavy duty iron bracket. as per direction by EIC.
Supply & Delivery of Infra Red Thermal Imaging Camera (Make- Fluke TiS -20+) having following specifications: IFOV (spatial resolution-7.6 mRad, Infrared resolution-120 x 90 (10,800 pixels), Temperature measurement range - -20 °C to 400 °C, Mini USB used to transfer image to PC, Should withstand drop up to 1 meter, IP 54 enclosure rating, Warranty Period- 02(Two) years.LCD touch screen.
N.B: i) Payment will be made after availability of fund from concern Department. ii) Payment will be made as per P.W.D norms.
RIK ENTERPRISE (BID ID -6183342)
M/S. S. D. CHATTERJEE AND CO. (BID ID -6183391)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .